WMD-06 Motorized electromechanical swing gate  

APPENDIX A. Control signal algorithm in pulse control mode  

The command is a signal active front (signal transfer from the high level to the low level) at any of 
the contacts at presence of the corresponding signal levels at the other contacts. 

 

Note: 

RC panel: 

  active front – pressing of the relevant button, 

  low level – the relevant button has been pressed, 

  high level – the relevant button has not been pressed. 

The following commands can be formed by sending a low-level signal to 

Unlock

 

A

Stop

 and 

Unlock

 

B

 contacts and 

GND

 contact on the 

XT2

 terminal block relative to the 

GND

 contact: 

Always locked (locked for entry and exit) 

- active front is at the contact 

Stop

 while there is a high 

level at the contacts 

Unlock

 

A

 and 

Unlock

 

B

. Both passage directions are locked at this command. 

Single passage in the direction 

А

 (open for passage of one person in the direction 

А

- active 

front is at the contact 

Unlock

 

A

 while there is a high level at the contacts 

Stop

 and 

Unlock

 

B

. At this 

command the passage direction 

А

 opens either for 5 sec. or until the passage has been made in 

this direction or until the “

Always locked”

 command, and the status of the passage direction 

В

 does 

not change at that. The command is ignored if at the moment of its receipt the status of the 
passage direction 

А

 is “

Always free

”. 

Single passage in the direction 

В

 (open for passage of one person in the direction 

В

- active 

front is at the contact 

Unlock

 

B

 while there is a high level at the contacts 

Stop

 and 

Unlock

 

A

. At this 

command the passage direction B opens either for 5 sec. or until the passage has been effected in 
this direction or until the command “

Always

 

locked

”, and the status of the passage direction A does 

not change. The command is ignored if at the moment of its receipt the status of passage direction 
B is “

Always

 

free

”. 

Free passage in the direction 

А

 (open for free passage in the direction 

А

- active front is at the 

contact 

Unlock

 A

 

while there is a low level at the contact 

Stop

 and a high level at the contact 

Unlock

 

B

, or active front is at the contact 

Stop

 while there is a low level at the contact 

Unlock

 

A

 and a high 

level at the contact 

Unlock

 

B

. At this command the passage direction 

А

 opens until the command 

Always locked

” is received; the status of the passage direction 

В

 does not change at that. 

Free passage in the direction 

В

 (open for free passage in the direction 

В

- active front is at the 

contact 

Unlock

 

B

 while there is a low level at the contact 

Stop

 and a high level at the contact 

Unlock

 

A

, or active front is at the contact 

Stop

 while there is a low level at the contact 

Unlock

 

B

 and a high 

level at contact 

Unlock

 

A

. At this command the passage direction 

В

 opens until the “

Always

 

locked

” 

command is received; the status of the passage direction 

А

 does not change at that. 

APPENDIX B. Control signal algorithm in potential control mode  

 

Note: 

For ACS controller outputs: 

  high level – either contacts of the output relay are broken or the output transistor is closed,

  low level – either contacts of the output relay are closed or the output transistor is open. 

Both directions are locked (locked for entry and exit)

 - there is a high level at the contacts 

Unlock

 

A

 and 

Unlock

 

B

, or a low level at the contact 

Stop

. The both passage directions are locked 

at this command. 

The direction 

А

 is open (open for passage in the direction 

А

)

 - there is a low level at the contact 

Unlock

 

A

 while a high level is present at the contacts 

Stop

 and 

Unlock

 

B

. At this command the 

direction 

А

 is opened till the low-level signal removal from the contact 

Unlock

 

А

 or until the command 

Both

 

directions

 

locked

” is received. The status of the direction 

В

 does not change at that. 

The direction 

В

 is open (open for passage in the direction 

В

)

 - there is a low level at the contact 

Unlock

 

В

 while there is a high level at the contacts 

Stop

 and 

Unlock

 

А

. At this command the direction 

B is opened till the low-level signal removal from the contact 

Unlock

 

B

 or until the command “

Both

 

directions

 

locked

” is received. The status of the direction A does not change at that. 

 

19

Summary of Contents for WMD-06

Page 1: ...ASSEMBLY AND OPERATION MANUAL WMD 06 Motorized Electromechanical Swing Gate ...

Page 2: ...WMD 06 Motorized electromechanical swing gate Assembly and Operation Manual ...

Page 3: ...QUIREMENTS 12 7 1 Installation safety 12 7 2 Operation safety 12 8 ASSEMBLY AND INSTALLATION 13 8 1 General recommendations 13 8 2 Tools and equipment required for installation 13 8 3 Appropriate cable length 13 8 4 Installation procedure 13 9 OPERATION 16 9 1 Power up 16 9 2 Pulse control mode 17 9 3 Potential control mode 17 9 4 Emergency situations 18 9 5 Troubleshooting 18 10 TRANSPORTATION AN...

Page 4: ...sed as a separate device It is recommended to define the number of swing gates necessary to secure fast and convenient passage in accordance with throughput rate see Section 3 For example it is recommended to install one turnstile per 500 people on the basis of maximum working load of 12 persons min 2 OPERATING CONDITIONS The swing gate with regard to resistance to environmental exposure complies ...

Page 5: ...0 mm passageway width is chosen by the customer RC panel with cable 1 SW1 5 Allen wrench 1 Gate mounting kit PFG IH 10 SORMAT Finland anchor bolt with washer and M10 nut 3 Panel installation kit M10 35 bolt 4 M10 nut 4 Spring washer 4 Expanded washer 8 Plastic bushing 4 Operational documentation Certificate 1 Assembly and operation manual 1 Template for gate installation 1 Package Box 1 gate post ...

