VOLTAGE MEASUREMENTS 

Once the unit is properly wired, measure the unit supply 
voltage.  Voltage  must  fall  within  the  voltage  utilization 
range given in 

.

Chart 3

WIRING

Cord connection to a wall socket is not permitted for 265V
units.   All 265V units must be hard wired using the hard 
wire  kit  or  make  use  of  the  plug  in  receptacle  in  the 
standard subbase. 

230~208V  units are equipped with LCDI

 

power cords and 

can open the electrical circuit to the unit. In the event the 
unit does not operate, check the reset button located on or 
near  the  head  of    the  power  cord  as  part  of  the  normal 
trouble shooting procedure.

WARNING

THIS  AIR  CONDITIONER  IS  NOT  MEANT  TO  PROVIDE 
UNATTENDED COOLING  OR LIFE SUPPORT  FOR  PERSONS 
OR ANIMALS WHO ARE UNABLE  REACT TO THE FAILURE OF 
THIS  PRODUCT. 
THE  FAILURE  OF  AN  UNATTENDED  AIR  CONDITIONER  MAY 
RESULT IN EXTREME HEAT   IN   THE   CONDITIONED   SPACE 
CAUSING  OVERHEATING  OR    DEATH    OF  PERSONS  OR 
ANIMALS.

Operating

 

Voltage

Rating

230

/

208

265

Unit

 

Voltage

Minimum

187

238

Voltage

 

Utilization

 

Range

Maximum

253

292

Chart 3 

-

Operating

 

Voltage

-6-

RED

-

24VAC

Purple

-

LS

 

control

Green

-

High

 

fan

 

speed

Blue

-

Reversing

 

valve

Yellow

-

Compressor

White

-

Heater

Orange

-

Low

 

fan

 

speed

Black

-

Common

 

ground

R

 

LS

 

GH

 

B

 

Y

 

W

 

GL

 

C

R

 

LS

 

GH

 

B

 

Y

 

W

 

GL

 

C

WALL

 

MOUNTED

 

THERMOSTAT

 

INTERFACE

Thermostat

WARNING

TO AVOID THE RISK OF PROPERTY DAMAGE, PERSONAL 
INJURY OR 

,

 

USE ONLY COPPER CONDUCTORS.

FIRE

WARNING

TO  AVOID  PROPERTY  DAMAGE,  PERSONAL  INJURY  OR 
DEATH  DUE  TO  ELECTRICAL  SHOCK,  DO  NOT  USE  AN 
EXTENSION CORD WITH THIS UNIT.

WARNING

TO AVOID  THE  RISK  OF  PROPERTY  DAMAGE,  PERSONAL 
INJURY  OR  FIRE

 

DO  NOT  INSTALL  WITH  POWER  CORD 

STRETCHED  OR  UNDER  A  STRAIN  AS  THIS  MAY  CREATE 
LOOSE PLUG/RECEPTACLE CONNECTION.

WARNING

TO  AVOID  THE  RISK  OF  PERSONAL  INJURY,  WIRING  TO  THE 
UNIT MUST BE PROPERLY POLARIZED AND GROUNDED.

Fig

 

9

 

wall

 

mounted

 

thermostat wiring

Fig 8 Receptacles

/

Sub

-

bases 

NOTE: See the “

"

use the thermostat.

Remote

 

Thermostat

 

Change instructions before 

 

Tandem

230

/

208V

 

15Amp

265V

 

15Amp

Perpendicular

230

/

208V

 

20

 

Amp

 

265V

 

20

 

Amp

 

Large

 

tandem

230

/

208V

 

30Amp

265V

 

30Amp

WARNING

HIGH VOLTAGE 

DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING 

THIS UNIT. MULTIPLE POWER SOURCES BE PRESENT, FAILURE 

TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY 

OR DEATH.

DO NOT SERVICE THIS UNIT WITHOUT FIRST SHUTTING OFF THE 

POWER  TO  THE  UNIT  FROM  THE  CIRCUIT  BREAKER  AND/OR 

REMOVING THE UNIT CORD SET PLUG FROM THE WALL OUTLET.

Summary of Contents for 2PTC12A-3.0

Page 1: ...MODELS 2PTC12A 3 0 2PTH15A 5 0 Before using your air conditioner please read this manual carefully and keep it for future reference along with your receipt USER MANUAL PACKAGED TERMINAL AIR CONDITION...

Page 2: ...nt the right is reserved to change specifications and design without notice IMPORTANT NOTE TO THE OWNER This manual is to be used by qualified professionally trained HVAC technicians only The manufact...

Page 3: ...ation Protection Automatically protects the compressor if heat pump is operated with high indoor coil temperatures Power to the outdoor fan and the compressor are turned off if the indoor coil gets to...

Page 4: ...at Electric And Non Electric Sub Base Kit IR REMOTE CONTROLLER NOTE Consult sales literature for the appropriate voltage and amperage selections if applicable 3 R LS GH B Y W GL C WALL MOUNTED THERMOS...

Page 5: ...ion of this unit is described in the following sections Following the steps in the order presented should ensure proper installation Front and discharge grille Electric heater Indoor Fan Display Modul...

Page 6: ...assis Installation View 2 3 Secure the chassis to the wall sleeve using three screws on each side of the chassis to ensure a proper seal between the chassis and the wall sleeve The screws are supplied...

Page 7: ...High fan speed Blue Reversing valve Yellow Compressor White Heater Orange Low fan speed Black Common ground RLSGHBYWGLC R LS GH B Y W GL C WALLMOUNTEDTHERMOSTATINTERFACE Thermostat WARNING TO AVOID TH...

Page 8: ...ent time indicator TEMPsetting button This button is used to sent the room temperature Pressing of or button the temperature setting is increased or decreased FAN SPEED button Press this button to sel...

Page 9: ...ODE button select the operation mode cool fan heat Press or button to set your desired temperature The setting temperature range is 61 88 F 16 31 C Press the FAN SPEED button to set your desired air f...

Page 10: ...Front Back MAINTENANCE AND CLEANING AIR DISCHARGE GRILLE The discharge grille can be adjusted to expel air at either a 15 or 55 angle Discharge Grille Orientation Options 15 Discharge Air 55 Discharge...

Page 11: ...lastic Creating this seal prevents water from entering the control area or the fan motor and damaging the unit 2 Spray condenser coil and base pan down with water Next spray a mild biodegradable deter...

Page 12: ...outside of the unit Air sounds The fan cycle switch sets the operational mode of the fan In the ON position the fan will run continuously whenever power is applied in this mode In the AUTO position t...