background image

MASTER PROGRAMMING MODE FLOW 
CHART 

continued

DIAGNOSTIC PROGRAMMING MODE  
FLOW CHART

Entering Diagnostic Programming Mode

1.  Push and release the "D" button.
2.  Press the Extra Cycle button once per display until all 

displays are viewed and Normal Display is resumed.

3.  Push and release the"D" button at anytime during 

diagnostic mode and the timer will exit the mode.

4.  Depending on the current controller programming, certain 

displays may not be able to be viewed or set.

Overview Diagnostic Mode

The current diagnostic will be displayed until Extra Cycle key is 

pressed. There is no time limit on each display. The timer will 

display local information, not system information. In the event 

of a regeneration occurring while displaying diagnostics, the 

regeneration step and time remaining will be displayed. When 

regeneration has been completed, the display will return to the 

main screen.

CURRENT FLOW

RATE:      0 gpm

PEAK FLOW RATE:

           0 gpm

TOTALIZER:

          130 g

LAST TWO REGENS:

         0 HOURS

LAST REGEN

         0 HOURS

VOLUME REMAIN:
         1000 g

VALVE ADDRESS

#2

VERSION:
            X.XX

NOTE: If a System 6, Unit #1 of “Tank Remaining” will display “System 

Remaining”.

Example:

Flow rate at this time.

Example:

Peak flow since last regeneration.

Example:

Gallons at the outlet since installation.

Example:

Hours between the last regeneration and the 

one before it.

Example:

Hours since last regeneration.

Example:

Volume remaining (can be adjusted).

Example:

Controller unit number.

Example:

Installed software level of the controller in use.

USER PROGRAMMING MODE FLOW CHART

Entering User Programming Mode

Hold the Set Up and Set Down buttons for 5 seconds.

NOTE: User Mode is only displayed when a metered option 

is chosen under System Type. Depending on current 

option settings, some displays cannot be viewed or 

set.

NOTE: User Mode cannot be entered on the Lag unit for 

System 6.

mg/l

FEED WATER
HARDNESS:    gpg

REGENERATION DAY
OVERRIDE: OFF

REGENERATION DAY
OVERRIDE:99 DAYS

REGENERATION
TIME:    02:00AM

VALVE ADDRESS:
              #2

Options:

 Valve Address #1 (First Control Valve)

 Valve Address #2 (Second Control Valve) 

(Default)

 Valve Address #3 (Third Control Valve)

 Valve Address #4 (Fourth Control Valve)

 

SYSTEM TYPE:   4
  SINGLE UNIT

Options:

 System 4 (single unit)

 

System 5 (2-4 units) Parallel Interlock

 

System 6 (2-4 units) Parallel Series Regeneration

 

System 7 (2 units) Alternating

 

System 9 (2-4 units) Alternating

 

System 14 (2-4 units) Demand Recall

Example:

System Type 4, Single Unit

Example:

Valve Address #2 (Second Control Valve) 

(Default)

Example:

U.S. Gallons 

(Default)

SELECT LANGUAGE:
  ENGLISH

Options:

 English

 

Espanol

 

Portugues

 

Deutsch

 

Francais

Example:

English

VALVE TYPE:
            2750

Options:  2750 (Default) 

 

2815

 

2850

 

2900

 

3150

 

3900

 Stager - Notch Cam  

Example:

2750 

(Default)

REGEN TYPE:
TIME CLK DELAYED

Options:

 Time Clock Delayed (System 4 Only) 

(Default)

 

Meter Immediate (All System Types)

 

Meter Delayed Fixed Reserve (Systems 4 & 6 Only)

Example:

Time Clock Delayed 

(Default)

REGENERANT FLOW:
        DOWNFLOW

Options:

 Downflow 

(Default)

 

Up Flow

 

UF Fill First

Example:

Downflow 

(Default)

REMOTE SIGNAL
START:  00:06:00

Options:

 Off 

(Default)

 

00:00:00 (Hours:Minutes:Seconds)

Range: 

1 second to 99 minutes (1 hour, 39 minutes)

NOTE: This display will not be viewed in System 4

Example:

00:06:00

(Hours:Minutes:Seconds)

NOTE: This screen will not display for System Type 4.

SYSTEM SIZE:
        2 VALVES

Options:

 2 Valves in the System 

(Default)

 

3 Valves in the System

 

4 Valves in the System

Example:

2 Valves in the System 

(Default)

Range:

 2 to 4 Valves in the System

NOTE: This screen will not display for System Type 4.

