AS-i/CC-Link Gateway
Connections, Displays and Operating Keys
Subject to reasonable modifications due to technical advances.
Copyright Fuchs, Printed in Germany
Fuchs Group · Tel.: Germany (6 21) 7 76-0 · USA (3 30) 4 25 35 55 · Singapore 7 79 90 91 · Internet http://www.pepperl-fuchs.com
is
s
u
e
d
a
te
1
0
.1
2
.2
0
0
2
15
PRG ENABLE Automatic address programming enabled.
Exactly one slave is missing in protected operating mode. The
slave can be replaced by another slave of the same type with ad-
dress zero. The master addresses the new slave to the faulty ad-
dress and thus eliminates the configuration error.
PRG MODE
The AS-i master is in configuration mode.
5.3.2
Push-Buttons
The push-buttons cause following:
mode
Switching between the configuration mode and the protected operating
mode and saving the actual AS-i configuration as the nominal configu-
ration.
set
Selection and assigning the address to a slave.
The detailled description is described in chapter 6.
By IP65 devices the push-buttons under the top of the housing to prevent liquids
from entering. For operation of the device the top of the housing is to be screwed
off.
Summary of Contents for VBG-CCL-G4F
Page 78: ...123904 12 02 00...