GENERAL INFORMATION

OVERLOAD HEATERS

If the electrical panel is not used, starters with 3 leg overload 
relay must be supplied on 3 phase pumps. Each leg is to have an 
identical heater sized in accordance with the nameplate amps on 
the motor housing. The amp draw on these submersible motors is 
slightly higher than a corresponding horsepower surface motor, 
so heaters must be sized by the nameplate rating.

INSTALLING SUMP LEVEL CONTROLS FLOAT CONTROLS

In all systems,  the lower or turn-off control is to be set to 
maintain a minimum level in the sump. This level shall be no 
more than 3-1/4" from the top of the motor housing down to the 
surface of the sewage.

The second or turn-on control is set above the lower turn-off 
control. The exact distance between the two floats must be a 
compromise between a frequent pumping cycle (15 starts per hour 
max.) to control septicity, solids and a slower cycle for energy 
economy. This distance should be determined by the engineer or 
consulting engineer, depending on the conditions of  
the application. 

INSTALLING PUMP IN SUMP

  

HAZARDOUS VOLTAGE.

 Can shock, burn, or kill. 

When installing, operating, or servicing this pump, carefully 
follow the safety instructions listed herein.

  

RISK OF FIRE OR EXPLOSION.

 Do not smoke or 

use open flames in or around this system. Only the FM listed 
products are to be used in a hazardous location applications per 
NFPA 70 National Electric Code. Do not pump flammable liquids.  
Do not use non-hazardous pumps in explosive environments. 

Before installing the pump in the sump, lay it on its side and rotate 
impeller. Impeller may be slightly stuck due to factory test water. 
The impeller should turn freely. 

DO NOT

 connect the power until 

after this test.

Clean all debris from sump and connect pump to piping. A check 
valve must be installed on each pump and a gate or plug valve 
in each pump discharge is highly recommended. This valve 
should be installed on the discharge side of the check valve so 
if it becomes necessary to service the check valve, the line 
pressure can be cut off. Single pump systems are sometimes 
installed without a check valve where it is desirable to self-drain 
the discharge line to prevent freezing. This can be done only with 
short discharge lines; otherwise water will return to the sump and 
cause short cycling of the pump.

Summary of Contents for MNG3SC

Page 1: ...pentair com INSTALLATION OPERATIONMANUAL 23833A733 MY12715 07 15 22 2022 Pentair All Rights Reserved SUBMERSIBLE SOLIDSHANDLINGPUMP MNG3SC X MNG4HC X MNG6MC X...

Page 2: ...TABLEOFCONTENTS SAFETY INSTRUCTIONS 3 SPECIFICATIONS 5 INSTALLATION 7 OPERATION MAINTENANCE 8 TROUBLESHOOTING 10 PARTS LIST 11 WIRING DIAGRAMS 17 WARRANTY 19...

Page 3: ...unit itself before installing or operating pump Keep this manual for future reference Follow all state and local codes regarding the installation and use of this pump GENERAL SAFETY Do not touch a pu...

Page 4: ...water appropriately to ensure satisfactory performance and prevent premature failure OTHER DANGERS RISK OF FIRE OR EXPLOSION Can cause severe personal injury property damage or death Do not smoke or...

Page 5: ...e circuit remains around 330K ohm If the circuit shows open the circuit is not complete indicating a broken wire corroded wire or loose connection If the lower seal leaks and moisture enters this cham...

Page 6: ...ING PUMP IN SUMP HAZARDOUS VOLTAGE Can shock burn or kill When installing operating or servicing this pump carefully follow the safety instructions listed herein RISK OF FIRE OR EXPLOSION Do not smoke...

Page 7: ...re to not damage the o ring or the machined surfaces of the castings Doing so could void FM agency certifications 2 While prying evenly on both sides separate the cord cap casting from the motor housi...

Page 8: ...pump conductor as sometimes a high leg will exist For excessive voltage on one leg the electric utility company should be consulted PUMP MAINTENANCE As the motors are oil filled no lubrication or othe...

Page 9: ...25 30 Ft lbs Ensure all screws have proper torque to prevent backing out A thread locking compound is recommended to prevent vibrational loosening over time 7 Measure the clearance with a feeler gaug...

Page 10: ...Discharge gate valve may be partially closed or partially clogged 2 Check valve may be partially clogged Raise level up and down to clear 3 Pump may be running in wrong direction Low speed pumps can o...

Page 11: ...11 MY12715 07 15 22 MNG3SC MNG4HC MNG6MC PARTS LIST...

Page 12: ...F14 BEARING BALL UPPER 000650111 1 1 F15 BEARING BALL ANG CONTACT DBL ROW 071670181 1 1 F16 PLUG PIPE 1 2 SKT HD 009240101 3 3 F17 SCREW DRIVE 6 045800011 6 6 E8 PROBE SEAL FAILURE 109010011 2 2 E9 SE...

Page 13: ...CREW CAP HEX SOC LINER JACK BOLT 005560211 4 005560211 4 B11 RING O VOL TO SEAL PLATE 001500241 05876A280 05876A280 B12 SCREW CAP HEX SST BRG HSG TO SEAL PLATE 19103A071 4 19103A071 4 B13 SCREW CAP HE...

Page 14: ...3SC015243 28251E023 15 460 3 8 4 6 25 154371102 MNG3SC015253 28251E024 15 575 3 10 4 6 25 154371102 MNG3SCX015203 28251E621 15 208 3 8 4 6 25 154371102 MNG3SCX015223 28251E622 15 230 460 3 8 4 6 25 15...

Page 15: ...MNG4HCX015423 28253E622 15 230 460 3 8 4 10 154471122 MNG4HCX015443 28253E623 15 460 3 8 4 10 154471122 MNG4HCX015453 28253E624 15 575 3 10 4 10 154471122 MNG4HC020403 28253E031 20 208 3 6 4 10 75 154...

Page 16: ...154421062 MNG6MCX015423 28252E622 15 230 460 3 8 4 9 25 154421062 MNG6MCX015443 28252E623 15 460 3 8 4 9 25 154421062 MNG6MCX015453 28252E624 15 575 3 10 4 9 25 154421062 MNG6MC020403 28252E031 20 20...

Page 17: ...17 MY12715 07 15 22 WIRINGDIAGRAMS...

Page 18: ...18 MY12715 07 15 22 WIRINGDIAGRAMS...

Page 19: ...ity this limited warranty will not apply a to defects or malfunctions resulting from failure to properly install operate or maintain the unit in accordance with the printed instructions provided b to...

Page 20: ...products and services Pentair reserves the right to change specifications without prior notice Pentair is an equal opportunity employer Loctite is a registered trademark of Henkel AG Company KGaA 2022...

Reviews: