MASTER PROGRAMMING MODE FLOW
CHART
continued
DIAGNOSTIC PROGRAMMING MODE
FLOW CHART
Entering Diagnostic Programming Mode
1. Push and release the "D" button.
2. Press the Extra Cycle button once per display until all
displays are viewed and Normal Display is resumed.
3. Push and release the"D" button at anytime during
diagnostic mode and the timer will exit the mode.
4. Depending on the current controller programming, certain
displays may not be able to be viewed or set.
Overview Diagnostic Mode
The current diagnostic will be displayed until Extra Cycle key is
pressed. There is no time limit on each display. The timer will
display local information, not system information. In the event
of a regeneration occurring while displaying diagnostics, the
regeneration step and time remaining will be displayed. When
regeneration has been completed, the display will return to the
main screen.
CURRENT FLOW
RATE: 0 gpm
PEAK FLOW RATE:
0 gpm
TOTALIZER:
130 g
LAST TWO REGENS:
0 HOURS
LAST REGEN
0 HOURS
VOLUME REMAIN:
1000 g
VALVE ADDRESS
#2
VERSION:
X.XX
NOTE: If a System 6, Unit #1 of “Tank Remaining” will display “System
Remaining”.
Example:
Flow rate at this time.
Example:
Peak flow since last regeneration.
Example:
Gallons at the outlet since installation.
Example:
Hours between the last regeneration and the
one before it.
Example:
Hours since last regeneration.
Example:
Volume remaining (can be adjusted).
Example:
Controller unit number.
Example:
Installed software level of the controller in use.
USER PROGRAMMING MODE FLOW CHART
Entering User Programming Mode
Hold the Set Up and Set Down buttons for 5 seconds.
NOTE: User Mode is only displayed when a metered option
is chosen under System Type. Depending on current
option settings, some displays cannot be viewed or
set.
NOTE: User Mode cannot be entered on the Lag unit for
System 6.
mg/l
FEED WATER
HARDNESS: gpg
REGENERATION DAY
OVERRIDE: OFF
REGENERATION DAY
OVERRIDE:99 DAYS
REGENERATION
TIME: 02:00AM
VALVE ADDRESS:
#2
Options:
Valve Address #1 (First Control Valve)
Valve Address #2 (Second Control Valve)
(Default)
Valve Address #3 (Third Control Valve)
Valve Address #4 (Fourth Control Valve)
SYSTEM TYPE: 4
SINGLE UNIT
Options:
System 4 (single unit)
System 5 (2-4 units) Parallel Interlock
System 6 (2-4 units) Parallel Series Regeneration
System 7 (2 units) Alternating
System 9 (2-4 units) Alternating
System 14 (2-4 units) Demand Recall
Example:
System Type 4, Single Unit
Example:
Valve Address #2 (Second Control Valve)
(Default)
Example:
U.S. Gallons
(Default)
SELECT LANGUAGE:
ENGLISH
Options:
English
Espanol
Portugues
Deutsch
Francais
Example:
English
VALVE TYPE:
2750
Options: 2750 (Default)
2815
2850
2900
3150
3900
Stager - Notch Cam
Example:
2750
(Default)
REGEN TYPE:
TIME CLK DELAYED
Options:
Time Clock Delayed (System 4 Only)
(Default)
Meter Immediate (All System Types)
Meter Delayed Fixed Reserve (Systems 4 & 6 Only)
Example:
Time Clock Delayed
(Default)
REGENERANT FLOW:
DOWNFLOW
Options:
Downflow
(Default)
Up Flow
UF Fill First
Example:
Downflow
(Default)
REMOTE SIGNAL
START: 00:06:00
Options:
Off
(Default)
00:00:00 (Hours:Minutes:Seconds)
Range:
1 second to 99 minutes (1 hour, 39 minutes)
NOTE: This display will not be viewed in System 4
Example:
00:06:00
(Hours:Minutes:Seconds)
NOTE: This screen will not display for System Type 4.
SYSTEM SIZE:
2 VALVES
Options:
2 Valves in the System
(Default)
3 Valves in the System
4 Valves in the System
Example:
2 Valves in the System
(Default)
Range:
2 to 4 Valves in the System
NOTE: This screen will not display for System Type 4.
DISPLAY FORMAT:
US-GALLONS
Options:
U.S. - Gallons
(Default)
Eu Metric - Liters (Metric)
NOTE: In European Units - Liters (Metric) mode, the display will be in
24-hour time.
NOTE: In U.S. - Gallons mode, the display will be in 12-hour time.
UNIT CAPACITY:
00000000 GRAINS
Options:
Grains (in U.S. Format)
(Default)
Grams (in Metric Format)
Example:
Grains
(Default)
NOTE: Use the Shift button to move to the left.
Range:
1 to 9,900,000 Grain Capacity in U.S. Format
1 to 198,000 grams CaCO3 Capacity in Metric Format
Example:
00%
(Default)
CAPACITY SAFETY
FACTOR: 00%
Range:
0 to 50%
NOTE: Use the Shift button to move to the left.
FEED WATER
HARDNESS: 15 GPG
Range:
1 to 199 Grains/Gallon (U.S. Format)
20 to 1,999 miligrams CaCO3/L (Metric Format)
Example:
15 GPG (U.S. Format)
(Default)
NOTE: Use the Shift button to move to the left.
NOTE: This screen will only display on the lead unit for System Types 6 & 7.
For all other System Types, it will display for all units.
TRIP POINT 1:
000 gpm
NOTE: Display will not appear unless timer is programmed as valve position
#1. Use the Shift button to change each decimal position.