DISPLAY FORMAT:
US-GALLONS

Options:

 U.S. - Gallons 

(Default)

 

Eu Metric - Liters (Metric)

NOTE: In European Units - Liters (Metric) mode, the display will be in 

24-hour time.

NOTE: In U.S. - Gallons mode, the display will be in 12-hour time.

UNIT CAPACITY:
 00000000 GRAINS

Options:

 Grains (in U.S. Format) 

(Default)

 

Grams (in Metric Format)

Example:

Grains 

(Default)

NOTE: Use the Shift button to move to the left.

Range: 

1 to 9,900,000 Grain Capacity in U.S. Format

 

1 to 198,000 grams CaCO3 Capacity in Metric Format

Example:

00% 

(Default)

CAPACITY SAFETY
FACTOR:      00%

Range: 

0 to 50%

NOTE: Use the Shift button to move to the left.

FEED WATER
HARDNESS: 15 GPG

Range: 

1 to 199 Grains/Gallon (U.S. Format)

 

20 to 1,999 miligrams CaCO3/L (Metric Format)

Example:

15 GPG (U.S. Format) 

(Default)

NOTE: Use the Shift button to move to the left.
NOTE: This screen will only display on the lead unit for System Types 6 & 7.

For all other System Types, it will display for all units.

TRIP POINT 1:
  

 000 gpm

NOTE: Display will not appear unless timer is programmed as valve position 

#1. Use the Shift button to change each decimal position.

REGENERATION DAY
OVERRIDE:OFF

Example:

Off 

(Default)

On 

(Default for time clock)

REGENERATION DAY
OVERRIDE:01 DAYS

Options: 

Off 

(Default for meter)

 or On

Example:

1 Day

Range: 

1 to 99 Days

REGENERATION
TIME:    02:00AM

Example:

2:00 A.M. 

(Default)

Options: 

A.M. (U.S. Format)

 

HR (Metric Format)

NOTE: Regeneration time will not appear unless Regeneration Day Override 

is on.

CYCLE 1 00:00:00
       BACK WASH

Example:

Cycle 1 in Back Wash Mode

Options:

 Regeneration Cycle Step #1

 

Regeneration Cycle Step #2

 

Regeneration Cycle Step #3

 

Regeneration Cycle Step #4

 

Regeneration Cycle Step #5

NOTE: Please refer to the “Regenerant Flow Default Cycle Steps & Times” 

in the Master Programming Mode section of the manual.
NOTE: If Stager is chosen for Valve Type, the Regeneration Cycle Step 

description will not display.

AUXILIARY RELAY:
DISABLED

Example:

Auxiliary Relay is Disabled

Options:

 Enabled

 

Disabled 

(Default)

AUX RELAY OUTPUT
START 1 00:00:00

Example:

Auxiliary Relay Output in Start 1 at 

0 hours, 0 minutes, & 0 seconds

Range:

  00:00:00 to 18:00:00

NOTE: Only displayed if Auxiliary Relay is enabled in previous screen. 

Auxiliary Relay will only display if Chemical Pump is OFF for System 

Types 6 & 7.

AUX RELAY OUTPUT
END 1 00:00:00

Example:

Auxiliary Relay Output in End 1 at 

0 hours, 0 minutes, & 0 seconds

Range:

  00:00:00 to 18:00:00

CHEMICAL PUMP:
        DISABLED

Example:

Chemical Pump is Disabled

Options:

 Enabled

 

Disabled 

(Default)

NOTE: This screen will only display on the lead unit for System Types 6 & 7. 

For all other System Types, it will display for all units.

CPO AUX RELAY
VOLUME:   000 g

Example:

Energize Chemical Pump Relay Every 50 Gallons

Energize Chemical Pump Relay Every 200 L

Range:

  1 to 999 gallons in U.S. Format

 

1 to 9999 L in Metric Format

NOTE: Only displayed on units that physically have a meter (Lead always has 

a meter). Only shown if Auxiliary Relay is disabled on System Types 6 & 7.

