Specifications 10
Product Specifications
model Family
SK60
Typical application:
Sewage, dewatering
capacities:
up to 130 GPm (8.2 LPS)
Heads:
up to 28 ft (8.5 m)
Electrical:
115V, 1ø, 12.0 FLa, 60Hz; 208V, 1ø, 6.9 FLa, 60Hz; 230V, 1ø, 6.0 FLa, 60Hz; 208V, 3ø, 2.9 FLa, 60Hz; 230V,
3ø, 2.5 FLa, 60Hz; 460V, 3ø, 1.3 FLa, 60Hz; 575V, 3ø, 1.04 FLa, 60Hz
motor:
(single phase) - 6/10 HP split phase with thermal overload protection, 1750 rPm;
(three phase) - 6/10 HP polyphase, 1750 rPm
Intermittent Liquid Temperature:
140°F (60°c)
minimum recommended Sump diameter:
Simplex = 24" (609.6 mm); duplex = 36" (914.4 mm)
automatic operation:
diaphragm pressure switch (single phase only, manual available)
materials of construction:
class 30 cast iron
Impeller:
class 30 cast iron two-vane nonclog
discharge Size:
2” NPT (50.8 mm); 3" NPT (76.2 mm) optional
Solids Handling:
2” (50.8 mm)
Power cord:
1ø, 115V - 10', STW-a (20' optional); other 1ø and all 3ø - 20', STW-a
Performance Curve
TO
TA
L DYNAMIC HEAD-FEET
CAPACITY-U.S. G.P.M.
0
24
48
72
96
120
144
0
8
16
24
32
6/10 HP