9.10 Reactors And Filters
Variable frequency drives produce voltage spikes that are
a function of voltage rise-time and length of motor cable.
In extreme cases peak voltage may exceed three times
the nominal operating voltage.
Reactors
A reactor is a resistance and inductance device that
reduces voltage spikes. It does this by both increasing the
voltage rise-time and improving the impedance match of
the cable and motor.
Filters
A filter combines a reactor with a capacitor network. The
capacitors absorb a portion of the voltage spikes. This
further reduces the peak voltage seen at the motor.
When to Use a Reactor or Filter
The chart below is a general guideline when choosing
between using a filter or reactor.
Motor Type
Lead Length
up to 50’
50’ to 150’
150’ to 1000’
230 V
460V
230V
460V
230V
460V
NEMA Above-Ground
Std. Efficiency
-
-
R
R
F
F
NEMA Above-Ground
Premium Efficiency
-
Submersible
R
R
F
R = Reactor F = Filter
The following list indicates a greater need for filters
and reactors:
• Long motor leads are used
• Standard efficiency or submersible motors are used.
• The cost of replacing the motor is prohibitive.
• Using a submersible motor with a voltage rating
greater than 230V.
• The quality and/or age of the motor is unknown.
• Condition of wiring and/or power quality is unknown.
9.9 PPC3 and PPC5 Tank Sizing
These instructions are only for systems that require
tanks. Pressure tanks are generally required to maintain
system pressure during periods of low or no demand.
Tank pre-charge must be less than the pressure set point
– wake up deviation.
Tank can be sized using Boyle’s law (V1 x P1 = V2 x P2).
Units are in gallons and PSI.
Typically tanks are sized for approximately 20% of pump
capacity. For example, a 150 gpm pump typically requires
30 gallon total tank size.
Total Tank Size x (Pr14.7)
__
Total Tank Size x (Pr14.7)
(S14.7 – Wake Up Deviation)
(S14.7)
Drawdown =
Reactors
Open Design
230 or 460 V
Model
NEMA 1
230 or 460 V
Model
Rated
Amps
NEMA 1
575 V
Model
Rated
Amps
KDRA1P
KDRA1PC1
3.4
KDRA31PC1
2.7
DDRA2P
KDRA2PC1
4.8
KDRA35PC1
3.9
KDRA3P
KDRA3PC1
7.6
KDRA33PC1
6.1
KDRA4P
KDRA4PC1
11
KDRA34PC1
9
KDRB1P
KDRB1PC1
14
KDRA36PC1
11
KDRD1P
KDRD1PC2
21
KDRD31PC2
17
KDRD2P
KDRD2PC2
27
KDRD32PC2
22
KDRD3P
KDRD3PC2
34
KDRD35PC2
27
KDRD4P
KDRD4PC2
40
KDRD33PC2
32
KDRC1P
KDRC1PC2
52
KDRD34PC2
41
KDRF1P
KDRF1PC3
65
KDRC31PC2
52
KDRF2P
KDRF2PC3
77
KDRF31PC3
62
KDRF3P
KDRF3PC4
96
KDRF32PC3
77
KDRH1P
KDRH1PC4
124
KDRF33PC4
99
KDRI1P
KDRI1PC4
156
KDRH31PC4
125
KDRI2P
KDRI2PC4
180
KDRI31PC4
144
KDRG1P
KDRG1PC4
240
KDRI32PC4
192
KDRG31PC4
242
Filters
NEMA 1, 230, 460 or 575 V
Model
NEMA 1, CUL Listed
Model
Rated Amps
KLC4BE
KLCUL4BE
4
KLC6BE
KLCUL6BE
6
KLC8BE
KLCUL8BE
8
KLC12BE
KLCUL12BE
12
KLC16BE
KLCUL16BE
16
KLC25BE
KLCUL25BE
25
KLC35BE
KLCUL35BE
35
KLC45BE
KLCUL45BE
45
KLC55BE
KLCUL55BE
55
KLC80BE
KLCUL80BE
80
KLC110BE
KLCUL110BE
110
KLC130BE
KLCUL130BE
130
KLC160BE
KLCUL160BE
160
KLC200BE
KLCUL200BE
200
KLC250BE
KLCUL250BE
250
SECTION 9: PPC Series 50/60 Hz Variable Frequency Drives
PPC Series
VFD
Summary of Contents for P42B0007A2-01
Page 1: ...pentek Electronics Manual Installation Operation Maintenance WWW PUMPS COM ...
Page 108: ...NOTES ...
Page 109: ...NOTES ...