background image

1 / 8

TT-NRM

Network relay Module INstallatIoN INstructIoNs

THERMAL MANAGEMENT SOLUTIONS

EN-TraceTekTTNRM-IM-H57474      01/13

TT-NRM-BASE 

unit with four 

TT-NRM-2RO 

modules removed

ON

TxD

I/O 

RUN

I/O 

ERR

RxD

CRC

750

-31

2

x 10

+

DEScRIpTION

The TraceTek Network Relay Module provides multiple relay 

outputs for switching alarm or control devices for the leak detection 

system. TT-NRM units are modular and may be configured with 2 to 

32 relay outputs. A single TTDM-128 unit communicates with up to 

up to 20 NRMs over a single, twisted pair RS-485 cable.

ADDITIONAL MATERIALS REqUIRED

•  TT-NRM-2RO, 2-channel relay output module (marked 750-517)  

[up to 15 additional modules may be added to one TT-NRM-BASE]

•  RS-485 cable, 1 shielded twisted pair [TT-RS485-BULK or 

equivalent]

•  Suitable enclosure or panel

•  Additional wire, as necessary

TOOLS REqUIRED

•  3.5-mm flat-blade terminal screwdriver

•  Wire stripper/cutter

REfERENcE DOcUMENTS

•  TTDM-128 Installation Manual (H57341)

•  TTDM-128 User Manual (H56583)

SpEcIfIcATIONS

Function  

Provides relay outputs to switch power to 
contactors under control of the TTDM-128

Ambient operating range  0°C to 55°C (32°F to 130°F)
Ambient storage range   –40°C to 60°C (–40°F to 140°F)
Relative humidity 

5% to 95%, noncondensing

Supply voltage 

94-264 Vac

Supply current 

60 VA max.

Relay output type 

Mechanical, normally open, voltage free 

Relay output rating 

230 Vac, 30 Vdc, 2 A max.

Communications 

RS-485, single shielded twisted pair, 
max. 20 NRM units per network

Connection terminals 

28–12 AWG (0.08–2.5 mm

2

)

This component is an electrical device. It must be installed 

correctly to ensure proper operation and to prevent shock or fire. 

Read and carefully follow these important installation instructions.

WARNING:

KIT cONTENTS

TT-NRM-BASE:
1  Network processor (marked 750-315)
1  24 Vdc power supply (marked 5101-7663)
1  Relay output module (marked 750-517)
1  End termination module (marked 750-600)
1  RS-485 network connection module
1  Ribbon cable with screws
1  DIN 35 rail for mounting
1  Ground terminal
2  DIN rail end stops

AppROvALS

Summary of Contents for TraceTek TT-NRM Series

Page 1: ...cuments TTDM 128 Installation Manual H57341 TTDM 128 User Manual H56583 Specifications Function Provides relay outputs to switch power to contactors under control of the TTDM 128 Ambient operating ran...

Page 2: ...127 circuits of leak detection TT NRM units switch external alarm or control devices NRMs are connected to the TTDM 128 unit via a single RS 485 network 1 Network processor marked 750 315 2 2 channel...

Page 3: ...is powered with line voltage and switches relay contacts that may be connected to line volt age Select an electrical panel or enclosure considering the area classification i e non hazardous or hazardo...

Page 4: ...he right of the last relay module added Refer to the TT NRM Assembly diagram on page 2 for the proper order of module assembly Important Modules and or external equipment may be damaged if modules are...

Page 5: ...C Address x 1 x 10 WAGO 750 315 I 0 SYSTEM 24V 0V L L N N L L N N 01 02 15 16 750 517 750 517 750 600 Note Previous wiring omitted for clarity L N POWER SUPPLY Using WAGO Terminals Insert flat blade s...

Page 6: ...2 channel relay output modules as shown ON TxD IO RN IO ER RxD CRC Address x 1 x 10 WAGO 750 315 I 0 SYSTEM 24V 0V L L N N L L N N 01 02 15 16 750 517 750 517 750 600 L L N N 15 16 750 517 Note Previo...

Page 7: ...with unique addresses to be daisy chained together along a common bus To add a new unit to the network simply daisy chain the RS 485 bus from the last unit to the new one or insert the new unit betwe...

Page 8: ...e must be triggered in order for the TTDM 128 to recognize new or changed TT NRM units Until this software function is run the TTDM 128 will not control new TT NRM units 1 Energize all TT NRMs in the...

Reviews: