10
P1062 (06/06/19)
PENTAIR PENTEK
*
SOLAR DRIVE WIRING INSTRUCTIONS
Figure 8: Wiring Inside the Pentair Pentek Solar Drive
Once the system is wired (per Figure 8), the power conductors wired to the DIN rail terminals
inside the Pentair Pentek Solar Drive should be tightened with torque values of:
– Solar PV and motor load conductors: 11 lb-in
– AC source conductors: 8 lb-in
The cable glands (cord grips) on the bottom of the enclosure should be used as follows:
– 1/2 inch cord grips should only be used with a cord that is 0.280-0.455 inch outer diameter.
– 3/4 inch cord grips should only be used with a cord that is 0.455-0.705 inch outer diameter.
When all conductors are wired into the controller, the cover (enclosure door) should be replaced
and tightened using the cover screws to 2-3 in-lb or equivalent.
Single phase motor loads should be wired as shown in Figure 8. Single phase 3-wire motors
should be wired so that the Common Lead is wired to Phase A, Starting Winding to AUX and Main
Winding to Phase C. Use DIP Switch 8 for proper single phase motor selection.
Float Switch/
Other Sensors
Solar PV 1
Solar PV 2
Three
Phase
Motor
Single
Phase
3-Wire
Motor
System
Ground
Yellow
Red
Black
Red
Black
Red
Black
Terminal 1
(Yellow)
Terminal Aux
(Gray)
Terminal 2
(Red)
Terminal 3
(Black)
IMPORTANT:
Three Phase Motor
Single Phase 3-wire Motor
Terminal 1 (Yellow):
YELLOW
wire
Terminal 2 (Red):
RED
wire
Terminal 3 (Black):
BLACK
wire
Terminal 1 (Yellow):
YELLOW
wire – common motor lead
Terminal Aux (Grey):
RED
Aux wire – start motor lead
Terminal 3 (Black):
BLACK
wire – main motor lead