CPO AUX RELAY
TIME:   00:00:00

Example:

Each Time the Chemical Pump Relay is on, Run 

for 30 Seconds (00:00:30)

Range:

  00:00:00 to 02:00:00

FLOW METER:
      1.0 PADDLE

Example:

1.0 Paddle Flow Meter

Options:

 1.0 Paddle (Fleck)

 

1.0 Turbine (Fleck)

 

1.5 Paddle (Fleck)

 

1.5 Turbine (Fleck)

 

2.0 Paddle (Fleck)

 

3.0 Paddle (Fleck)

 Generic (Non-Fleck)

NOTES: Default flow meter type is based on the valve type. This screen will 

only display on the lead unit for System Types 6 & 7. All other system types 

it will display for all units.

MAXIMUM FLOW
RATE:   0000 gpm

Example:

Maximum Flow Rate of 0 gpm

Range: 

20 - 2000 gpm (U.S. Format)

 

20 - 2000 L (Metric Format)

 

NOTE: Only displayed if “Generic” is chosen for the flow meter.

Range: 

1 - 255 Gallons (U.S. Format)

 

1 - 255L (Metric Format)

 Pulses: 1 - 255

Options: 

Gallons (U.S. Format)

 

Liters (Metric Format)

ADD 01 GALLONS
EVERY 001 PULSES

Example:

Add 1 Gallon for Each Pulse in U.S. Format

NOTE: Only displayed if “Generic” is chosen for the flow meter.

PROGRAMMING UNIT
PLEASE WAIT...

Example:

Master Programming Mode is Exiting

NOTE: Display will not appear unless timer is programmed as valve position 

#1. Use the Shift button to move one space to the left.

TRIP DELAY 1:
 

30 SECONDS

NOTE: Display will not appear unless timer is programmed as valve position 

#1. System size must be 3 or 4 to appear. Use the Shift button to move one 

space to the left.

TRIP DELAY 2:
 

30 SECONDS

NOTE: Display will not appear unless timer is programmed as valve position 

#1. System size must be 3 or 4 to appear. Use the Shift button to move one 

space to the left.

TRIP POINT 2:
  gpm

NOTE: Display will not appear unless timer is programmed as valve position 

#1. System size must be 4 to appear. Use the Shift button to move one 

space to the left.

TRIP POINT 3:
  gpm

NOTE: Display will not appear unless timer is programmed as valve position 

#1. System size must be 4 to appear. Use the Shift button to move one 

space to the left.

TRIP DELAY 3:
 

30 SECONDS

Examples:  

Default will need to be changed before next step      [000] = 

(Default)

  

   Brings 2nd valve In Service after 125 gpm 

     [125]

  

   Brings 2nd valve In Service after 400 lpm 

     [400]

Range:      

1 to 997 gpm (U.S. Format)

  

   0.01 to 3997 lpm (Metric Format)

Examples:  

Brings 3rd valve In Service after 250 gpm     [250]

  

   Brings 3rd valve In Service after 900 lpm       [900]

Range:      

Trip Point 1 + 1 to 998 gpm (U.S. Format)

  

   Trip Point 1 + 1 to 3998 lpm (Metric Format)

Examples:  

Brings 4th valve In Service after 350 gpm         [350]

  

   Brings 4th valve In Service after 1300 lpm       [1300]

Range:      

Trip Point 2 + 1 to 999 gpm (U.S. Format)

  

   Trip Point 2 + 1 to 3999 lpm (Metric Format)

Fleck

 3200 NXT • 11

Summary of Contents for FLECK NXT TIMER

Page 1: ...FLECK NXT TIMER SERVICE MANUAL waterpurification pentair com...

Page 2: ...UPPER 2900S LOWER POWERHEAD ASSEMBLY 13 3150 3900 UPPER LOWER POWERHEAD ASSEMBLY 15 METER ASSEMBLY PLASTIC 17 1 INCH BRASS METER ASSEMBLY 18 1 INCH STAINLESS STEEL METER ASSEMBLY 19 1 1 2 INCH BRASS M...

Page 3: ...operation CYCLE 1 00 00 00 BACK WASH Example 12 minutes remaining in Cycle 1 Backwash Press the Extra Cycle button during a system queued Regeneration Cycle to immediately advance the valve to the nex...

Page 4: ...has left Standby and returned to Service When the Regeneration cycle is complete the regenerated unit will enter Standby Standby on each tank is controlled by the lower drive output terminals on the...

Page 5: ...4 5 The third valves returns to stand by as demand decreases past the second trip point Standby Flow Split Between Two Meters 1 2 3 4 6 Valves return to stand by due to decreased total flow rate and...

Page 6: ...CHG will be displayed when the lower drive changes from one state to another in dual piston valves INI Initializing INI will display on the screen for 30 to 45 seconds when initializing after a power...

