VFD68 Variable Frequency Drives (230 or 460 VAC)
29
P.161
Frequency Setting/Key Lock Operation Select:
10 = change speed on dial, then press SET to change VFD
speed; 11 = change speed on dial to instantly change VFD
speed
10, 11
11
P.162
Auto Restart After Instantaneous Power Failure:
1 = Enable without frequency search, 0 = Enable with frequency
search
0, 1
1
P.167
Output Over Current Detection: 0 = no motor stoppage when
over current occurs, 1= motor stops when over current occurs
0, 1
0
P.241
Analog Input Display Unit Switchover:
0 = display in 0.1%
increments, 1 = display in 0.01V/0.01mA increments
0, 1
1
P.250
Stop Selection:
9999 = decelerate to stop,
1 = coast to stop
9999, 1
9999
P.255
Life Alarm Status Display:
Displays remaining-life status of the
control circuit capacitor, main circuit capacitor, cooling fan, and
inrush current limit circuit
(0: new; 15: end of life)
Read Only
P.256
Inrush Current Limit Circuit Life Display:
Displays the
deterioration level of inrush current limit circuit. (100[%]: new,
0[%]: end of life)
Read Only
P.257
Control Circuit Capacitor Life Display:
Displays deterioration
level of control circuit capacitor (100[%]: new, 0[%]: end of life).
Read Only
P.266
Set to 1 to enable voltage high signal select using both analog
inputs (and set switch to
V
). Set to 0 to enable analog input 2
(Terminal 4) as a current input (and set AI2 mode switch to
I
).
0, 1
1
P.267
Analog Input 2 (AI2) Mode:
Defines the input signal type to be
connected to terminal 4. (Select 0 for 4–20 mA and position
AI2 mode switch to I, or select 1 for 0–5 V or
2 for 0–10 V and position AI2 mode switch to V.)
0, 1, 2
1
P.295
Magnitude of Frequency Change:
0.1 = Frequency changes
by 0.1 increments by rotation the selection dial.
0.1
0.1
P.296
Password Lock Level:
Defines the read/write access level
when password lock is enabled. (9999: No password lock; 1–6
or 101–106 = Set read/write restriction level when a password is
implemented). Refer to the
VFD68 Variable Frequency Drive Technical Bulletin
(Part No. 24-7664-3051).
1–6, 101–106, 9999
9999
P.297
Password Lock and Error Count:
If P.296 is 1–6 or 101–106,
then password can be implemented from 1000 to 9998. After
password is implemented ,this parameter counts up to 5
password unlock failures. If P.296 is 9999, then P.297 is 9999,
no password lock, read only.
1000–9998,
(0–5, 9999)
9999
P.299
Rotation Direction Detection:
0 = disabled; 1 = enabled
Example: If P. 78=1 and the controlled motor starts, but the VFD
detects reverse rotation, the VFD decellerates the motor to a
stop and then runs the motor in a forward direction.
0,1
1
P.549
Communication Bus Protocol Selection:
0= drive protocol, 1
= ModBus RTU
0,1
1
P.882
Regenerative Avoidance Operation Selection:
1 = Regenerative avoidance is always valid. If the VFD drive
detects overvoltage, the VFD drive increases the frequency to
avoid an overvoltage fault.
1
1
Table 19: Basic and Advanced Parameter Descriptions for VFD68Bxx and VFD68Cxx Drives
(Part 3 of 4)
Parameter
Indication
on Monitor
Description
Range
VFD68xxx-2
Defaults