VALVE ADDRESS:
#2
Options:
Valve Address #1 (First Control Valve)
Valve Address #2 (Second Control Valve)
(Default)
Valve Address #3 (Third Control Valve)
Valve Address #4 (Fourth Control Valve)
SYSTEM TYPE: 4
SINGLE UNIT
Options:
System 4 (single unit)
System 5 (2-4 units) Parallel Interlock
System 6 (2-4 units) Parallel Series Regeneration
System 7 (2 units) Alternating
System 9 (2-4 units) Alternating
System 14 (2-4 units) Demand Recall
Example:
System Type 4, Single Unit
Example:
Valve Address #2 (Second Control Valve)
(Default)
Example:
U.S. Gallons
(Default)
SELECT LANGUAGE:
ENGLISH
Options:
English
Espanol
Portugues
Deutsch
Francais
Example:
English
VALVE TYPE:
2750
Options: 2750 (Default)
2815
2850
2900
3150
3900
Stager - Notch Cam
Example:
2750
(Default)
REGEN TYPE:
TIME CLK DELAYED
Options:
Time Clock Delayed (System 4 Only)
(Default)
Meter Immediate (All System Types)
Meter Delayed Fixed Reserve (Systems 4 & 6 Only)
Example:
Time Clock Delayed
(Default)
REGENERANT FLOW:
DOWNFLOW
Options:
Downflow
(Default)
Up Flow
UF Fill First
Example:
Downflow
(Default)
REMOTE SIGNAL
START: 00:06:00
Options:
Off
(Default)
00:00:00 (Hours:Minutes:Seconds)
Range:
1 second to 99 minutes (1 hour, 39 minutes)
NOTE: This display will not be viewed in System 4
Example:
00:06:00
(Hours:Minutes:Seconds)
NOTE: This screen will not display for System Type 4.
SYSTEM SIZE:
2 VALVES
Options:
2 Valves in the System
(Default)
3 Valves in the System
4 Valves in the System
Example:
2 Valves in the System
(Default)
Range:
2 to 4 Valves in the System
NOTE: This screen will not display for System Type 4.
DISPLAY FORMAT:
US-GALLONS
Options:
U.S. - Gallons
(Default)
Eu Metric - Liters (Metric)
NOTE: In European Units - Liters (Metric) mode, the display will be in
24-hour time.
NOTE: In U.S. - Gallons mode, the display will be in 12-hour time.
UNIT CAPACITY:
00000000 GRAINS
Options:
Grains (in U.S. Format)
(Default)
Grams (in Metric Format)
Example:
Grains
(Default)
NOTE: Use the Shift button to move to the left.
Range:
1 to 9,900,000 Grain Capacity in U.S. Format
1 to 198,000 grams CaCO3 Capacity in Metric Format
Example:
00%
(Default)
CAPACITY SAFETY
FACTOR: 00%
Range:
0 to 50%
NOTE: Use the Shift button to move to the left.
FEED WATER
HARDNESS: 15 GPG
Range:
1 to 199 Grains/Gallon (U.S. Format)
20 to 1,999 miligrams CaCO3/L (Metric Format)
Example:
15 GPG (U.S. Format)
(Default)
NOTE: Use the Shift button to move to the left.
NOTE: This screen will only display on the lead unit for System Types 6 & 7.
For all other System Types, it will display for all units.
TRIP POINT 1:
000 gpm
NOTE: Display will not appear unless timer is programmed as valve position
#1. Use the Shift button to change each decimal position.
REGENERATION DAY
OVERRIDE:OFF
Example:
Off
(Default)
On
(Default for time clock)
REGENERATION DAY
OVERRIDE:01 DAYS
Options:
Off
(Default for meter)
or On
Example:
1 Day
Range:
1 to 99 Days
REGENERATION
TIME: 02:00AM
Example:
2:00 A.M.
(Default)
Options:
A.M. (U.S. Format)
HR (Metric Format)
NOTE: Regeneration time will not appear unless Regeneration Day Override
is on.
CYCLE 1 00:00:00
BACK WASH
Example:
Cycle 1 in Back Wash Mode
Options:
Regeneration Cycle Step #1
Regeneration Cycle Step #2
Regeneration Cycle Step #3
Regeneration Cycle Step #4
Regeneration Cycle Step #5
NOTE: Please refer to the “Regenerant Flow Default Cycle Steps & Times”
in the Master Programming Mode section of the manual.
NOTE: If Stager is chosen for Valve Type, the Regeneration Cycle Step
description will not display.
AUXILIARY RELAY:
DISABLED
Example:
Auxiliary Relay is Disabled
Options:
Enabled
Disabled
(Default)
AUX RELAY OUTPUT
START 1 00:00:00
Example:
Auxiliary Relay Output in Start 1 at
0 hours, 0 minutes, & 0 seconds
Range:
00:00:00 to 18:00:00
NOTE: Only displayed if Auxiliary Relay is enabled in previous screen.
Auxiliary Relay will only display if Chemical Pump is OFF for System
Types 6 & 7.
AUX RELAY OUTPUT
END 1 00:00:00
Example:
Auxiliary Relay Output in End 1 at
0 hours, 0 minutes, & 0 seconds
Range:
00:00:00 to 18:00:00
CHEMICAL PUMP:
DISABLED
Example:
Chemical Pump is Disabled
Options:
Enabled
Disabled
(Default)
NOTE: This screen will only display on the lead unit for System Types 6 & 7.
For all other System Types, it will display for all units.
CPO AUX RELAY
VOLUME: 000 g
Example:
Energize Chemical Pump Relay Every 50 Gallons
Energize Chemical Pump Relay Every 200 L
Range:
1 to 999 gallons in U.S. Format
1 to 9999 L in Metric Format
NOTE: Only displayed on units that physically have a meter (Lead always has
a meter). Only shown if Auxiliary Relay is disabled on System Types 6 & 7.
CPO AUX RELAY
TIME: 00:00:00
Example:
Each Time the Chemical Pump Relay is on, Run
for 30 Seconds (00:00:30)
Range:
00:00:00 to 02:00:00
FLOW METER:
1.0 PADDLE
Example:
1.0 Paddle Flow Meter
Options:
1.0 Paddle (Fleck)
1.0 Turbine (Fleck)
1.5 Paddle (Fleck)
1.5 Turbine (Fleck)
2.0 Paddle (Fleck)
3.0 Paddle (Fleck)
Generic (Non-Fleck)
NOTES: Default flow meter type is based on the valve type. This screen will
only display on the lead unit for System Types 6 & 7. All other system types
it will display for all units.
MAXIMUM FLOW
RATE: 0000 gpm
Example:
Maximum Flow Rate of 0 gpm
Range:
20 - 2000 gpm (U.S. Format)
20 - 2000 L (Metric Format)
NOTE: Only displayed if “Generic” is chosen for the flow meter.
Range:
1 - 255 Gallons (U.S. Format)
1 - 255L (Metric Format)
Pulses: 1 - 255
Options:
Gallons (U.S. Format)
Liters (Metric Format)
ADD 01 GALLONS
EVERY 001 PULSES
Example:
Add 1 Gallon for Each Pulse in U.S. Format
NOTE: Only displayed if “Generic” is chosen for the flow meter.
PROGRAMMING UNIT
PLEASE WAIT...
Example:
Master Programming Mode is Exiting
NOTE: Display will not appear unless timer is programmed as valve position
#1. Use the Shift button to move one space to the left.
TRIP DELAY 1:
30 SECONDS
NOTE: Display will not appear unless timer is programmed as valve position
#1. System size must be 3 or 4 to appear. Use the Shift button to move one
space to the left.
TRIP DELAY 2:
30 SECONDS
NOTE: Display will not appear unless timer is programmed as valve position
#1. System size must be 3 or 4 to appear. Use the Shift button to move one
space to the left.
TRIP POINT 2:
gpm
NOTE: Display will not appear unless timer is programmed as valve position
#1. System size must be 4 to appear. Use the Shift button to move one
space to the left.
TRIP POINT 3:
gpm
NOTE: Display will not appear unless timer is programmed as valve position
#1. System size must be 4 to appear. Use the Shift button to move one
space to the left.
TRIP DELAY 3:
30 SECONDS
Examples:
Default will need to be changed before next step [000] =
(Default)
Brings 2nd valve In Service after 125 gpm
[125]
Brings 2nd valve In Service after 400 lpm
[400]
Range:
1 to 997 gpm (U.S. Format)
0.01 to 3997 lpm (Metric Format)
Examples:
Brings 3rd valve In Service after 250 gpm [250]
Brings 3rd valve In Service after 900 lpm [900]
Range:
Trip Point 1 + 1 to 998 gpm (U.S. Format)
Trip Point 1 + 1 to 3998 lpm (Metric Format)
Examples:
Brings 4th valve In Service after 350 gpm [350]
Brings 4th valve In Service after 1300 lpm [1300]
Range:
Trip Point 2 + 1 to 999 gpm (U.S. Format)
Trip Point 2 + 1 to 3999 lpm (Metric Format)
Regeneration Cycle Steps
This step programs the Regeneration Cycle step times 1
through 5. Please Refer to the chart below for regenerant flow
default cycle steps and times.
Regenerant
Flow
Cycle 1
Time
Cycle 2
Time
Downflow
Backwash
10
Minutes
Brine &
Slow Rinse
1 Hour
UF Brine Draw
Brine &
Slow Rinse
1 Hour
Backwash
10
Minutes
UF Fill First
Brine Tank
Fill
12
Minutes
Brine
Making
1 Hour
Regenerant
Flow
Cycle 3
Time
Cycle 4
Time
Downflow
Rapid Rinse
10
Minutes
Brine Tank
Fill
12
Minutes
UF Brine Draw
Rapid Rinse
10
Minutes
Brine Tank
Fill
12
Minutes
UF Fill First
Brine &
Slow Rinse
1 Hour
Backwash
10
Minutes
Regenerant
Flow
Cycle 5
Time
Downflow
Pause
N/A
UF Brine Draw
Pause
N/A
UF Fill First
Rapid Rinse
10
Minutes
MASTER PROGRAMMING MODE
FLOW CHART
continued
VALVE ADDRESS:
#2
Options:
Valve Address #1 (First Control Valve)
Valve Address #2 (Second Control Valve)
(Default)
Valve Address #3 (Third Control Valve)
Valve Address #4 (Fourth Control Valve)
SYSTEM TYPE: 4
SINGLE UNIT
Options:
System 4 (single unit)
System 5 (2-4 units) Parallel Interlock
System 6 (2-4 units) Parallel Series Regeneration
System 7 (2 units) Alternating
System 9 (2-4 units) Alternating
System 14 (2-4 units) Demand Recall
Example:
System Type 4, Single Unit
Example:
Valve Address #2 (Second Control Valve)
(Default)
Example:
U.S. Gallons
(Default)
SELECT LANGUAGE:
ENGLISH
Options:
English
Espanol
Portugues
Deutsch
Francais
Example:
English
VALVE TYPE:
2750
Options: 2750 (Default)
2815
2850
2900
3150
3900
Stager - Notch Cam
Example:
2750
(Default)
REGEN TYPE:
TIME CLK DELAYED
Options:
Time Clock Delayed (System 4 Only)
(Default)
Meter Immediate (All System Types)
Meter Delayed Fixed Reserve (Systems 4 & 6 Only)
Example:
Time Clock Delayed
(Default)
REGENERANT FLOW:
DOWNFLOW
Options:
Downflow
(Default)
Up Flow
UF Fill First
Example:
Downflow
(Default)
REMOTE SIGNAL
START: 00:06:00
Options:
Off
(Default)
00:00:00 (Hours:Minutes:Seconds)
Range:
1 second to 99 minutes (1 hour, 39 minutes)
NOTE: This display will not be viewed in System 4
Example:
00:06:00
(Hours:Minutes:Seconds)
NOTE: This screen will not display for System Type 4.
SYSTEM SIZE:
2 VALVES
Options:
2 Valves in the System
(Default)
3 Valves in the System
4 Valves in the System
Example:
2 Valves in the System
(Default)
Range:
2 to 4 Valves in the System
NOTE: This screen will not display for System Type 4.
DISPLAY FORMAT:
US-GALLONS
Options:
U.S. - Gallons
(Default)
Eu Metric - Liters (Metric)
NOTE: In European Units - Liters (Metric) mode, the display will be in
24-hour time.
NOTE: In U.S. - Gallons mode, the display will be in 12-hour time.
UNIT CAPACITY:
00000000 GRAINS
Options:
Grains (in U.S. Format)
(Default)
Grams (in Metric Format)
Example:
Grains
(Default)
NOTE: Use the Shift button to move to the left.
Range:
1 to 9,900,000 Grain Capacity in U.S. Format
1 to 198,000 grams CaCO3 Capacity in Metric Format
Example:
00%
(Default)
CAPACITY SAFETY
FACTOR: 00%
Range:
0 to 50%
NOTE: Use the Shift button to move to the left.
FEED WATER
HARDNESS: 15 GPG
Range:
1 to 199 Grains/Gallon (U.S. Format)
20 to 1,999 miligrams CaCO3/L (Metric Format)
Example:
15 GPG (U.S. Format)
(Default)
NOTE: Use the Shift button to move to the left.
NOTE: This screen will only display on the lead unit for System Types 6 & 7.
For all other System Types, it will display for all units.
TRIP POINT 1:
000 gpm
NOTE: Display will not appear unless timer is programmed as valve position
#1. Use the Shift button to change each decimal position.
REGENERATION DAY
OVERRIDE:OFF
Example:
Off
(Default)
On
(Default for time clock)
REGENERATION DAY
OVERRIDE:01 DAYS
Options:
Off
(Default for meter)
or On
Example:
1 Day
Range:
1 to 99 Days
REGENERATION
TIME: 02:00AM
Example:
2:00 A.M.
(Default)
Options:
A.M. (U.S. Format)
HR (Metric Format)
NOTE: Regeneration time will not appear unless Regeneration Day Override
is on.
CYCLE 1 00:00:00
BACK WASH
Example:
Cycle 1 in Back Wash Mode
Options:
Regeneration Cycle Step #1
Regeneration Cycle Step #2
Regeneration Cycle Step #3
Regeneration Cycle Step #4
Regeneration Cycle Step #5
NOTE: Please refer to the “Regenerant Flow Default Cycle Steps & Times”
in the Master Programming Mode section of the manual.
NOTE: If Stager is chosen for Valve Type, the Regeneration Cycle Step
description will not display.
AUXILIARY RELAY:
DISABLED
Example:
Auxiliary Relay is Disabled
Options:
Enabled
Disabled
(Default)
AUX RELAY OUTPUT
START 1 00:00:00
Example:
Auxiliary Relay Output in Start 1 at
0 hours, 0 minutes, & 0 seconds
Range:
00:00:00 to 18:00:00
NOTE: Only displayed if Auxiliary Relay is enabled in previous screen.
Auxiliary Relay will only display if Chemical Pump is OFF for System
Types 6 & 7.
AUX RELAY OUTPUT
END 1 00:00:00
Example:
Auxiliary Relay Output in End 1 at
0 hours, 0 minutes, & 0 seconds
Range:
00:00:00 to 18:00:00
CHEMICAL PUMP:
DISABLED
Example:
Chemical Pump is Disabled
Options:
Enabled
Disabled
(Default)
NOTE: This screen will only display on the lead unit for System Types 6 & 7.
For all other System Types, it will display for all units.
CPO AUX RELAY
VOLUME: 000 g
Example:
Energize Chemical Pump Relay Every 50 Gallons
Energize Chemical Pump Relay Every 200 L
Range:
1 to 999 gallons in U.S. Format
1 to 9999 L in Metric Format
NOTE: Only displayed on units that physically have a meter (Lead always has
a meter). Only shown if Auxiliary Relay is disabled on System Types 6 & 7.
CPO AUX RELAY
TIME: 00:00:00
Example:
Each Time the Chemical Pump Relay is on, Run
for 30 Seconds (00:00:30)
Range:
00:00:00 to 02:00:00
FLOW METER:
1.0 PADDLE
Example:
1.0 Paddle Flow Meter
Options:
1.0 Paddle (Fleck)
1.0 Turbine (Fleck)
1.5 Paddle (Fleck)
1.5 Turbine (Fleck)
2.0 Paddle (Fleck)
3.0 Paddle (Fleck)
Generic (Non-Fleck)
NOTES: Default flow meter type is based on the valve type. This screen will
only display on the lead unit for System Types 6 & 7. All other system types
it will display for all units.
MAXIMUM FLOW
RATE: 0000 gpm
Example:
Maximum Flow Rate of 0 gpm
Range:
20 - 2000 gpm (U.S. Format)
20 - 2000 L (Metric Format)
NOTE: Only displayed if “Generic” is chosen for the flow meter.
Range:
1 - 255 Gallons (U.S. Format)
1 - 255L (Metric Format)
Pulses: 1 - 255
Options:
Gallons (U.S. Format)
Liters (Metric Format)
ADD 01 GALLONS
EVERY 001 PULSES
Example:
Add 1 Gallon for Each Pulse in U.S. Format
NOTE: Only displayed if “Generic” is chosen for the flow meter.
PROGRAMMING UNIT
PLEASE WAIT...
Example:
Master Programming Mode is Exiting
NOTE: Display will not appear unless timer is programmed as valve position
#1. Use the Shift button to move one space to the left.
TRIP DELAY 1:
30 SECONDS
NOTE: Display will not appear unless timer is programmed as valve position
#1. System size must be 3 or 4 to appear. Use the Shift button to move one
space to the left.
TRIP DELAY 2:
30 SECONDS
NOTE: Display will not appear unless timer is programmed as valve position
#1. System size must be 3 or 4 to appear. Use the Shift button to move one
space to the left.
TRIP POINT 2:
gpm
NOTE: Display will not appear unless timer is programmed as valve position
#1. System size must be 4 to appear. Use the Shift button to move one
space to the left.
TRIP POINT 3:
gpm
NOTE: Display will not appear unless timer is programmed as valve position
#1. System size must be 4 to appear. Use the Shift button to move one
space to the left.
TRIP DELAY 3:
30 SECONDS
Examples:
Default will need to be changed before next step [000] =
(Default)
Brings 2nd valve In Service after 125 gpm
[125]
Brings 2nd valve In Service after 400 lpm
[400]
Range:
1 to 997 gpm (U.S. Format)
0.01 to 3997 lpm (Metric Format)
Examples:
Brings 3rd valve In Service after 250 gpm [250]
Brings 3rd valve In Service after 900 lpm [900]
Range:
Trip Point 1 + 1 to 998 gpm (U.S. Format)
Trip Point 1 + 1 to 3998 lpm (Metric Format)
Examples:
Brings 4th valve In Service after 350 gpm [350]
Brings 4th valve In Service after 1300 lpm [1300]
Range:
Trip Point 2 + 1 to 999 gpm (U.S. Format)
Trip Point 2 + 1 to 3999 lpm (Metric Format)
10 •
Fleck
3200 NXT