Page 7: ...e Transformer 1 Locate the ground label to find the screw to attach the ground wire on the transformer 2 Remove the screw and attach the ground wire and re attach the screw 3 Insert white and black tr...

Page 8: ...nges press the Diagnostic button NOTE If no keypad activity is made for 5 minutes while in the Master Programming Mode or if there is a power failure no changes will be saved and the unit will go back...

Page 9: ...time NOTE In U S Gallons mode the display will be in 12 hour time UNIT CAPACITY 00000000 GRAINS Options Grains in U S Format Default Grams in Metric Format Example Grains Default NOTE Use the Shift b...

Page 10: ...nse 1 Hour Backwash 10 Minutes UF Fill First Brine Tank Fill 12 Minutes Brine Making 1 Hour Regenerant Flow Cycle 3 Time Cycle 4 Time Downflow Rapid Rinse 10 Minutes Brine Tank Fill 12 Minutes UF Brin...

Page 11: ...ate at this time Example Peak flow since last regeneration Example Gallons at the outlet since installation Example Hours between the last regeneration and the one before it Example Hours since last r...

Page 12: ...Start c c c c c c c c c c c c c c c c c c c c c Aux Relay Output End c c c c c c c c c c c c c c c c c c c c c Chemical Pump x x x x x x u u x x x x x x x x CPO Aux Relay Volume c c c c c c c c c c c...

Page 13: ...ERHEAD ASSEMBLY 37 35 31 41 39 32 19 7 6 30 36 32 40 20 38 33 22 52 12 21 13 44 16 14 15 14 17 16 46 25 16 26 1 42 23 46 2 11 4 3 5 6 7 10 19 32 28 29 18 6 11 43 9 8 32 24 61501 3200NXT 2_Page2_REVA 2...

Page 14: ...e 27 1 60217 02 Cover Assy 2900 Lower Black Environmental 28 1 18626 Spacer Indicator 29 1 18746 Bearing Connecting Rod 30 2 11224 Screw Hex Hd 5 16 18 X 5 8 Ss 31 1 10250 Ring Retaining 32 7 10872 Sc...

Page 15: ...5 9 27 26 11 46 7 8 12 6 47 40 42 4 11 45 15 25 35 16 43 23 44 18 17 20 21 22 31 23 27 26 11 10 8 13 12 11 19 15 25 17 16 24 34 9 14 28 29 32 28 38 30 50 24 28 49 32 52 37 48 23 31 22 21 20 18 33 52 3...

Page 16: ...0VA 41049 Transformer Euro 230V 24V 108VA 41050 Transformer Aust 230V 24V 108VA 36 1 19121 Meter Cable Assembly 19121 08 Meter Cable Assembly 35 inch long with connector 19121 09 Meter Cable Assembly...

Page 17: ...1 1 2 BSP Plastic w O Ring 20 61560 Meter Assy 1 1 2 INLN ELEC PLAS w o Nipples TURB 61560 01 Meter Assy 1 INLN NPT ELEC PLAS PLAS Nipples TURB 61560 02 Meter Assy 1 INLN BSP ELEC PLAS PLAS Nipples T...

Page 18: ...r 1 9 1 13287 O ring 123 10 1 14961 10 Fitting 1 Quick Connector BSP 11 1 14962 Nut Quick Connect NPT 12 1 60613 Meter Assy 1 Inline NPT Electronic Brass PDL 60613NP Meter Assy 1 Inline NPT Electronic...

Page 19: ...tended Range 1 61932 20 Meter Assy 1 inch Inline Stainless Steel BSP Standard Range 1 61932 21 Meter Assy 1 inch Inline Stainless Steel BSP Extended Range 3 1 44022 Union 1 inch NPT Optional on models...

Page 20: ...12 1 60614 Meter Assy 1 1 2 Inline NPT Electronic Brass Body PDL 60614NP Meter Assy 1 1 2 INLN NPT ELEC BRS BDY NP PDL 60614 01 Meter Assy 1 1 2 INLN NPT ELEC BRS BDY PDL 1 SLV 60614 01NP Meter Assy...

Page 21: ...1 2 inch Inline Stainless Steel BSP Standard Range 1 61933 21 Meter Assy 1 1 2 inch Inline Stainless Steel BSP Extended Range 3 1 44024 Union 1 1 2 inch NPT Optional on models with electronic controls...

Page 22: ...NP Fitting Nipple 2 BSP Brass NP 14 1 14679 O ring 227 15 1 14569 Nut Quick Connect 16 60615 Meter Assy 2 INLN NPT ELEC BRS PDL 1 5 SLV 60615NP Meter Assy 2 INLN NPT ELEC NP PDL 1 5 SLV 60615 20 Meter...

Page 23: ...el BSP Standard Range 1 61934 21 Meter Assy 2 inch Inline Stainless Steel BSP Extended Range 3 1 44026 Union 2 inch NPT Optional on models with electronic controls 1 44027 Union 2 inch BSP Optional on...

Page 24: ...Flow Straightener 11 8 40118 Screw SCKT HD 1 2 13 UN 12 8 16386 Nut Hex Jam 1 2 13 18 8 S S 13 6 12473 Screw Hex Washer Head 10 24 x 0 625 14 60617 Meter Assy 3 INLN NPT Electronic BRS BDY Paddlewhee...

Page 25: ...ange 61935 11 Meter Assy 3 Inch Inline Stainless Steel NPT Extended Range 61935 20 Meter Assy 3 Inch Inline Stainless Steel BSP Standard Range 61935 21 Meter Assy 3 Inch Inline Stainless Steel BSP Ext...

Page 26: ...NAL SOLENOID VALVE ON DURING REGENERATION OR STANDBY P6 OUTPUT 24VAC 50 60Hz 0 25 A MAX OPTIONAL INTERLOCK SWITCH N O UNSWITCHED HOT 24VAC 3A MAX RESISTIVE 30VDC 3A MAX RESISTIVE NEUTRAL SWITCHED HOT...

Page 27: ...H N O 24VAC 3A MAX RESISTIVE 30VDC 3A MAX RESISTIVE SWITCHED HOT BLACK ORANGE RED WHITE BLACK C N O N C SW 4 GREEN LDCAM LDM RED BLACK WHITE GREEN LOWER DRIVE UPPER DRIVE BLACK RED GREEN OPTIONAL MOTO...

Page 28: ...WHITE STRIPE RED WHITE STRIPE GREEN WHITE STRIPE WHITE BLACK STRIPE RED BLACK STRIPE BLUE BLACK STRIPE BLUE WHITE STRIPE GREEN 3 19 13 14 2 8 17 15 12 11 1 18 16 4 5 CONNECTOR FRONT VIEW BELDEN 9458...

Page 29: ...DM 13 14 15 16 17 18 19 12 11 10 9 8 4 5 6 7 1 2 3 BLK TAN PINK BLUE HOME P N 19781 NOT USED UDM LINE RED BLACK BLACK IC1 RED GREY METER STEP AUX LDM WHITE GREEN WHITE RED BLACK 5 VDC BLACK NOT USED 9...

Page 30: ...T NEUTRAL 250VAC 3A MAX RESISTIVE 30VDC 3A MAX RESISTIVE HCAM SCAM C N O N C SW1 C N O N C SW2 UDM 13 14 15 16 17 18 19 12 11 10 9 8 4 5 6 7 1 2 3 LDM LDCAM C N O N C SW4 BLK TAN PINK BLUE HOME P N 19...

Page 31: ...EUTRAL 250VAC 3A MAX RESISTIVE 30VDC 3A MAX RESISTIVE BLACK P N 19781 9 6 3 FLOW METER 5 VDC DC GROUND 7 8 4 1 5 2 OPTIONAL SHIELD TB2 ORANGE OPTIONAL OPTIONAL SENSOR INPUT METER INPUT GREEN RED LOCKO...

Page 32: ...50VAC 3A MAX RESISTIVE 30VDC 3A MAX RESISTIVE P N 19781 9 6 3 FLOW METER 5 VDC DC GROUND 7 8 4 1 5 2 OPTIONAL SHIELD TB2 ORANGE OPTIONAL OPTIONAL SENSOR INPUT METER INPUT GREEN RED LOCKOUT INPUT SENSO...

Page 33: ...valve address number Program each unit with unique valve address number in Master Programming Detected Error Program Mismatch Master program parameters do not match between two or more controls Confi...

Page 34: ...34 Fleck 3200 NXT...

Page 35: ...Fleck 3200 NXT 35...

Page 36: ...RPURIFICATION PENTAIR COM CUSTOMER CARE 800 279 9404 tech support pentair com For a detailed list of where Pentair trademarks are registered please visit waterpurification pentair com brands Pentair t...

Reviews: