6” Submersible Motors
6.6 Motor Fuse Sizing and Cable Selection
CABLE SELECTION
75° C
COPPER CABLE SIZE - From Main Breaker Panel to Motor (in feet)
MOTOR
AWG
MCM
VOLTS HP KW
FUSE
STD
Dual
Element 14
12
10
8
6
4
3
2
1
0
00
000 0000 250 300 350 400 500
THREE PHASE
230 V
60 hz
5
3.7
45
25
-
245
391
620
965 1538 1933 2442 3076 3883 4899 6184 7791 9198
7.5 5.5
60
40
-
-
277
438
682 1087 1367 1726 2174 2745 3463 4372 5508 6502 7806 9124
10 7.5
90
50
-
-
-
308
479
764
961 1213 1529 1930 2434 3073 3872 4571 5488 6415 7334 9125
15
11
125
80
-
-
-
-
337
537
675
852 1073 1355 1709 2158 2719 3210 3853 4504 5149 6407
20
15
175
110
-
-
-
-
-
400
503
636
801 1011 1275 1610 2028 2394 2874 3360 3842 4780
25 18.5 225
125
-
-
-
-
-
-
417
527
664
838 1057 1334 1681 1985 2383 2785 3184 3962
30
22
250
125
-
-
-
-
-
-
-
471
593
749
945 1193 1503 1775 2130 2490 2847 3543
460 V
60 hz
or
380 V
50 h
5
3.7
20
10
617
982 1566 2480 3859 6152 7734 9767
7.5 5.5
30
20
436
694 1107 1753 2728 4349 5467 6904 8698
10 7.5
45
25
-
488
778 1233 1918 3057 3844 4854 6115 7719 9738
15
11
70
40
-
-
546
865 1347 2147 2699 3408 4293 5419 6837 8631
20
15
90
50
-
-
-
646 1005 1601 2013 2543 3203 4043 5101 6439 8113 9578
25 18.5 110
60
-
-
-
535
833 1328 1669 2108 2655 3351 4228 5338 6725 7939 9531
30
22
125
70
-
-
-
-
745 1187 1492 1884 2374 2997 3781 4773 6013 7099 8522 9961
40
30
150
100
-
-
-
-
-
870 1093 1381 1740 2196 2770 3497 4406 5202 6244 7299 8345
lengths meet the us National electrical code ampacity requirements for either individual conductors or jacketed rated 75° c cable and can be in conduit or direct buried. Flat molded and web/
ribbon cable are considered jacketed cable. refer to Nec table 310.15(B)(16) for more information.
CABLE SELECTION
60° C
COPPER CABLE SIZE - From Main Breaker Panel to Motor (in feet)
MOTOR
AWG
MCM
VOLTS HP KW
FUSE
STD
Dual
Element 14
12
10
8
6
4
3
2
1
0
00
000 0000 250 300 350 400 500
THREE PHASE
230 V
60 hz
5
3.7
45
25
-
-
391
620
965 1538 1933 2442 3076 3883 4899 6184 7791 9198
7.5 5.5
60
40
-
-
277
438
682 1087 1367 1726 2174 2745 3463 4372 5508 6502 7806 9124
10 7.5
90
50
-
-
-
-
479
764
961 1213 1529 1930 2434 3073 3872 4571 5488 6415 7334 9125
15
11
125
80
-
-
-
-
-
537
675
852 1073 1355 1709 2158 2719 3210 3853 4504 5149 6407
20
15
175
110
-
-
-
-
-
-
503
636
801 1011 1275 1610 2028 2394 2874 3360 3842 4780
25 18.5 225
125
-
-
-
-
-
-
-
527
664
838 1057 1334 1681 1985 2383 2785 3184 3962
30
22
250
125
-
-
-
-
-
-
-
-
593
749
945 1193 1503 1775 2130 2490 2847 3543
460 V
60 hz
or
380 V
50 hz
5
3.7
20
10
617
982 1566 2480 3859 6152 7734 9767
7.5 5.5
30
20
436
694 1107 1753 2728 4349 5467 6904 8698
10 7.5
45
25
-
-
778 1233 1918 3057 3844 4854 6115 7719 9738
15
11
70
40
-
-
546
865 1347 2147 2699 3408 4293 5419 6837 8631
20
15
90
50
-
-
-
646 1005 1601 2013 2543 3203 4043 5101 6439 8113 9578
25 18.5 110
60
-
-
-
-
833 1328 1669 2108 2655 3351 4228 5338 6725 7939 9531
30
22
125
70
-
-
-
-
745 1187 1492 1884 2374 2997 3781 4773 6013 7099 8522 9961
40
30
150
100
-
-
-
-
-
-
1093 1381 1740 2196 2770 3497 4406 5202 6244 7299 8345
lengths meet the us National electrical code ampacity requirements for either individual conductors or jacketed rated 60° c cable and can be in conduit or direct buried. Flat molded and web/
ribbon cable are considered jacketed cable. refer to Nec table 310.15(B)(16) for more information.
* = motors are 8” diameter