PROLINE

Top-MounT Air CondiTioner

2000/4000 BTu/Hr.

INSTRUCTION MANUAL

Summary of Contents for PAC216T66

Page 1: ... 2016 Pentair Equipment Protection 87567377 Rev E P N 11359799 PROLINE Top Mount Air Conditioner 2000 4000 BTU Hr INSTRUCTION MANUAL ...

Page 2: ...ure to do so may result in damage to the unit or other enclosure equipment The air conditioner power source should be electrically isolated from all other sources to the enclosure equipment This is particularly important if any of the equipment is susceptible to noise or voltage fluctuations which may be encountered during air conditioner start up CAUTION TABLE OF CONTENTS Introduction 2 Design Da...

Page 3: ...0 1172 125 52 140 63 R134A 13 0 PAC426T68 23 31 x 23 61 592 x 400 230 50 60 8 0 7 5 4000 1172 125 52 140 63 R134A 13 0 PAC416T86 31 19 x 15 75 792 x 400 115 50 60 14 7 13 6 4000 1172 125 52 140 63 R134A 13 0 PAC426T86 31 19 x 15 75 792 x 400 230 50 60 8 0 7 5 4000 1172 125 52 140 63 R134A 13 0 PAC416T88 31 19 x 23 61 792 x 400 115 50 60 14 7 13 6 4000 1172 125 52 160 72 R134A 13 0 PAC426T88 31 19 ...

Page 4: ...ore operating in order to allow the compressor oil to drain to the compressor sump area NEVER attempt to operate the air conditioner while in any other position than the operating position Running the refrigeration compressor without oil in the lower part of the housing will cause permanent damage to the unit This also voids the warranty CAUTION PRODUCT IDENTIFICATION For installation and maintena...

Page 5: ...perature measuring device The cool air output should be between 50 F to 60 F when room temperature is between 70 F to 80 F These units are equipped with a thermostat If the thermostat is not set properly the condenser fan and compressor may not operate while the evaporator fan runs If this condition exists the entering air temperature to the evaporator may be below the thermostat setpoint To corre...

Page 6: ... all internal and external electrical clearances to ensure equipment will function safely and properly CAUTION 1 Remove cover from PROLINE frame 2 Remove shroud from air conditioner Four bolts and washers at the top of the air conditioner Two screws in the front flange 3 Place the air conditioner base on top of the PROLINE frame 4 Use four bolts and washers to fasten air conditioner base to the to...

Page 7: ...nly generally available in any reputable air conditioning repair or service company in your local area Refer to the data on your nameplate which specifies the type of refrigerant and the charge sizes in ounces Prior to recharging the system must be evacuated and checked for leaks FANS AND MOTORS Fan motors require no maintenance All bearings shafts etc are lubricated during manufacturing for the l...

Page 8: ...ons in operating duty cycles of the air conditioner Amounts of airborne dust dirt particles are different in every location It is recommended that when a fine layer of dust or lint is visible on the surface of the filter it should be flushed drained coated with proper adhesive and reinstalled Do not run the air conditioner for an extended period of time with the inlet filter removed Particles of d...

Page 9: ... 1106 101 10 1106 101 Filter Air Reusable Wide N S 10 1000 56 10 1000 56 10 1000 56 10 1000 56 Filter Dryer 7 52 6028 00 52 6028 00 52 6028 00 52 6028 00 Grille Front Wide N S 10 1130 00 10 1130 00 10 1130 00 10 1130 00 Hot Gas By Pass Valve 8 52 6027 16 52 6027 16 52 6027 16 52 6027 16 Pan Condensate 9 10 1130 24 10 1130 24 10 1130 24 10 1130 24 Pan Evaporator 10 10 1130 11 10 1130 11 10 1130 11 ...

Page 10: ...ir Equipment Protection label affixed to product without written Pentair Equipment Protection approval Pentair Equipment Protection must be notified of a claim in writing not later than fourteen 14 days from the date when Buyer has become aware of such occurrence or where the defect is such that it may cause damage immediately such notice containing a description of how the defect manifests itself...

Page 11: ...is fee If approval is not received within 30 days material will be scrapped and all shipping expenses and corresponding analysis fees will be billed to Buyer E At Buyer s request Failure Analysis can be provided by Pentair Equipment Protection for warrantable goods at no charge Failure analysis for non warranty repairs are subject to a 150 per hour Engineering charge plus any other incurred testin...

Page 12: ... 2016 Pentair Equipment Protection 87567377 Rev E P N 11359799 Pentair Equipment Protection 2100 Hoffman Way Minneapolis MN 55303 USA 1 763 422 2211 1 763 576 3200 PentairProtect com ...