SLCT* and SLCT*/35 safety light curtains
Installation
2
7
1
6
9
5
2
0
1
7
-1
2
17
The switch-on time after beam interruption without a restart function is between
80 ms and 200 ms. The switch-on time depends on the number of protective
beams.
Notes on setting up safety light curtains
The protective equipment must be arranged in such a manner that it is impossible
to reach over, reach under, or walk behind the protection field. If the distance from
the protective equipment is too great, additional protective equipment must be put
in place (see illustration below).
Reaching over
The operator must not be able to reach over the protection field and into the
hazardous area (A: protection field, B: mechanical protection).
Walking behind
The machine operator must not be able to walk between the light curtain and into
the danger zone (A: protection field, B: mechanical protection).