Page 6: ...electromagnetic stopper unit bearing units drive control board 6 RC panel is included into delivery set 17 The gate is operated with 24 V DC voltages via cable 13 The control board is installed inside the gate post The control board overview is shown in Fig 3 The control board contains XT1 and XT2 terminal blocks are designed for power supply input output of control signals and indication Marking ...

Page 7: ...base 2 housing 3 cover 4 glass panel 5 metal ring 6 control board 7 rotary support 8 M3 screw 3 pcs 9 anchor stud bolt 10 M10 nut 11 washer 12 plastic ring 13 power cable 14 control cable from RC panel WRC device ACS controller 15 decorative plate 16 screw M4 17 RC panel 6 ...

Page 8: ...trol board Terminal block No Item Designation 1 24 V 2 GND External power supply connection 3 NO 4 C 5 NC Light A relay contacts remote indicator connection for direction А 6 NO 7 C 8 NC Light B relay contacts remote indicator connection for direction В 9 12 V Power supply positive terminal of RC panel 10 GND Power supply negative terminal 11 Common Common contact for PASS А PASS В signals 12 Pass...

Page 9: ...C panel features three control buttons to set swing gate passage modes The buttons LED indicators are located above The STOP button in the middle serves for setting the Always locked operating mode the RIGHT and LEFT buttons for allowing passage in the chosen direction The RC panel features a built in piezoelectric buzzer for audio signals generation The standard orientation of the RC panel in rel...

Page 10: ...tput signals from rotation sensor Upon received data the microcontroller generates commands for the gate control mechanism and also signals for connected external indication devices indication on the RC panel Led A Led Stop and Led B signals on the performed rotation of the swing panel on outputs Pass А and Pass В 5 4 1 Inputs for control devices connection The swing gate can be operated with RC p...

Page 11: ...be used as a control element If the Fire Alarm input is not used it is necessary to install a jumper between Fire Alarm and GND contacts on the XT2 terminal block The jumper is installed by default The gate can operate in two control modes pulse and potential Control mode is set by installing or removing the jumper on Imp Pot connector If the jumper is installed the gate operates in the pulse cont...

Page 12: ...l specifications maximum switching voltage 42 V DC maximum switching current 0 25 А closed contact resistance max 0 15 Ohm 5 4 3 Outputs for external indication connection Light A and Light B outputs are used for external indication connection and are basically relay changeover contacts see Fig 9 Each output has full contact set on XT1 terminal block normally open NO normally closed NC and common ...

Page 13: ...eing damaged during transportation and storage The box 1 contains gate post and RC panel the box 2 contains a swing panel Boxes have the marking of the packed product and additional marking in accordance with design documents and delivery set Dimensions L W H box 1 121 37 22 cm box 2 for AGG 650 glass panel 96 12 90 cm box 2 for AGG 900 glass panel 121 12 90 cm Gross weight box 1 max 36 kg box 2 f...

Page 14: ... Appropriate cable length Maximum acceptable length of RC panel ACS controller cable 30 m Maximum acceptable length of power supply cable depends on its cross section and shall be as following for 1 5 mm2 cross section AWG 15 max 10 m for 2 5 mm2 cross section AWG 13 max 20 m 8 4 Installation procedure Attention The manufacturer shall not be liable for any damage caused in the result of improper i...

Page 15: ...e the metal ring 5 Put a washer 11 on each anchor and fix the gate post with three M10 nuts 10 9 Connect power cable and control cable to XT1 and XT2 terminal blocks of the control board 6 Put cables as shown in Fig 3 10 If needed connect Fire Alarm emergency unlocking device If the device is not connected a wire jumper shall be installed on Fire Alarm and GND contacts on XT2 terminal block 11 If ...

Page 16: ... of the swing gate 24V DC 4А А3 Power supply unit of remote indicators A4 A5 Remote indicators 2 pcs A6 1 ACS controller input A6 2 ACS controller output A7 Device sending Fire Alarm FA emergency unlocking signal A8 RC panel PERCo H6 4 A9 WRC device 1 Wire jumper Installed when the Fire Alarm device А7 is not connected Installed on default Not included in standard delivery set 15 ...

Page 17: ...y cause mechanical damage or corrosion of the surfaces 9 1 Power up Attention Make sure that there are no obstacles in the rotation zone and passageway of the gate before starting the power up Perform the following actions in order 1 Connect the power cable to the electric socket with voltage and frequency set in the certificate of the power supply unit 2 Turn the power supply unit on 3 The swing ...

Page 18: ...c in the Single passage in chosen direction mode Timing starts after the swing panel rotates 85º After that the swing panel moves to Closed position and locks the swing gate switches to the Always locked mode Single passage in chosen direction mode can be changed to Free passage mode in the same direction or to Always locked mode Always free mode can be changed to Always locked mode only 9 3 Poten...

Page 19: ...t the PERCo Technical Support Department Table 6 Troubleshooting Fault Possible cause Remedy When powered up RC panel indication does not work No supply voltage on control board De energize power supply unit Remove the cover and housing of the gate Check the power cable and its connection to the XT1 terminal block The gate cannot operate in one of the directions RC panel indication is on Control s...

Page 20: ...at the contact Unlock A while there is a low level at the contact Stop and a high level at the contact Unlock B or active front is at the contact Stop while there is a low level at the contact Unlock A and a high level at the contact Unlock B At this command the passage direction А opens until the command Always locked is received the status of the passage direction В does not change at that Free ...

Page 21: ...PERCo Polytechnicheskaya str 4 block 2 194021 Saint Petersburg Russia Tel 7 812 247 04 64 E mail export perco com support perco com www perco com ...

Page 22: ...www perco com ...

Reviews: