Risk of injury from high pressure in the system
•Before loosening any lines and valves turn o
ff
the pressure and vent the valves
DANGER
!
Always wear the appropriate PPE for the situa on. Use correctly sized tools for opera ons that require tools
Risk of injury from overhea ng of the control head.
Before accessing the inside of the F783E Ex
‐
ia control head, isolate any control power which may be hazardous to the
health of the operator.
Ensure the control head is safe to work on – secure the system against uninten onal ac va on
Avoid leaving live loose wires which can contact ground or each other and ini ate protec ve devices.
When commissioning and tes ng the control head, before manually opera ng the actuator ensure it is safe to do so.
Ensure opera ng the valve won’t compromise personal or product safety. Keep hands clear of moving parts at all mes.
WARNING
!
The control head can be installed in any installa on posi on. Ensure there is su
ffi
cient height above the control head to
remove the cap and adjust the switches.
The device should be installed such that layers of dust thicker than 5 mm cannot form; meaning that such should
be ensured through correspondingly regular cleaning.
Risk of injury from improper assembly!
Do not improperly stress the control head.
Do not apply any leverage e
ff
ect on the head and do not climb on it.
For the installa on of the F783E Ex
‐
ia control head to a linear
‐
type actuator, you will require an actuator
‐
speci
fi
c target. Be
sure to order the correct target for that actuator.
For installa on of the F783E Ex
‐
ia control head on a rotary
‐
type actuator, the target will always be the same. Depending on
the type and brand of actuator an adaptor kit may be required.
When moun ng the F783E Ex
‐
ia control head on a
PENTAIR
brand F257 or F272S actuator no special moun ng adaptor is
required.
8.2.1. Moun ng the base
NOTE!
Maximum supply cable length is to be 30m. Control top must be installed in the same building as the control cabinet.
Installa on environment and wiring are in
fl
uen al on the module’s EMC: Thus the installer must secure EMC of the
whole device.
According to Norm EN 61326
‐
1: 2006 (chart 2) DC supply connec ons to the module are treated as input/output
signal lines. For cable lengths greater than 30 m and outdoor applica ons addi onal measures must be implemented
in order to comply with CE
For installa on in Ex. situa on: refer to special condi ons in Sec on 5 of this manual. Use only Ex. cer
fi
ed product
Summary of Contents for F783E
Page 1: ...F783E Ex ia Pg 1 00 ISN 203_Rev B 29 01 2021 Opera ng Manual ...
Page 5: ...F783E Ex ia Pg 5 00 ISN 203_Rev B 29 01 2021 This page le blank ...
Page 13: ...F783E Ex ia Pg 13 00 ISN 203_Rev B 29 01 2021 This page le blank ...
Page 15: ...F783E Ex ia Pg 15 00 ISN 203_Rev B 29 01 2021 Fig 1 Structure of the control top ...