Accessories VisuNet RM and VisuNet PC
9.2.1
Connection Instructions
Preparation of the BOX-A10 for Installation on a DIN Rail (35 mm)
The modules are grounded directly
on the rail via the ground contact
spring. This spring is connected by
a ground terminal to the
equipotential bonding. The rail must
be electrically conductive
If the module is not supposed to be
grounded, press the locking latch
on the housing down and remove
the ground contact spring.
Then snap the lower housing part
of the E-DAT REG module onto
the rail
Preparation of the DATL-CAT71 Ethernet Cable
Remove about 25 mm (max. 30
mm) of the plastic sheath.
Fold back the braided shield…
…and wrap it around the plastic
sheath.
Glue in the shield film for the wire
pairs and remove.
Separate the pairs of wires
according to how they exit at the
cable ends…
..and arrange them as shown in
the photo to facilitate wire
insertion into the loader later.