![Pepperl+Fuchs VAG-PB-G4F-R4 Manual Download Page 49](http://html1.mh-extra.com/html/pepperl-fuchs/vag-pb-g4f-r4/vag-pb-g4f-r4_manual_1527742049.webp)
AS-i/PROFIBUS Gateway
Appendix: AS-i Slave Lists and Data Telegrams
Subject to reasonable modifications due to technical advances.
Copyright Fuchs, Printed in Germany
Fuchs Group · Tel.: Germany (6 21) 7 76-0 · USA (3 30) 4 25 35 55 · Singapore 7 79 90 91 · Internet http://www.pepperl-fuchs.com
is
s
u
e
d
a
te
1
2
.1
0
.1
9
9
9
49
11
Appendix: AS-i Slave Lists and Data Telegrams
11.1
AS-i Slave Lists
The AS-i Slave lists LPS, LDS, LAS, LCS, LOS and the configuration error list are built
up as follows:
Meaning of the Lists:
LPS List of Projected Slaves
LDS List of Detected Slaves
LAS List of Activated Slaves
LCS List of Corrupted Slaves
List of those slaves, that have caused a short-time configuration error.
LOS List of Off-line Slaves
List of those slaves, with that in case of configuration error the AS-i Master
shall switch to the Off-line phase.
configuration error list
A bit in the configuration error list is set, if the concerning bit in the LPS (List
of Projected Slaves) differs from the one in the LDS (List of Detected Slaves)
or if the projected AS-i configuration data (I/O- and ID-code) of the concern-
ing AS-i slave differ from the detected configuration in the AS-i circuit.
11.2
Execution Control Flags
The execution control flags are transmitted in the diagnosis telegram, if the gateway
is operated in the professional mode.
When set, the individual bits have the following meaning:
byte
0
1
bit
0
1
2
3
4
5
6
7
0
1
2
3
4
5
6
7
slave
-
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
byte
2
3
bit
0
1
2
3
4
5
6
7
0
1
2
3
4
5
6
7
slave
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
bit 0:
config_OK
no configuration error
bit 1:
LDS.0
slave with address 0 present
bit 2:
Auto_Address_Assign
automatic programming permitted
bit 3:
Auto_Address_Available
automatic programming available
bit 4:
Configuration_Active
configuration mode active
bit 5:
Normal_Operation_Active
normal operation active
bit 6:
AS-i power failure