Page 22
Diagnostic Programming Guide
When the Diagnostics Mode is entered, all available displays are viewed as needed. Depending on current option
settings, some displays cannot be viewed.
Overview Diagnostic Mode
The current diagnostic will be displayed until Extra Cycle key is pressed. There is no time limit on each display.
The timer will display local information, not system information. In the event of regeneration occurring while
displaying diagnostics, the regeneration step and time remaining will be displayed. When regeneration has been
completed, the display will return to diagnostic display.
Entering and Exiting Diagnostic Mode
Push and Release the “D” button to enter. Pressing the Extra Cycle button will move to the next diagnostic to be
displayed. Push the Extra Cycle button once per display until all are viewed. The Diagnostic Mode is exited and
normal operation resumes. Pressing the Diagnostic button, while in the Diagnostic Mode, will cause the unit to
leave the Diagnostic Mode and return to the normal time of day display.
.
1. Flow Rate (Display Code r)
Flow Rate for this particular Timer will be calculated and displayed. Flow rates will be calculated over the
time between pulses up to 20 seconds. Times between pulses longer than 20 seconds will be ignored. If
the display is flashing, the flow rate has exceeded the range and will not calculate. The display updates
once per second.
.
Display example: r100
Range = 0.0 – 99.9 gpm, 100 – 500gpm
Range = 0.0 – 99.9 m3/h, 100 – 113 m3/h
— Depress the Extra Cycle button.
2. Peak Flow Rate (Display Code P)
The Peak Flow Rate since the last regeneration will be captured. Reset to zero by holding up and down
keys for 5 seconds during the Peak Flow Rate display.
Display example: P100
Range = 0.0 – 99.9 gpm, 100 – 500gpm
Range = 0.0 – 99.9 m3/h, 100 – 113 m3/h
— Depress the Extra Cycle button.
Summary of Contents for Fleck 3200NT
Page 1: ...3200NT Service Manual IMPORTANT Fill in Pertinent Information on Page 3 for Future Reference...
Page 25: ...Page 25 Notes...
Page 26: ...Page 26 Power Head Assembly 2750 2850 2900 Upper Drive and 2900 Lower Drive...
Page 28: ...Page 28 Power Head Assembly 3150 3900 Upper Drive and 3900 Lower Drive...
Page 36: ...Page 36 2750 2850 Timer Wiring Diagram...
Page 37: ...Page 37 3150 Timer Wiring Diagram...
Page 38: ...Page 38 2900 Timer Wiring Diagram...
Page 39: ...Page 39 3900 Timer Wiring Diagram...
Page 40: ...Page 40 3200NT Remote Timer Wiring Diagram 42073_REVA...
Page 41: ...Page 41 2750 2850 3200NT Remote Wiring Diagram 42074_REVA...
Page 42: ...Page 42 3150 3200NT Remote Wiring Diagram 42076_REVA...
Page 43: ...Page 43 2900 3200NT Remote Wiring Diagram 42075_REVA...
Page 44: ...Page 44 3900 3200NT Remote Wiring Diagram 42077_REVA...
Page 49: ...Page 49 Notes...
Page 50: ...Page 50 Notes...
Page 51: ...Page 51 Notes...
Page 52: ...P N 41093 Rev E 9 06...