REGENERATION DAY
OVERRIDE:OFF
Example:
Off
(Default)
On
(Default for time clock)
REGENERATION DAY
OVERRIDE:01 DAYS
Options:
Off
(Default for meter)
or On
Example:
1 Day
Range:
1 to 99 Days
REGENERATION
TIME: 02:00AM
Example:
2:00 A.M.
(Default)
Options:
A.M. (U.S. Format)
HR (Metric Format)
NOTE: Regeneration time will not appear unless Regeneration Day Override
is on.
CYCLE 1 00:00:00
BACK WASH
Example:
Cycle 1 in Back Wash Mode
Options:
Regeneration Cycle Step #1
Regeneration Cycle Step #2
Regeneration Cycle Step #3
Regeneration Cycle Step #4
Regeneration Cycle Step #5
NOTE: Please refer to the “Regenerant Flow Default Cycle Steps & Times”
in the Master Programming Mode section of the manual.
NOTE: If Stager is chosen for Valve Type, the Regeneration Cycle Step
description will not display.
AUXILIARY RELAY:
DISABLED
Example:
Auxiliary Relay is Disabled
Options:
Enabled
Disabled
(Default)
AUX RELAY OUTPUT
START 1 00:00:00
Example:
Auxiliary Relay Output in Start 1 at
0 hours, 0 minutes, & 0 seconds
Range:
00:00:00 to 18:00:00
NOTE: Only displayed if Auxiliary Relay is enabled in previous screen.
Auxiliary Relay will only display if Chemical Pump is OFF for System
Types 6 & 7.
AUX RELAY OUTPUT
END 1 00:00:00
Example:
Auxiliary Relay Output in End 1 at
0 hours, 0 minutes, & 0 seconds
Range:
00:00:00 to 18:00:00
CHEMICAL PUMP:
DISABLED
Example:
Chemical Pump is Disabled
Options:
Enabled
Disabled
(Default)
NOTE: This screen will only display on the lead unit for System Types 6 & 7.
For all other System Types, it will display for all units.
CPO AUX RELAY
VOLUME: 000 g
Example:
Energize Chemical Pump Relay Every 50 Gallons
Energize Chemical Pump Relay Every 200 L
Range:
1 to 999 gallons in U.S. Format
1 to 9999 L in Metric Format
NOTE: Only displayed on units that physically have a meter (Lead always has
a meter). Only shown if Auxiliary Relay is disabled on System Types 6 & 7.
CPO AUX RELAY
TIME: 00:00:00
Example:
Each Time the Chemical Pump Relay is on, Run
for 30 Seconds (00:00:30)
Range:
00:00:00 to 02:00:00
FLOW METER:
1.0 PADDLE
Example:
1.0 Paddle Flow Meter
Options:
1.0 Paddle (Fleck)
1.0 Turbine (Fleck)
1.5 Paddle (Fleck)
1.5 Turbine (Fleck)
2.0 Paddle (Fleck)
3.0 Paddle (Fleck)
Generic (Non-Fleck)
NOTES: Default flow meter type is based on the valve type. This screen will
only display on the lead unit for System Types 6 & 7. All other system types
it will display for all units.
MAXIMUM FLOW
RATE: 0000 gpm
Example:
Maximum Flow Rate of 0 gpm
Range:
20 - 2000 gpm (U.S. Format)
20 - 2000 L (Metric Format)
NOTE: Only displayed if “Generic” is chosen for the flow meter.
Range:
1 - 255 Gallons (U.S. Format)
1 - 255L (Metric Format)
Pulses: 1 - 255
Options:
Gallons (U.S. Format)
Liters (Metric Format)
ADD 01 GALLONS
EVERY 001 PULSES
Example:
Add 1 Gallon for Each Pulse in U.S. Format
NOTE: Only displayed if “Generic” is chosen for the flow meter.
PROGRAMMING UNIT
PLEASE WAIT...
Example:
Master Programming Mode is Exiting
NOTE: Display will not appear unless timer is programmed as valve position
#1. Use the Shift button to move one space to the left.
TRIP DELAY 1:
30 SECONDS
NOTE: Display will not appear unless timer is programmed as valve position
#1. System size must be 3 or 4 to appear. Use the Shift button to move one
space to the left.
TRIP DELAY 2:
30 SECONDS
NOTE: Display will not appear unless timer is programmed as valve position
#1. System size must be 3 or 4 to appear. Use the Shift button to move one
space to the left.
TRIP POINT 2:
gpm
NOTE: Display will not appear unless timer is programmed as valve position
#1. System size must be 4 to appear. Use the Shift button to move one
space to the left.
TRIP POINT 3:
gpm
NOTE: Display will not appear unless timer is programmed as valve position
#1. System size must be 4 to appear. Use the Shift button to move one
space to the left.
TRIP DELAY 3:
30 SECONDS
Examples:
Default will need to be changed before next step [000] =
(Default)
Brings 2nd valve In Service after 125 gpm
[125]
Brings 2nd valve In Service after 400 lpm
[400]
Range:
1 to 997 gpm (U.S. Format)
0.01 to 3997 lpm (Metric Format)
Examples:
Brings 3rd valve In Service after 250 gpm [250]
Brings 3rd valve In Service after 900 lpm [900]
Range:
Trip Point 1 + 1 to 998 gpm (U.S. Format)
Trip Point 1 + 1 to 3998 lpm (Metric Format)
Examples:
Brings 4th valve In Service after 350 gpm [350]
Brings 4th valve In Service after 1300 lpm [1300]
Range:
Trip Point 2 + 1 to 999 gpm (U.S. Format)
Trip Point 2 + 1 to 3999 lpm (Metric Format)
Fleck
3200 NXT • 11