T-SERIES

Air Conditioner

t53 Model

INSTRUCTION MANUAL

Summary of Contents for T50 T-SERIES

Page 1: ... 2013 Pentair Equipment Protection 88004712 Rev F P N 10 1008 224 T SERIES Air Conditioner T53 Model INSTRUCTION MANUAL ...

Page 2: ...ING THE AIR CONDITIONER 3 INSTALLATION INSTRUCTIONS 4 Design Data 4 DIMENSIONAL DRAWING 4 MOUNTING CUTOUT DIMENSIONS 5 Components List 6 Wiring Diagram with Optional Heater 7 TEMPERATURE CONTROL 8 PRINCIPLES OF OPERATION 8 MAINTENANCE 8 Compressor 8 Inlet Air Filter 8 How To Remove Clean or Install a New Inlet Air Filter 9 Condenser and Evaporator Air Movers 9 Refrigerant Loss 9 TROUBLE SHOOTING 1...

Page 3: ...ITY BEFORE MOUNTING THE AIR CONDITIONER TO THE ENCLOSURE Refer to the nameplate for proper electrical current requirements and then connect the power cord to a properly grounded power supply Minimum circuit ampacity should be at least 125 of the amperage shown in the design data section for the appropriate model No other equipment should be connected to this circuit to prevent overloading Operate ...

Page 4: ...tion during operation 5 When routing the drain tube caution should be taken to keep it from kinking or being elevated above the exit point of the air conditioner The drain tube must be on a continuous downward slope A slight elevation of the tube could result in secondary trap FAILURE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN OVERFLOWING OF THE CONDENSATE DRAIN PAN 6 Refer to top of nameplate f...

Page 5: ... 2013 Pentair Equipment Protection 88004712 5 MOUNTING CUTOUT DIMENSIONS Surface Mount Recess Mount CUTOUT INSTRUCTIONS As viewed from outside of enclosure NOTE Dashed lines represent air conditioner ...

Page 6: ... μF 52 6084 00 Capacitor Evap Blower Motor 5 μF 52 6084 05 Rod Heater 3000W 240V Optional 10 1030 24 Limit Switch Auto Optional 10 1033 01 Limit Switch Manual Optional 10 1033 07 Coil Condenser 89098474 Coil Evaporator 53 1001 00 Air Filter Reusable 89057627 Filter Dryer 52 6028 06 Thermal Expansion Valve 10 1040 40 Freeze Stat 10 1061 05 Head Pressure Control Switch 52 6104 53 Malfunction Limit S...

Page 7: ... 9 6 4 9 6 7 1 24 5514 70 6 10 59 6 126 9 6 4 6 56 140 8 214 614 19 4 19 4 10 05 4 24 5574 5 9 6 0 1 4 1 0 9 6 9 6 9 6 9 6 7 40 40 9 6 40 4 4 9 6 9 6 470 2 4 5 5 7 59 6 5 6 14 5 48 5 40 9 6 7 40 761 4 5 6 07 5 5 4 5 6 4 2 2 6 4 0 1 F 7D AEF3F 6 4 156 6 9 4 5 176 14 7561 4 100 6 10 21 6 0 106 614 21 106 614 11 0 73F7D ...

Page 8: ...d or tampered with Breaking of seals on compressor access fittings during warranty period will void warranty on hermetic system Recharging ports are provided for the ease and convenience of reputable refrigeration repair service personnel for recharging the air conditioner INLET AIR FILTER Proper maintenance of the inlet air filter located behind the front grille will assure normal operation of th...

Page 9: ...ter do so from both sides for maximum concentration of adhesive CONDENSER AND EVAPORATOR AIR MOVERS Blower and impeller motors require no maintenance All bearings shafts etc are lubricated during manufacturing for the life of the motor If the condenser blower motor ambient blower should fail it is not necessary to remove the air conditioner from the cabinet or enclosure to replace the blower The c...

Page 10: ...s there airflow YES proceed to step 6 NO possible problem Defective thermostat Open motor winding Stuck blower motor Obstructed wheels blades Repair or Replace defective part 6 Carefully check the compressor for operation motor should cause slight vibration and the outer case of the compressor should be warm Is the compressor showing signs of this YES wait 5 minutes then proceed to step 7 NO possi...

Page 11: ...t but won t run Low line voltage at start Should be 10 rated voltage Compressor motor stuck Bad relay Bad overload switch Bad run start capacitor Unit blows breakers Undersized breaker fuse or not time delayed Short in system Getting water in enclosure Drain plugged Drain tube kinked Enclosure not sealed allowing humidity in For additional technical support i e amp draw pressures temperatures cont...

Page 12: ... 2013 Pentair Equipment Protection 88004712 12 NOTES ...

Page 13: ... 2013 Pentair Equipment Protection 88004712 13 NOTES ...

Page 14: ... than fourteen 14 days from the date when Buyer has become aware of such occurrence or where the defect is such that it may cause damage immediately such notice containing a description of how the defect manifests itself Failure to provide such prompt notice to Pentair Equipment Protection shall result in forfeiture of Buyer s rights under this warranty In the event of a warranty claim Buyer is to...

Page 15: ...st Failure Analysis can be provided by Pentair Equipment Protection for warrantable goods at no charge Failure analysis for non warranty repairs are subject to a 100 per hour Engineering charge plus any other incurred testing costs F All returned merchandise must be sent to the following address Pentair Equipment Protection 2100 Hoffman Way Anoka MN 55303 1745 G Credit for accepted returns shall b...

Page 16: ... 2013 Pentair Equipment Protection 88004712 Rev F P N 10 1008 224 Pentair Equipment Protection 2100 Hoffman Way Minneapolis MN 55303 USA 1 763 422 2211 1 763 576 3200 PentairEquipmentProtection com ...