ARS*-B2-IC*

Operation

 2

021-

03

25

Reset Button

If the device is installed in explosion hazardous area, the reset button may be operated during 

operation.

Rebooting Switch

Figure 4.1

To reboot the switch, push the reset button for at least 1 second.

Spurs Start-Up Management

Sequential Start-Up of Spurs

During start-up, the spurs are sequentially activated to minimize the initial high inrush current 

demand for the auxiliary power supply. Therefore, the auxiliary power supply is less stressed 

during the start-up phase, and its expected useful lifetime is increased.

Fold-Back Characteristics of the Spur Short Circuit Current Limitation

If a spur short circuit occurs, the spur current is switched off quickly. When the short circuit cur-

rent has been cleared, the spur current returns. If multiple simultaneous short circuit currents 

occur, the current management system minimizes the additional current demand of the auxil-

iary power supply.

1

Reset button

Serial No:

yyyy

PA

RESET

PWR A

PWR B
STATUS

LNK/CHK

P1

P2

P3

P4

P1

P2

P3

P4

PWR A

PWR B

FA

IL

-

+

-

+

1

2

LNK/CHK

S1

S2

S3

-
+

S

-
+

S

-
+

S

-
+

S

S1

S2

S3

S4

S4

RESET

PWR A

PWR B
STATUS

LNK/CHK

P1

P2

P3

P4

1

Summary of Contents for ARS1-B2-IC08-1

Page 1: ...ARS B2 IC Ethernet APL Rail Field Switch Hardware Manual ...

Page 2: ...rsion as well as the supplementary clause Expanded reservation of proprietorship Worldwide Pepperl Fuchs Group Lilienthalstr 200 68307 Mannheim Germany Phone 49 621 776 0 E mail info de pepperl fuchs com North American Headquarters Pepperl Fuchs Inc 1600 Enterprise Parkway Twinsburg Ohio 44087 USA Phone 1 330 425 3555 E mail sales us pepperl fuchs com Asia Headquarters Pepperl Fuchs Pte Ltd P F Bu...

Page 3: ...ription 6 2 1 Overview and Application 6 2 2 Type Codes 6 2 3 Components and Dimensions 8 2 4 Accessories 9 2 5 Scope of Delivery 12 2 6 Technical data 12 3 Installation 15 3 1 General Installation Information 15 3 2 Mounting and Dismounting 15 3 3 Connection Assignment 20 3 4 Grounding Shielding 22 4 Operation 24 4 1 Operating Elements 24 ...

Page 4: ...ion certificate EU declaration of conformity Attestation of conformity Certificates Control drawings Additional documents 1 2 Target Group Personnel Responsibility for planning assembly commissioning operation maintenance and dismount ing lies with the plant operator Only appropriately trained and qualified personnel may carry out mounting installation com missioning operation maintenance and dism...

Page 5: ... in descending order as fol lows Informative Symbols Action This symbol indicates a paragraph with instructions You are prompted to perform an action or a sequence of actions Danger This symbol indicates an imminent danger Non observance will result in personal injury or death Warning This symbol indicates a possible fault or danger Non observance may cause personal injury or serious property dama...

Page 6: ... are rated intrinsically safe Ex ic IIC for Zone 2 and Zone 22 mount ing The spurs are compatible with the Ethernet APL port profile SPCC 2 RJ45 and 2 SFP Ethernet interfaces permit the connection to industrial Ethernet networks like PROFINET or EtherNet IP 2 of the 4 ports may be used in ring configuration Fiber optic small form factor pluggable SFP transceivers are available as accessories Prod ...

Page 7: ...her details Contact your Pepperl Fuchs representative to check the availability of individual product ver sions Order designation Number of Ethernet APL spur connec tions Terminal pluggable Screw terminal Spring terminal ARS1 B2 IC08 1 8 x ARS1 B2 IC08 2 8 x ARS1 B2 IC16 1 16 x ARS1 B2 IC16 2 16 x ARS1 B2 IC24 1 24 x ARS1 B2 IC24 2 24 x Table 2 1 ...

Page 8: ...10 11 6 7 Dimension a DIN Rail Mounting 1 Year of production 2 Serial number 3 PA connection to equipotential bonding 4 Slot for separation wall 5 MAC ID 6 LED S1 Sn status spur ports S1 Sn 7 Connectors for intrinsically safe spurs S1 Sn 8 Ethernet port P1 9 Ethernet port P2 10 Ethernet SFP port P3 11 Ethernet SFP port P4 12 LED LNK CHK P1 P4 communication status LED P1 P4 13 Connector for auxilia...

Page 9: ...mber 3 PA connection to equipotential bonding 4 Slot for separation wall 5 MAC ID 6 LED S1 Sn status spur ports S1 Sn 7 Connectors for intrinsically safe spurs S1 Sn 8 Ethernet port P1 9 Ethernet port P2 10 Ethernet SFP port P3 11 Ethernet SFP port P4 12 LED LNK CHK P1 P4 communication status LED P1 P4 13 Connector for auxiliary power and status indication output 14 LED STATUS status switch 15 Res...

Page 10: ...plies with 100BASE FX Transfer rate 100 Mbit s Reach length of up to 2 km LC duplex connector Multi mode fiber with 1310 nm Complies with a Class 1 laser product in accordance with EN 60825 1 ACC PC 45 RJ45 protective covers packing unit 10 pieces ACC PC SFP SFP protective covers packing unit 10 pieces ACC ARS SW separation walls packing unit 2 pieces ACC ARS WMK Wall mounting kit Table 2 2 Order ...

Page 11: ... product in accordance with EN 60825 1 For further SFP transceiver versions contact your Pepperl Fuchs sales representative Protective Cover for RJ45 Sockets Figure 2 5 To protect unused RJ45 sockets against dust or unintentional harm protective covers are pro vided Protective Cover for SFP Sockets Figure 2 6 To protect unused SFP sockets against dust or unintentional harm protective covers are pr...

Page 12: ...spur terminals Wall Mounting Kit Figure 2 8 A wall mounting kit is provided as an accessory The kit includes 2 brackets The factory installed DIN mounting rail clamps must be removed before installing 2 5 Scope of Delivery The rail field switch is delivered with mounting brackets for DIN mounting rail 2 6 Technical data Depending on the mounting position of the rail field switch and the use of SFP...

Page 13: ...ARS B2 IC Product Description 2021 03 13 Figure 2 9 Figure 2 10 Horizontal Mounting Position Vertical Mounting Position ...

Page 14: ...21 03 14 ARS B2 IC Product Description Mounting position Use of SFP transceivers Ambient temperature Horizontal No 40 C 70 C Horizontal Yes 40 C 65 C Vertical No 40 C 55 C Vertical Yes 40 C 55 C Table 2 3 ...

Page 15: ...phere If the device is installed in Zone 2 without mounting it in a sufficiently suitable surrounding enclosure gas dust water or other external interferences can cause the live device to spark The sparks can ignite the surrounding potentially explosive atmosphere Mount the device in a surrounding enclosure that complies with the requirements for surround ing enclosures according to IEC EN 60079 0...

Page 16: ...e electronics onto the DIN mounting rail 3 Move the top hook over the upper end of the DIN mounting rail until the locking mechanism engages Dismounting DIN mounting rail Figure 3 2 1 Use a slot head screwdriver and push down the locking mechanism to release the device 2 Tilt the device downwards to free it from the DIN mounting rail 1 2 3 1 2 ...

Page 17: ...g bracket remove the factory installed DIN mounting rail clamps To remove the DIN mounting rail clamps loosen 3 screws each clamp To remove the adapter loosen 2 screws each adapter Figure 3 4 Note When using product version with 8 Ethernet APL spur connections only 1 bracket is needed 1 Screws for DIN mounting rail clamp 2 TX20 screws for adapter 1 2 1 Screw 1 ...

Page 18: ...sion hazard from sparking when using operating elements Using operating elements in a potentially explosive atmosphere can cause sparks that can ignite the surrounding atmosphere While power is on do not insert and remove SFP transceivers When installing or removing SFP transceivers make sure that power is removed Only use operating elements e g switch slider button etc in the absence of a potenti...

Page 19: ...arance distance of 50 mm between the non intrinsically safe circuits and intrinsi cally safe circuits install the separation walls Figure 3 5 1 Press the separation walls into the provided slots on the front of the switch 2 Make sure that they are locked in place Danger Explosion hazard from wrong separation distances If you do not observe the minimum separation distances between intrinsically saf...

Page 20: ...ductor When using stranded conductors crimp wire end ferrules on the conductor ends Use only one conductor per terminal When installing the conductors the insulation must reach up to the terminal Observe the tightening torque of the terminal screws Danger Explosion hazard from connection damage Manipulating connections outside of the specified ambient temperature range can lead to material damage ...

Page 21: ...R A and PWR B Figure 3 6 Screw terminal Figure 3 7 Spring terminal The switches must be supplied with a DC voltage Un 20 V 60 V that meets the require ments for safety extra low voltage SELV or protective extra low voltage PELV and not exceed a maximum voltage of 60 V DC even under fault condition At the power terminal the cross section of the cables must be chosen in accordance with the maximum f...

Page 22: ...This can ignite the surrounding potentially explosive atmosphere Ground the device Observe the grounding requirements for type of protection Ex i according to IEC EN 60079 14 Ensure that external ground connections exist are in good condition and are not damaged or corroded Caution Risk of electric shock or property damage from inadequate grounding If you fail to connect all metal parts of the dev...

Page 23: ...l PA The shields of the connected field devices must be connected to local earth Grounding the Ethernet Copper Cable The Ethernet cable is directly connected to the grounding terminal PA through the RJ45 con nector 1 Phillips head screw M4 x 16 mm 2 Flat washer M4 3 Spring washer 4 Cable lug 5 Flat washer M4 6 Flat washer M4 1 2 3 4 5 6 Warning Dangerous atmospheres and plant damages due to commun...

Page 24: ... switch to Pep perl Fuchs STATUS Status of the switch Off Good Blue on Maintenance required See note Red flashing Out of specifica tion See note Red on Failure See note LNK CHK P1 P4 Status of the Ethernet ports Off No communica tion link estab lished Green on Communication link established Green flashing Communication link activity Red flashing Check function See note S1 Sn Status of the spurs Of...

Page 25: ...upply is less stressed during the start up phase and its expected useful lifetime is increased Fold Back Characteristics of the Spur Short Circuit Current Limitation If a spur short circuit occurs the spur current is switched off quickly When the short circuit cur rent has been cleared the spur current returns If multiple simultaneous short circuit currents occur the current management system mini...

Page 26: ...Pepperl Fuchs Quality Download our latest policy here www pepperl fuchs com quality www pepperl fuchs com Pepperl Fuchs Subject to modifications Printed in Germany DOCT 7025 ...

Reviews: