Warning Device NVD-111
Commissioning
26
6859
201
4-
04
EN - 31
EN
The following table contains a list of possible configuration settings.
Switches
Description
DIP 1
Reaction time (reaction
time of the fat level
sensor)
ON
Operating mode
–
delay of the sensor reaction
OFF
Service/test mode
–
instant sensor reaction
DIP 2
Overflow sensor KVF-O
ON
connected
OFF
not connected
DIP 3
Fat level sensor KVF-F
or FAU-104
ON
connected
OFF
not connected
DIP 4
Acoustic alarm
ON
Acoustic alarm on.
OFF
Acoustic alarm off.
DIP 5
Relay setting
ON
Relays 1 and 2 switch irrespective of the alarm states and
with which sensor. If the alarm status disappears, relays 1
and 2 switch again (if
“
ALARM RESET
”
is actuated, the
relays switch again).
DIP 6
ON
DIP 5
Relay setting
ON
Relays 1 and 2 switch, irrespective of the alarm states.
After 3 minutes, relay 2 switches again (even if an alarm
status is present). If the alarm status disappears, relay 1
and/or relay 2 switches again (if
“
ALARM RESET
”
is
actuated, the relays switch again).
DIP 6
OFF
DIP 5
Relay setting
OFF
In the case of active alarm status, relay 1 switches to
overflow sensor KVF-O and relay 2 switches to fat level
sensor KVF-F/FAU-104. If the alarm status disappears,
relay 1 and/or relay 2 switch again (if
“
ALARM RESET
”
is
actuated, the relays switch again).
DIP 6
ON
DIP 5
Relay setting
OFF
Relays 1 and 2 switch, irrespective of the alarm states. If
an alarm event is no longer present, relay 1 automatically
switches back
and
relay 2 remains unchanged until the
alarm is cleared by actuating
“
ALARM RESET
”
. It shows
that an alarm occurred.
DIP 6
OFF
DIP 7
Repeat alarm in 24
hours
ON
Repeat alarm on. This also applies to the function of
relays 1 and 2.
OFF
Repeat alarm off.
DIP 8
Reset key (ALARM
RESET activation)
ON
"ALARM RESET" button is activated. The acoustic alarm
and the alarm relay can be reset.
OFF
"ALARM RESET" button is deactivated. The acoustic
alarm and the alarm relay cannot be reset.