REGULATION INSTRUCTIONS
41
5. REGULATING THE APPLIANCE
5.1 Parameters table
PARAMETER
N°
TYPE OF OPERATION
PARAMETER
VALUE
FUNC TION
1
Selects the type of boiler
00
01
02
03
PCC 34-H
PCI 18/8-H or PCI 34/20-H
PCH 34B-H, PCH 18B-H or PCH 50B-H
D.H.W. Temperature 95-160 °F (PCC 34-H only)
2
Selects the type of gas
00
01
Natural gas
Propane
3
Sets the central heating
Temperature
Displayed in °C only
00
01
Standard (86-176°F)
Reduced (77-104°F )
4
1
Selects pump mode during heating
phase
00
01
Standard ( 3
’ pump overrun) Permanent (pump runs
continuously)
5
Water hammer cycle prevention
00
01
Off
On
6
Central heating timer
00-90 (default = 36)
Electronically timed heating differential.
Expressed in steps of
5 sec (factory set at 36 x 5 = 180 sec)
7
Central heating pump overrun timer
00-90 (default = 36)
The overrun timer can be modified.
Expressed in steps of 5 sec (factory set at 36 x 5 = 180 sec)
8
D.H.W pump overrun timer
00-90 (default = 18)
The overrun timer can be modified.
Expressed in steps of 5 sec (factory set at 18 x 5 = 90 sec)
9
Not Applicable
-
Not applicable for premix boilers
10
Not Applicable
-
Not applicable for premix boilers
11
Not Applicable
-
Not applicable for premix boilers
12
Not Applicable
-
Not applicable for premix boilers
13
D.H.W. priority function (2 min
delay on D.H.W. function)
00
01
Off
On (Recommended)
14
Selects the type of burner
00
01
02
03
Atmospheric (not premix)
18 kW
34 kW
50 kW
15
Zone management activation
Not Applicable
00
01
Off
On
16
Telephone control
Not Applicable
00
01
Off
On
17
Minimum fan speed setting
55 Hz (Natural Gas
52 Hz (Propane)
To set the minimum frequency value
(Hz) for the fan operation
18
Maximum fan speed setting
164 Hz (Natural Gas)
155 Hz (Propane)
To set the maximum frequency value
(Hz) for the fan operation
19
Minimum fan speed setting
(Central Heating)
55 Hz (Natural Gas
52 Hz (Propane)
To set the minimum frequency value
(Hz) for the fan operation in heating mode.
20
Maximum fan speed setting
(Central Heating)
164 Hz (Natural Gas)
155 Hz (Propane)
To set the maximum frequency value
(Hz) for the fan operation in heating mode
21
Ignition sequence setting
110 Hz (Natural Gas)
130 Hz (Propane)
To set the fan frequency value (Hz) at
the ignition
22
Fan frequency value display
00
01
Off
On (for 10 min. time)
NOTES:
1 - Activate only for
“heating only” boilers;
2- W hen the parameter value 01, 02 and/or 03 is set, parameters from no.17 to 22 are automatically activated and boiler settings are carried-out in
through these parameters (in Hz). Once the parameter value has been set according to the boiler output, the P.C.B will automatically adjust the
maximum and minimum values.
Summary of Contents for PCI 20-H
Page 8: ...GENERAL INFORMATION 5 ...
Page 9: ...GENERALInformation 6 ING ...
Page 10: ...GENERALInformation 7 ...
Page 11: ...GENERALInformation 8 ...
Page 33: ...INSTALLATION INSTRUCTIONS 29 Venting Pictures Illustrations ...
Page 34: ...INSTALLATION INSTRUCTIONS 30 Included With Each Combination Boiler Is A PAHVK Horizontal Kit ...
Page 38: ...INSTALLATION INSTRUCTIONS 34 ...
Page 73: ...69 6 13 Sequence of Operations ...
Page 74: ......