background image

7 / 8

THERMAL MANAGEMENT SOLUTIONS

EN-TraceTekTTNRM-IM-H57474      01/13

D. connect RS-485 cables and set address

1.  Select the RS-485 address for the TT-NRM unit.

Each TT-NRM connected to a TTDM-128 must have a unique 

address in the range 1 to 99. If two TT-NRM units are as-

signed the same address, communications faults will result.
To ensure you assign an unique address to each TT-NRM unit, 

review the system layout. If a layout document does not exist, 

create one. Assign an unique address to each TT-NRM unit.

Note: TraceTek TTSIM modules are connected on the same 

RS-485 network and must not have the same address as any 

TT-NRM.

2.  Set the RS-485 address for the TT-NRM unit.

Use a small flat-blade screwdriver to rotate the address 

switch marked “x1” to the desired address. For an address 

of 50, set the “x1” to 0 and the “x10” to 5. 

Set address 0-9

Set 10's digit of address

L

N

+

ON

TxD

IO/RN

IO/ER

RxD

CRC

Address  x 1 

x 10

WAGO 750-315

I/0

SYSTEM

24V 0V

750-517 750-517 750-517

RS-485

3

2

1

Note: Previous wiring omitted for clarity

POWER SUPPLY

3.  connect RS-485 cables.

Note: Do not make connections to the RS-485 bus while it 

is connected to an operating TTDM-128, or damage and/or 

alarms could result.
The RS-485 bus allows units with unique addresses to be 

daisy-chained together along a common bus. To add a new 

unit to the network, simply daisy-chain the RS-485 bus from 

the last unit to the new one—or insert the new unit between 

two existing units on the bus. The order in which units are 

attached to the RS-485 bus does not matter. There are just 

two constraints on the RS-485 network:
•  Each TT-NRM must be assigned a unique address.
•  The RS-485 bus must be a continuous string from the 

first unit to the last unit in the system.

Note: The RS-485 bus operates at 5 V, and equipment 

connected to it could be damaged by exposure to higher 

voltages. Take precautions to avoid exposing the RS-485 

wiring to discharge of static electricity or other sources of 

high voltage potential; in particular, avoid contact with the 

power supply wiring.

4

3

2

1

 

Connect the clear or white wire of the RS-485 cable to 

the (+) terminal as shown.

4

3

2

1

 

Connect the black wire of the RS-485 cable to the (–) 

terminal as shown.

4

3

2

1

 

Connect the shield wire of the RS-485 cable to the 

shield terminal as shown.

If connecting two RS-485 cables (one IN and one OUT), use 

the same terminals for both wires.
Important: Do not connect the shield of the RS-485 cable 

to the enclosure or panel grounding terminal. Connect the 

shield only to the terminal provided. To avoid the potential 

for spurious ground loops, the RS-485 cable shield should 

be connected to ground only in the TTDM-128.

Summary of Contents for TraceTek TT-NRM Series

Page 1: ...cuments TTDM 128 Installation Manual H57341 TTDM 128 User Manual H56583 Specifications Function Provides relay outputs to switch power to contactors under control of the TTDM 128 Ambient operating ran...

Page 2: ...127 circuits of leak detection TT NRM units switch external alarm or control devices NRMs are connected to the TTDM 128 unit via a single RS 485 network 1 Network processor marked 750 315 2 2 channel...

Page 3: ...is powered with line voltage and switches relay contacts that may be connected to line volt age Select an electrical panel or enclosure considering the area classification i e non hazardous or hazardo...

Page 4: ...he right of the last relay module added Refer to the TT NRM Assembly diagram on page 2 for the proper order of module assembly Important Modules and or external equipment may be damaged if modules are...

Page 5: ...C Address x 1 x 10 WAGO 750 315 I 0 SYSTEM 24V 0V L L N N L L N N 01 02 15 16 750 517 750 517 750 600 Note Previous wiring omitted for clarity L N POWER SUPPLY Using WAGO Terminals Insert flat blade s...

Page 6: ...2 channel relay output modules as shown ON TxD IO RN IO ER RxD CRC Address x 1 x 10 WAGO 750 315 I 0 SYSTEM 24V 0V L L N N L L N N 01 02 15 16 750 517 750 517 750 600 L L N N 15 16 750 517 Note Previo...

Page 7: ...with unique addresses to be daisy chained together along a common bus To add a new unit to the network simply daisy chain the RS 485 bus from the last unit to the new one or insert the new unit betwe...

Page 8: ...e must be triggered in order for the TTDM 128 to recognize new or changed TT NRM units Until this software function is run the TTDM 128 will not control new TT NRM units 1 Energize all TT NRMs in the...

Reviews: