Commissioning
4
Commissioning
4.1
Introduction
Components
To commission the module, you will require the following components:
•
WCS-PNG410 interface module
•
Cordset from the interface module to the read head
•
Connector for the PROFINET connection to the interface module
•
Ethernet cable
•
10 VDC...30 VDC voltage supply
GSDML file (the GSDML file can be downloaded free of charge from our website
www.pepperl-fuchs.com).
Connecting the Interface Module
To ensure that the assembly functions correctly, you must carry out the following steps during
commissioning:
1.
Assign a PROFINET address.
2.
Assign a PROFINET device name.
3.
Connect the module to PROFINET using the interface labeled "RJ45 PROFINET IO."
4.
For information on commissioning the process device (read head), please refer to its manual.
5.
Ground the DIN mounting rail onto which the assembly is clipped.
6.
Connect the direct current to the terminals provided.
7.
Use any programming tool for project planning. The GSDML file can be downloaded from our
website: www.pepperl-fuchs.com. Simply enter the product name or item number in the
product/keyword field and click "Search."
Warning!
Danger to life due to defective work
Errors during installation and commissioning can cause life-threatening injuries and significant
property damage.
•
Installation and commissioning must be carried out only by trained personnel in accor-
dance with safety regulations.
Note
On delivery, the module does not yet have an IP address. In normal operation,
the IP address is usually assigned to the module by the PROFINET IO
controller (PLC).
Note
On delivery, the interface module does not yet have a device name. The device
name is assigned to the interface module via the configuration software.
Note
A more detailed description of the individual steps is provided on the following
pages.