ICDM-RX/MOD User Manual
Overview
6/
3/1
9
9
1.4. Modbus Router Functionality
The Modbus Router application provides the following functionality:
•
Provides robust connectivity from all supported master devices to all supported slave devices:
-
Supported Masters:
-
Modbus/TCP Master - accepts Modbus/TCP messages on up to eight TCP/IP ports. This includes
502 and seven configurable ports.
-
Modbus/RTU Serial Master
-
Modbus/ASCII Serial Master
-
Modbus/RTU over Ethernet TCP/IP Master
-
Modbus/ASCII over Ethernet TCP/IP Master
-
Supported Slaves:
-
Modbus/RTU Serial Slaves
-
Modbus/RTU ASCII Slaves
-
Remote Modbus/TCP Slaves (addressable to device ID and IP address/port)
-
Remote Modbus/RTU Serial Slaves (via Modbus/TCP using another gateway)
-
Remote Modbus/ASCII Serial Slaves (via Modbus/TCP using another gateway)
•
Multiple ICDM-RX/MOD chassis can be used together to form a Modbus network.
•
Supports up to 255 public Modbus devices per gateway and/or Modbus network. Both standard, (1-247),
and reserved, (248-255), device IDs are supported.
•
All Modbus devices not configured remotely are assumed to be locally connected to the gateway.
•
The locations of all local Modbus devices are determined automatically.
•
Modbus Device ID Aliasing. Modbus message device ID can be
aliased
when messages are received from
a Modbus master.
•
Device ID Offset. At the serial port interface, device IDs can have a positive or negative offset applied to
change the device ID range.
•
Supports up to 96 Modbus/TCP connections. This can include any combination of slave and master
connections.
•
Modbus/RTU and Modbus/ASCII over Ethernet TCP/IP Master specific:
-
Can support up to six TCP/IP connections per serial port configuration.
-
All messages received from any Ethernet TCP/IP Master connection enter the routing functionality and
can be routed to any local or remote device.
-
Combined with a serial port redirector, such as the Fuchs Comtrol Secure Port Redirector, can
provide COM port functionality from a computer to the Modbus network.
•
Supports connectivity to private Modbus serial buses, such as a serial master and slave(s) on a RS-485
loop:
-
The Modbus master is provided connectivity to the public Modbus network.
-
Only the master has direct access to the serial devices on the private serial network.
-
Private slaves are protected from intrusion by other master(s).
-
Both slave device specific and port level diagnostics are provided for private network communication.
•
Advanced Master-to-Master connectivity is provided via the Shared Memory sub-system. Features are:
-
Eight Holding Register blocks containing 200 registers each.
-
Eight Coil blocks containing 160 coils each.
-
Read access to all master(s) on the Modbus network.