WARNING DEVICE LAL-SRW3
Installation
23
2971
20
11-
03
EN - 23
EN
The product is a Class II device (with reinforced insulation). Connect the power
supply as follows:
■
Terminal 7: phase (F/L2)
■
Terminal 6: zero (N/L1)
■
Terminal 5: ground (loop terminal)
For extending the sensor cable, use cable connector LAL-SK2.
Note!
Additional relays can be connected via terminals 1 to 3 and 10 to 12. They can be
used, for example, for an external alarm or the connection to a central monitoring
system.
Note!
Sensor cables must not be run together or parallel to other cables or cable
bundles.
To ensure perfect operation of the warning device, do not exceed the max. cable
length of 250 m.