MODELS CBV-S5 AND CBV-NPT5

4

ITEM 

1040 SERIES

DATED 

MARCH 2015

Connect pressure measuring device to the CBV metering ports 

as follows:
  • Remove protective cap from metering ports (¼" NPT 

connection).

  • Insert the meter probe into the metering ports. The hose with 

red fitting, up stream; the hose with blue fitting downstream. 

Refer to Fig. 6.

When inserting probe, do not bend, as this will cause 

permanent damage to the probe, adversely affecting the 

pressure measurement. Do not use any lubrication on 

the probes when inserting them. If necessary, simply wet       

the probes with clean water.

The probe should not be left inserted into the fitting for 

prolonged periods of time, overnight, etc., as leakage of 

the P.M.P. may occur when the probe is removed.

The locking nut on the probe is designed to hold it in the 

P.M.P. when taking readings. As sealing is accomplished 

internally on the probe stem, it is only necessary to 

tighten the locking nut FINGER-TIGHT. Overtightening 

may cause damage to the P.M.P. or locking nut threads.

Before taking a measurement reading, set the valve to its fully 

open position (5.0) or at a preset position. Read the pressure 

drop across the venturi with a digital meter. Determine flow rate 

by use of Venturi C

v

 Performance Curves (Fig. 8).

The handle of the CBV is not designed to be removable. Do not 

try to take it off the valve, or it may become damaged. If for any 

reason the handle is damaged, replace the entire handle/stem 

assembly with the appropriate replacement part indicated below.

571155-225 for size 1/2"– 2"

570155-105 for size 2-1/2"– 6"

570155-015 for size 8"– 12"

MEMORY SETTING:
After valve has been properly adjusted and without moving 

the handwheel, the locking memory stop should be set. The 

memory stop will allow the valve to be fully closed for isolation 

and then reopened to the preset flow position.

Insert a 2.5 mm (or 3/32") Allen key through the hole provided 

in the valve’s handle cap. (Fig. 7)

Turn the setscrew in a clockwise direction until it stops. 

It is not necessary to tighten. The memory has now been 

set.  This  establishes  the  maximum  opening  position  for  this           

particular valve.

The valve may now be closed tightly, as needed, for isolating 

the piping during system maintenance.

To return the valve to its preset “balanced” position, simply 

open the valve by turning the handwheel counterclockwise 

until the handle stops turning (the valve stem inside the 

handle has hit the memory set screw). DO NOT APPLY 

EXCESSIVE FORCE WHEN REOPENING THE VALVE 

– OPEN ONLY UNTIL THE VALVE STOPS TURNING 

UNDER “HAND-TIGHT” CONDITIONS. DO NOT USE 

A WRENCH TO OPEN, CLOSE, OR TIGHTEN VALVES.

High Pressure Port (red) 

Low Pressure Port (blue)

Fig. 6

CAUTION

Summary of Contents for AURORA CBV-S5

Page 1: ...rovide this manual to the owner of the equip ment or to the responsible party who maintains the system MODELS CBV S5 AND CBV NPT5 FIVE TURN VENTURI CIRCUIT BALANCING VALVES INSTALLATION AND OPERATION MANUAL Part A 03 353 2015 Pentair Ltd 03 18 15 ...

Page 2: ...ent in the fluid must be removed The operation of the valve is dependent on the fluid characteristics such as specific gravity and viscosity which vary with the fluid temperature For installations using fluids other than 100 water flow rates must be corrected for the changes created by the fluid medium To ensure accuracy of measurement Circuit Balancing Valves CBV s should be located at least five...

Page 3: ...erms of the number of full turns Fig 3 Micrometer Scale This scale is marked 0 9 and is located on the upper half of the handle assembly Each mark represents 1 10th of a full 360 turn of opening when lined up with an arrow head symbol located above the handwheel turns display window Fig 3 The valve is considered zeroed when fully closed hand tight The 0 on the micrometer scale should be within one...

Page 4: ...formance Curves Fig 8 The handle of the CBV is not designed to be removable Do not try to take it off the valve or it may become damaged If for any reason the handle is damaged replace the entire handle stem assembly with the appropriate replacement part indicated below 571155 225 for size 1 2 2 570155 105 for size 2 1 2 6 570155 015 for size 8 12 MEMORY SETTING After valve has been properly adjus...

Page 5: ...has cracked fractured Remove and reinstall a new valve being careful not to overtighten Valve does not shut off completely when closed hand tight The seat O ring has been deformed due to overheating during soldering Remove the handle stem assembly and replace with the appropriate replacement part indicated in the table on page 3 CBV S5 CBV NPT5 Fig 9 These curves show the pressure drop across the ...

Page 6: ...THIS PAGE INTENTIONALLY LEFT BLANK ...

Page 7: ...THIS PAGE INTENTIONALLY LEFT BLANK ...

Page 8: ...his warranty shall be at its option to repair or replace any equipment or its component parts which has a defect covered by this warranty or to refund the purchase price of such equipment or part Under the terms of this warranty Seller shall not be liable for a consequential collateral special or liquidated losses or damages b equipment conditions caused by normal wear and tear abnormal conditions...