OM3 - EPI-2 LOcaL IntErfacE MOduLE
InstallatIon and MaIntenance InstructIons
• Connect the Local Interface module to the
ground stud by screwing the ‘ground kit’
(screw + toothed washer).
fIgures 6/6a -
Grounding the Local Interface
• Take the 4 screws for connecting the Local
Interface black connector to the terminal
board, in pos. 28-29-30-31 (see figures 7/7a
and wiring diagram), and connect it with the
screwdriver (see figure 8).
fIgures 7/7a -
Position of the Local Interface connector on the terminal board
fIgure 8 -
connecting the Local Interface connector
• Now the Local Interface is connected to the
actuator (see figure 9).
• Take the 4 screws removed from terminal
board cover and use them to fix the Local
Interface to the actuator, using the 5 mm
allen key (see figure 10).
fIgure 9 -
OM3 kit connected to the EPI-2
terminal board
fIgure 10 -
fixing the local interface onto
the EPI-2 actuator
• The installation of the OM3 Local Interface
module onto the EPI-2 actuator is
now complete.
IMportant
Please note that the design of the Local Interface
black connector has been engineered to allow the
installation in one way only.
Due to the special design, it is not possible to
reverse the connection of the 4 cables to the
terminal board and it is not possible to make a
wrong connection of the connector.