MAKING ELECTRICAL CONNECTIONS

  

 ElECTROCUTION HAZARD:

 Must be 

installed by a qualified professional. Disconnect all electrical 
power before installation or servicing the pump.

All electrical wiring must be in accordance with local codes, 
and only competent electricians should make the installations. 
Complete wiring diagrams are glued to the inside cover of the 
panel. It is VERY IMPORTANT to check all wires for grounds with 
an ohmmeter or Megger meter after the connections are made 

as one grounded wire can cause considerable trouble

.

NOTICE:

 FM rated models are only to be used in  

60hz applications.

IMPORTANT:

 If equipment is not properly wired and protected as 

recommended, the warranty is void.

 The 230 volt 3 phase pump has a dual marked 

nameplate. For ordinary location pumps, voltage may be rewired 
by qualified personnel. For hazardous location pumps, voltage 
may be rewired by the manufacturer or a Class I, Div I equipment 
qualified electrician. Once the voltage is changed, the factory 
cord tag indicating 230 volt 3 phase must be removed.

For record keeping purposes, we suggest the pump be marked 
externally with the new voltage and qualified personnel that 
performed the change. Pumps shipped from the factory as 460 
volt 3 phase cannot be rewired to any other voltage.

TO RE-WIRE THE PUMP FROM 230V TO 460V 3 PHASE

Only a 230V pump from the factory is considered dual voltage, a 
cord label clearly states the factory wound voltage.

1.  Remove all six (#7) cap screws then raise the cord cap 

assembly enough to slip a prying instrument on opposite 
sides between the cord cap casting and the motor housing. 
Take care to not damage the o-ring or the machined 
surfaces of the castings. Doing so could void FM agency 
certifications. 

2.  While prying evenly on both sides; separate the cord cap 

casting from the motor housing, the assembly is airtight 
and will have a vacuum effect when disassembling.

3.  Once separated, the cord cap can be inverted and rotated 

to the outside of the pump assembly, and a bolt can be 
re-used to secure the upside down cord cap to the motor 
housing for ease of rewiring. 

Refer to the wiring diagram within this manual for wiring 
details. Once all electrical connections are finished and secure 
(a crimped electrical connector is best to prevent issues due 
to vibration if required), the cord cap should be re-attached 
reversing the steps above.  Ensure the o-ring is in place and 
perform a hi-pot test for safety once everything is complete.

HEAT SENSORS AND SEAL FAILURE CONNECTIONS

Be sure heat sensor wires are connected in series with the starter 
coil. Connections are provided on the terminal strip.

DUAL VOLTAGE

3 PHASE MOTOR WIRING

230V  3ø

460V  3ø

GREEN

GREEN

R

(L3)

W

(L2)

BL

(L1)

R

(L3)

W

(L2)

BL

(L1)

1

2

3

7

8

9

4

5

6

1

2

3

7

8

9

4

5

6

INSTALLATION

SYSTEM TYPE

NUMBER OF 

CONTROL WIRES

NUMBER OF 

POWER LINES

NUMBER OF 

GROUND WIRES #8

HEAT SENSOR & SEAL FAILURE

NUMBER OF SENSOR 

WIRES

NUMBER OF GROUND 

WIRES

Simplex

4

3

1

3

1

Simplex with Alarm

6

3

1

3

1

Duplex

6

6

2

6

2

Duplex with Alarm

8

6

2

6

2

NUMBER OF CONDUCTORS REQUIRED BETWEEN CONTROL PANEL AND NEMA 4 JUNCTION BOX

Power lines and control wires can be carried in conduit or can be underground buried cable

HEAT SENSORS

 IN MOTOR WINDINGS

BLACK

WHITE

MOTOR HEAT SENSORS

ELECTRODE

ELECTRODE

RED

ORANGE

330KΩ

HAZARDOUS  RATED ONLY

SEAL FAILURE

ELECTRODE

ELECTRODE

RED

ORANGE

NON-HAZARDOUS  RATED ONLY

SEAL FAILURE

HEAT SENSORS AND SEAL FAILURE CONNECTIONS

FOR ANY VOLTAGE MOTOR

Summary of Contents for MNG3SC

Page 1: ...pentair com INSTALLATION OPERATIONMANUAL 23833A733 MY12715 07 15 22 2022 Pentair All Rights Reserved SUBMERSIBLE SOLIDSHANDLINGPUMP MNG3SC X MNG4HC X MNG6MC X...

Page 2: ...TABLEOFCONTENTS SAFETY INSTRUCTIONS 3 SPECIFICATIONS 5 INSTALLATION 7 OPERATION MAINTENANCE 8 TROUBLESHOOTING 10 PARTS LIST 11 WIRING DIAGRAMS 17 WARRANTY 19...

Page 3: ...unit itself before installing or operating pump Keep this manual for future reference Follow all state and local codes regarding the installation and use of this pump GENERAL SAFETY Do not touch a pu...

Page 4: ...water appropriately to ensure satisfactory performance and prevent premature failure OTHER DANGERS RISK OF FIRE OR EXPLOSION Can cause severe personal injury property damage or death Do not smoke or...

Page 5: ...e circuit remains around 330K ohm If the circuit shows open the circuit is not complete indicating a broken wire corroded wire or loose connection If the lower seal leaks and moisture enters this cham...

Page 6: ...ING PUMP IN SUMP HAZARDOUS VOLTAGE Can shock burn or kill When installing operating or servicing this pump carefully follow the safety instructions listed herein RISK OF FIRE OR EXPLOSION Do not smoke...

Page 7: ...re to not damage the o ring or the machined surfaces of the castings Doing so could void FM agency certifications 2 While prying evenly on both sides separate the cord cap casting from the motor housi...

Page 8: ...pump conductor as sometimes a high leg will exist For excessive voltage on one leg the electric utility company should be consulted PUMP MAINTENANCE As the motors are oil filled no lubrication or othe...

Page 9: ...25 30 Ft lbs Ensure all screws have proper torque to prevent backing out A thread locking compound is recommended to prevent vibrational loosening over time 7 Measure the clearance with a feeler gaug...

Page 10: ...Discharge gate valve may be partially closed or partially clogged 2 Check valve may be partially clogged Raise level up and down to clear 3 Pump may be running in wrong direction Low speed pumps can o...

Page 11: ...11 MY12715 07 15 22 MNG3SC MNG4HC MNG6MC PARTS LIST...

Page 12: ...F14 BEARING BALL UPPER 000650111 1 1 F15 BEARING BALL ANG CONTACT DBL ROW 071670181 1 1 F16 PLUG PIPE 1 2 SKT HD 009240101 3 3 F17 SCREW DRIVE 6 045800011 6 6 E8 PROBE SEAL FAILURE 109010011 2 2 E9 SE...

Page 13: ...CREW CAP HEX SOC LINER JACK BOLT 005560211 4 005560211 4 B11 RING O VOL TO SEAL PLATE 001500241 05876A280 05876A280 B12 SCREW CAP HEX SST BRG HSG TO SEAL PLATE 19103A071 4 19103A071 4 B13 SCREW CAP HE...

Page 14: ...3SC015243 28251E023 15 460 3 8 4 6 25 154371102 MNG3SC015253 28251E024 15 575 3 10 4 6 25 154371102 MNG3SCX015203 28251E621 15 208 3 8 4 6 25 154371102 MNG3SCX015223 28251E622 15 230 460 3 8 4 6 25 15...

Page 15: ...MNG4HCX015423 28253E622 15 230 460 3 8 4 10 154471122 MNG4HCX015443 28253E623 15 460 3 8 4 10 154471122 MNG4HCX015453 28253E624 15 575 3 10 4 10 154471122 MNG4HC020403 28253E031 20 208 3 6 4 10 75 154...

Page 16: ...154421062 MNG6MCX015423 28252E622 15 230 460 3 8 4 9 25 154421062 MNG6MCX015443 28252E623 15 460 3 8 4 9 25 154421062 MNG6MCX015453 28252E624 15 575 3 10 4 9 25 154421062 MNG6MC020403 28252E031 20 20...

Page 17: ...17 MY12715 07 15 22 WIRINGDIAGRAMS...

Page 18: ...18 MY12715 07 15 22 WIRINGDIAGRAMS...

Page 19: ...ity this limited warranty will not apply a to defects or malfunctions resulting from failure to properly install operate or maintain the unit in accordance with the printed instructions provided b to...

Page 20: ...products and services Pentair reserves the right to change specifications without prior notice Pentair is an equal opportunity employer Loctite is a registered trademark of Henkel AG Company KGaA 2022...

Reviews: