VAA-2E-KE1-S

Commissioning

4

Commissioning

4.1

Preparation

Unpacking the Device

1.

Check the packaging and contents for damage.

 In the event of damage, inform the shipping company and notify the supplier.

2.

Check the package contents against your order and the shipping documents to ensure that all 
items are present and correct.

 Should you have any questions, direct them to Fuchs.

3.

Retain the original packaging in case the device is to be stored or shipped again at a later date.

4.2

Configuring the AS-Interface Safety Monitor

For details of necessary organizational measures affecting configuration of the safety monitor, 
please refer to the documentation for the safety monitor.

Safety Classification

The module contains two independent, redundant input channels. If both input channels are 
used, the module is suitable for use up to category 4/PL e in accordance with ISO 13849-1, or 
SIL 3 in accordance with EN/IEC 61508 and EN/IEC 62061. In this case, the monitor must be 
programmed so that dual-channel switching is monitored.

If a single-channel switch is used, the module is suitable for use up to category 2/PL c in accor-
dance with ISO 13849-1, or SIL 1 in accordance with EN/IEC 61508 and EN/IEC 62061. Only 
tested and certified power supplies with safe isolation may be used to supply power. These 
power supplies must have PELV voltage in accordance with EN 50295/IEC 62026-2, and a 
minimum MTBF of 50 years.  The power supplies are designed to exclude a short circuit 
between the primary and secondary sides.

4.3

Installation

For installation of the module a suitable top hat DIN rail in accordance with DIN 50022 is recom-
mended.

4.4

Addressing modules

Addressing of the module is performed by means of a manual addressing device or with an AS-
Interface master. If a manual addressing device is used, it should be connected and addressed 
to the addressing socket of the module (identified with ADDR) using the addressing cable 
included with delivery. Addresses from 1 to 31 can be assigned. The state as supplied is 
address 0.

4.5

Operational Testing

Perform function tests as part of the installation by activating the safety function. The opera-
tional test uncovers all existing faults at the time of installation. Because the safe inputs are 
monitored for crossed circuits, it is not necessary to test for short circuits in the cabling.

Summary of Contents for VAA-2E-KE1-S

Page 1: ...VAA 2E KE1 S Original Instructions Manual...

Page 2: ...ion as well as the supplementary clause Expanded reservation of proprietor ship Worldwide Pepperl Fuchs Group Lilienthalstr 200 68307 Mannheim Germany Phone 49 621 776 0 E mail info de pepperl fuchs c...

Page 3: ...ilure on Demand Calculation 8 3 Product Description 9 3 1 AS Interface Safety at Work VAA 2E KE1 S 9 3 2 Connections and Indications 9 3 3 Interface Properties 10 4 Commissioning 12 4 1 Preparation 12...

Page 4: ...VAA 2E KE1 S Contents 4 182314 2020 09 8 Annex B 21 8 1 Summary of the Requirements for Categories acc to ISO 13849 1 21 8 2 Certificates 22...

Page 5: ...able EU type examination certificate EU declaration of conformity Attestation of conformity Certificates Control drawings Instruction manual Other documents 1 2 Target Group Personnel Responsibility f...

Page 6: ...ons 1 4 Declaration of Conformity This product was developed and manufactured in line with the applicable European standards and directives The product manufacturer Pepperl Fuchs Group 68307 Mannheim...

Page 7: ...cked prior to initial commissioning The safety monitor PL cate gory or SIL must as a minimum comply with the PL category or SIL required by the applica tion Cabling Requirements The requirements set o...

Page 8: ...on the PFD values for all components used within this function must be taken into consideration In the case of dual channel applications the AS Interface safe input module does not significantly contr...

Page 9: ...so an LED for monitoring AS Interface communication and to display that the module has the address 0 If single channel positive action mechanical switches are connected the module can be graded up to...

Page 10: ...le terminals One or more mechanical switches can be connected in series per channel Figure 3 1 Two mechanical switches or one dual channel switch If only one single channel switch is to be used input...

Page 11: ...annels that individually meet the requirements of category 4 PL e in accordance with EN ISO 13849 1 Crossed Circuit Monitoring The inputs are monitored for inter crossed circuits The crossed circuit m...

Page 12: ...is used the module is suitable for use up to category 2 PL c in accor dance with ISO 13849 1 or SIL 1 in accordance with EN IEC 61508 and EN IEC 62061 Only tested and certified power supplies with saf...

Page 13: ...ctivating operating modes for the inputs is not possible The parameters in the AS interface may influence the performance of the outputs The chapter Operating principle contains a more accurate descri...

Page 14: ...182314 2020 09 14 VAA 2E KE1 S Maintenance and Repair 5 Maintenance and Repair 5 1 Maintenance and repair Regular function tests may be necessary depending on the safety category...

Page 15: ...26 5 31 6 V PELV from AS Interface Rated operating current 70 mA Protection class III Number Type 2 safety related inputs for mechanical contacts cross circuit monitored 2 single channel contacts up t...

Page 16: ...5 1 kV asymmetric criterion B EN 61000 6 4 Emitted interference EN 61000 6 4 2001 Insulation coordination EN 50178 1998 Functional safety Cat 4 PL e acc to EN ISO 13849 1 2015 SIL 3 acc to IEC 62061...

Page 17: ...cting two independent mechanical position switches of Category 2 Figure 7 1 7 3 Category 3 The occurrence of a fault must not lead to the loss of the safety function Connection of two dependent mechan...

Page 18: ...nels are needed to achieve a category 3 safety function Figure 7 4 The following function blocks can be parameterized to achieve safety category 3 in this applica tion during operation of the AS Inter...

Page 19: ...switch cannot be excluded two dependent mechani cal switches must be used for each channel To detect a dangerous accumulation of faults the safety function must be tested The test intervals must be ad...

Page 20: ...VAA 2E KE1 S Annex A Dual channel dependent Dual channel force guided Danger The function block Dual channel independent must not be used Warning The cable length between the module and the sensor is...

Page 21: ...est intervals The loss of the safety function is detected by the test Via the structure 3 The requirements of B must be ful filled and principles that are proven for safety engineering purposes must b...

Page 22: ...182314 2020 09 22 VAA 2E KE1 S Annex B 8 2 Certificates Approvals in accordance with EN ISO 13849 1 EN IEC 62061 and EN IEC 61508...

Page 23: ...VAA 2E KE1 S Annex B 182314 2020 09 23...

Page 24: ...Pepperl Fuchs Quality Download our latest policy here www pepperl fuchs com quality www pepperl fuchs com Pepperl Fuchs Subject to modifications Printed in Germany 182314 DOCT 0694D...

Reviews: