Pentair Digitrace E507S-LS Installation Instructions Download Page 1

1 / 2

E507S-LS

LINE-SENSING THERMOSTAT FOR HAZARDOUS LOCATIONS INSTALLATION INSTRUCTIONS

THERMAL MANAGEMENT SOLUTIONS

EN-DigiTraceE507SLS-IM-H56913      01/13

DESCRIPTION

The E507S-LS thermostat is designed for controlling heat-tracing 
systems in hazardous locations. The E507S-LS can be used to 
control heat-tracing circuits in a pipe-sensing mode (see Figure 1 
on back page), to indicate low-temperature (see Figure 2) or high-
temperature (see Figure 3) alarm conditions, or to control the coil 
on a contactor (see Figure 4). 

APPROVALS

SPECIFICATIONS

Enclosure

NEMA 4, 7, 9, lacquer-coated cast-aluminum 
housing, stainless-steel hardware

Entries

One 3/4 in. NPT conduit hub

Set point range

25°F to 325°F (–4°C to 163°C)

Sensor exposure 
limits

–40°F to 420°F (–40°C to 215°C)

Housing exposure 
limits

–40°F to 140°F (–40°C to 60°C)

Switch

SPDT

Electrical rating

22 A at 125/250/480 Vac

Accuracy

±6°F (±3.3°C)

Deadband

2°F to 12°F (1.1°C to 6.7°C) above actuation 
temperature

Set point  
repeatability

±3°F (±1.7°C) 

Sensor type

Fluid-filled (silicone) bulb and 9 ft (2.7 m) 
capillary

Sensor material

300 series stainless steel

Connection  
terminals

Screw terminals, 10–14 AWG (2–5 mm

2

)

Class I, Div. 1 and 2, Groups B, C, D
Class II, Div. 1 and 2, Groups E, F, G
Class III

Hazardous locations

This component is an electrical device. It must be installed 
correctly to ensure proper operation and to prevent shock or 
fire. Read these important warnings and carefully follow all the 
installation instructions.

Component approvals and performance are based on the use of 
specified parts only. Do not use substitute parts or vinyl electrical 
tape to make connections.

WARNING:

4.0 in. (102 mm)

4.5 in. (114 mm)

Ø.28 in. (7 mm) 
mounting hole 
(4X)

4.5 in.

(114 mm)

6.6 in.

(168 mm)

4.0 in.

(102 mm)

8.0 in.

(202 mm)

Adjusting knob

Removable knob cover

4.0 in. (102 mm)

1.2 in. (30 mm)

2.0 in.

(50 mm)

3⁄4 in. NPT conduit entry

0.3 in. (9 mm)

Terminal

block

Reviews: