Safety Manual SIL KFD0-RSH-1(-Y2), KFD2-SL-4
Proof Test
Within the test, the switches are used. The correct settings for the application
must be established again subsequent to the test.
KFD2-SL-4
Figure 4.2
Proof test set-up for KFD2-SL-4
Test No.
Procedure
Input and common disable
output
Output
1
Attach the input voltage subsequently
to each input and check if only the
related output is activated. For this test,
the line fault detection DIP switches
must be in OFF position (position II).
24 V DC between
terminals 11, 12
load resistor on output
Multimeter shows
24 V DC
2
Attach the input voltage subsequently
to each input and check that no output
is switching. For this test, the line fault
detection DIP switches must also be in
OFF position (position II). The
OFF LED is blinking.
0 V DC between terminals
11, 12
load resistor on output
Multimeter shows
0 V DC
3
For this test, the line fault detection DIP
switches must be in ON position
(position I) for all four signal paths.
Deactivate all inputs. The OFF LED and
the four channel switching status LEDs
must be blinking red.
24 V DC between
terminals 11, 12
load resistance removed
–
Table 4.2
KFD2-SL-4
24 V DC
14+
15-
11
12
V
V
10+
9+
8+
7+
1+
2+
3+
4+
5-
6-
1 kΩ
Multimeter
(V)