SU17 Series Programming

Sensitivity Adjustment

The SU17 Series offers automatic sensitivity/hysteresis adjustment for the following 

three distict applications:

•  Contrast Sensing:

   for distinguishing 2 targets of different material, color, or 

distance (2 teachings required)

•  Position Sensing:

  for sensing the leading edge of a target

•  Max. Sensitivity:

  for maximizing the thru scan sensitivity and scanning distance

Contrast

Positioning

Maximum 

Sensitivity

Step

1

2

3

4

    tuning

completed

Target

position

Operation

Place the

first target

"A" to the

position

Place the

second target

"B" to the

position

Switch the

operation

mode selec-

tor to "SET"

Switch the

operation

mode selec-

tor to "RUN"

Push the

tuning button

once (first

teaching)

Push the tu-

ning button

once

(second

teaching)

Indicator status

Digital

Red LED Green LED

"1" will be

indicated

for step 1

"2" will be

indicated

for step 2

Margin level in scale

of 1-9 will show

Level of light reception

will show in scale of 0-9

OFF

OFF

OFF

Depends

on LO/DO

setting

OFF

FLASH

ON

Should be

ON

for stable

operation

Alarms for teaching errors

Insufficient light

Insufficient contrast

Digital

Red

LED

Green

LED

Digital

Red

LED

Green

LED

"E"

for

error

will

flash

"E" will

con-

tinue to

flash.

Output

is locked

FLASH

"E" for error

will be ON

"E" will

continue

FLASH

FLASH

FLASH

OFF

OFF

ON

ON

OFF

OFF

"A"

"B"

to be  "ON"

Output is

locked

SET

RUN

SET

RUN

Step

1

2

3

   

 tuning

completed

Target position Operation

Push the

tuning

button

once

Indicator status

Digital

Red LED Green LED

Level of light reception

will show in scale of 0-9

OFF

OFF

Depends

on LO/

DO

setting

OFF

FLASH

Should be

ON

for stable

operation

Alarms

Insufficient light

Digital

Red

LED

Green

LED

"E" for error

will flash

FLASH FLASH

FLASH OFF

"2" will

show but

do not push

the tuning

button again

"1" will be

indicated

for step 1

Switch the

operation

mode selec-

tor to "SET"

Switch the

operation

mode selec-

tor back to

"RUN"

Position the

target

SET

RUN

SET

RUN

Step

1

2

3

Operation

Push the tuning

button for a

minimum of

3 seconds

Indicator status

Digital

Red LED Green LED

OFF

ON

OFF

"H" will show

"1" will be indicated

for step 1

Switch the

operation

mode selector

back to "RUN"

ON

Level of light reception

will show

Switch the ope-

ration mode

selector to "SET

"

SET

RUN

SET

RUN

Depends

on LO/

DO

setting

Should be

ON

for stable

operation

Note 1

The SU17 sensor is preset in the «RUN», Light Operate «LO» and «Maximum 

Sensitivity» before delivery.

Note 2

The alarm is locked on (output locked off) until the sensor is re-taught. The 

«E» display indicates that the fiber optic/target is not positioned correctly. 

Please confirm that the standoff distance and angle of the fiber optic is in 

accordance with the fiber optic specification, then re-teach the SU17.