Power repeater / power supply according to IEC 61158-2
Safety
Subject to reasonable modifications due to technical advances.
Copyright Fuchs, Printed in Germany
Fuchs Group • Tel.: Germany (06 21) 7 76-0 • USA (330) 4 25 35 55 • Singapore 7 79 90 91 • Internet http://www.pepperl-fuchs.com
D
a
te
of
is
su
e1
2.
02
.2
00
2
7
In the second case, power feed takes place that must be made available from a de-
vice other than the power repeater. If this power feed device is a device that also is
equipped with an electrical current limitation in accordance with ignition protection
type "Non incendive“ (for example KLD2-STR-NI1.13.225.IEC), no special wiring
techniques are necessary. If the power feed device does not have any such current
limitation (for example KLD2-STR-1.24.400.IEC), the wiring must be adequate to
comply with the requirements of Class 1 Division 2 Installation. In this case, no work
is permitted on the transmission line between the host and power repeater in
Class 1 Division 2 under voltage.