Commissioning
4
Commissioning
4.1
Preparation
Unpacking the Device
1.
Check the packaging and contents for damage.
In the event of damage, inform the shipping company and notify the supplier.
2.
Check the package contents against your order and the shipping documents to ensure that all
items are present and correct.
Should you have any questions, direct them to Fuchs.
3.
Retain the original packaging in case the device is to be stored or shipped again at a later date.
4.2
Configuring the AS-Interface Safety Monitor
For details of necessary organizational measures affecting configuration of the safety monitor,
please refer to the documentation for the safety monitor.
Safety Classification
The module contains two independent, redundant input channels. If both input channels are
used, the module is suitable for use up to category 4/PL e in accordance with ISO 13849-1, or
SIL 3 in accordance with EN/IEC 61508 and EN/IEC 62061. In this case, the monitor must be
programmed so that dual-channel switching is monitored.
If a single-channel switch is used, the module is suitable for use up to category 2/PL c in accor-
dance with ISO 13849-1, or SIL 1 in accordance with EN/IEC 61508 and EN/IEC 62061. Only
tested and certified power supplies with safe isolation may be used to supply power. These
power supplies must have PELV voltage in accordance with EN 50295/IEC 62026-2, and a
minimum MTBF of 50 years. The power supplies are designed to exclude a short circuit
between the primary and secondary sides.
4.3
Installation
For installation of the module a suitable top hat DIN rail in accordance with DIN 50022 is recom-
mended.
4.4
Addressing modules
Addressing of the module is performed by means of a manual addressing device or with an AS-
Interface master. If a manual addressing device is used, it should be connected and addressed
to the addressing socket of the module (identified with ADDR) using the addressing cable
included with delivery. Addresses from 1 to 31 can be assigned. The state as supplied is
address 0.
4.5
Operational Testing
Perform function tests as part of the installation by activating the safety function. The opera-
tional test uncovers all existing faults at the time of installation. Because the safe inputs are
monitored for crossed circuits, it is not necessary to test for short circuits in the cabling.