USB Intrinsic Safety Barrier

Installation and Commissioning

3

Installation and Commissioning

3.1

General Installation Requirements

Devices being operated in connection with hazardous areas may not be changed or 

manipulated. If there is a defect, the product must always be replaced with an original 

part. If devices have been operated in general electrical systems, they must not 

subsequently be operated in electrical systems related to explosive areas. The installation 

of the intrinsically safe circuits has to be conducted in accordance with the relevant 

installation regulations, particularly IEC/EN 60079-14.
The device must be mounted in the non-explosive hazardous area.
If Intrinsically safe circuits are connected to earth, there must exist equipotential bonding 

along the intrinsically safe circuits.

3.2

Intrinsically Safe Wiring and Cable Parameters

Only use cables that meet the requirements of IEC/EN 60079-14 to connect to the terminals on 

the barrier. The cable length from the barrier to the keyboard/mouse and from the barrier to the 

host PC should not exceed 4.6 m. The total cable length should not exceed 6.1 m.

Wiring Information

Field terminals 1 ... 4 and 5 ... 8 are for connection to a USB or PS2 keyboard or mouse with 

proper matching entity parameters. Connections 9 ... 12 are the host side USB/PS2 data signal 

connections. These match the common named field connections (D+ D- keyboard are the 

datalines to the keyboard connections on the field side, etc.). 13 and 14 are for connection to a 

properly rated SELV supply voltage. Connections 15 and 16 are to be connected to ground. By 

connecting the host USB cables, the connections 4, 8, 12, 14, 15, and 16 are grounded via the 

host PC. The precondition for this is that the GND line of the PC USB connection is internally 

connected to ground. This must be ensured by measurement.

Div. 2 / Zone 2

SK-PC-D2-UU1-10-HS

6+

7-

8-

5+

2+

3-

4-

1+

10-

11+

12-

9+

14-

15

16

13+

Summary of Contents for SK-PC-D2-UU1-10-HS

Page 1: ...USB Intrinsic Safety Barrier SK PC D2 UU1 10 HS PROCESS AUTOMATION MANUAL...

Page 2: ...Delivery for Products and Services of the Electrical Indus try published by the Central Association of the Electrical Industry Zentralverband Elektrotechnik und Elektroindustrie ZVEI e V in its most r...

Page 3: ...Technical Data 7 2 3 Dimensions 9 2 4 Transport Storage and Maintenance 9 2 5 Disposal 9 3 Installation and Commissioning 10 3 1 General Installation Requirements 10 3 2 Intrinsically Safe Wiring and...

Page 4: ...examination certificate EU declaration of conformity Attestation of conformity Certificates Control drawings Additional documents 1 2 Target Group Personnel Responsibility for planning assembly commi...

Page 5: ...displayed in descending order as follows Informative Symbols Action This symbol indicates a paragraph with instructions You are prompted to perform an action or a sequence of actions Danger This symbo...

Page 6: ...The barrier provides protected USB 1 1 or PS2 power and data signals to an Ex rated mouse keyboard in the field The barrier shall be installed according to all applicable standards and regulations fo...

Page 7: ...against electrical shock IEC 61140 Ambient conditions Ambient temperature 40 60 C 40 140 F Relative humidity 0 95 noncondensing Vibration resistance 5 G 58 150 Hz Impact resistance 15 g 11 ms Mechanic...

Page 8: ...g at field terminals for Class I Zone 2 Group IIC and Group IIIB hazardous locations USL Class I Zone 2 AEx nA ic IIC T6 Gc Class I Zone 2 AEx nA ic IIIB IIC T6 Gc CNL Class I Zone 2 Ex nA ic IIC T6 G...

Page 9: ...one Store all devices in a clean and dry environment 2 5 Disposal Disposal of devices and their packaging material must be performed in compliance with the applicable laws and guidelines of the corre...

Page 10: ...ble Parameters Only use cables that meet the requirements of IEC EN 60079 14 to connect to the terminals on the barrier The cable length from the barrier to the keyboard mouse and from the barrier to...

Page 11: ...2 UU1 10 HS barrier to the host PC as follows Grounding is executed via the host PC The precondition for this is that the GND line of the PC USB connection is internally connected to ground This must...

Page 12: ...16 Grounding is executed via terminal 16 In common application scenarios pins number 4 minus wires of the host USB connectors are connected within the host If not connect pins 4 together to terminal...

Page 13: ...ite Input 2 Host 11 D I O Green 12 D I O White Supply 13 PWR Supply 14 PWR Supply Input 1 host 15 GND Supply Black ground from host Input 2 host 16 GND Supply Black ground from host Connector Terminal...

Page 14: ...Intrinsic Safety Barrier Appendix 4 Appendix 4 1 Accessories Item Number Name Description Contact sales for individual configuration EXTA 3 product family Keyboard and mouse system stand alone option...

Page 15: ...rl fuchs com Worldwide Headquarters Pepperl Fuchs GmbH 68307 Mannheim Germany Tel 49 621 776 0 E mail info de pepperl fuchs com For the Pepperl Fuchs representative closest to you check www pepperl fu...

Reviews: