V46 and V47 Repair Parts and Service Instructions

2

Adjustments

To raise the valve opening point on direct-acting valves, turn the adjusting screw counterclockwise. To lower the 
valve opening point, turn the range adjusting screw clockwise. See Figure 2. The closing point of the valve is not 
adjustable. Pressure-actuated valves close approximately 3 to 7 psi (21 to 48 kPa) below the opening point, and 
temperature-actuated valves close approximately 3 to 5°F (1.7 to 2.8°C) below the opening point.

If the compressor operates in high ambient temperatures, head pressures may remain high enough during off 
cycles to prevent the valve from closing completely. In such instances, the opening point of the valve should be 
raised just enough to cause the valve to close during compressor standby periods. The opening of the valve raises 
the throttling point.

The all-range pressure-actuated valve settings can be adjusted for both low pressure refrigerant ranges of R-134a 
and higher pressure refrigerant ranges of 
R-22 (R-502).

Manual Flushing

To clear any sediment that may accumulate, valves may be manually flushed by inserting screwdrivers under both 
sides of the main spring and lifting upwards to flush the valve. Manual flushing does not affect valve adjustments.

Inspection and Service

To inspect and replace internal parts, follow the procedures in this section.

After long periods of operation, the valve seat and rubber disc may become worn, pitted, or wiredrawn, preventing 
the valve from completely closing off, allowing leakage through the valve in the closed position, when the pressure 
and temperature is below the setpoint.

Shut off the liquid supply and relieve pressure in the line before servicing the valve. Contents of liquid lines could 
be under pressure and the release of liquid under pressure may cause severe personal injury.

Figure 1:  Manual Flushing

Summary of Contents for V46 Series

Page 1: ...ulb Avoid mounting the valve where the bulb might be partly above operating liquid level or surrounded by an air pocket Mount the valve vertically with the bellows facing downward IMPORTANT The V46 and V47 valves are intended to control liquid flow under normal operating conditions Where failure or malfunction of the V46 and V47 valves could lead to personal injury or property damage to the contro...

Page 2: ...he throttling point The all range pressure actuated valve settings can be adjusted for both low pressure refrigerant ranges of R 134a and higher pressure refrigerant ranges of R 22 R 502 Manual Flushing To clear any sediment that may accumulate valves may be manually flushed by inserting screwdrivers under both sides of the main spring and lifting upwards to flush the valve Manual flushing does no...

Page 3: ...e IMPORTANT To decrease the pressure in the sensing element on the V47 valves cool the bulb by submerging it in ice water Do not remove the bulb from the ice water until the element is ready to be reinstalled Otherwise the pressure increases in the sensing element resulting in a valve that is hard to reassemble Figure 2 Valve Components Assembly Figure 3 V46 and V47 2 in and 2 1 2 in ...

Page 4: ... Replace the guide plate gasket and bellows sealing ring Figure 4 10 Assemble the sensing element to the valve body with the bellows push rod new diaphragms guide plate gasket and bellows sealing ring in place 11 Assemble the new disc disc retainer and extension sleeve a Apply a small amount of grease to the grooves on the bottom of the new extension sleeve and the top of the new disc retainer Pla...

Page 5: ...ctions 5 16 Before leaving the installation run the system through at least one complete operating cycle to be sure the valve is operating correctly Figure 4 Guide Plate Gasket and Bellows Sealing Ring Identification Gasket for pressure Push Rod ...

Page 6: ...adjusting screw spring and valve spring guide Figure 6 c Clean off any excess grease on the valve spring guide d Place the new ISO loss washer over the guide plate e Replace the valve spring guide spring range adjusting screw and spring housing IMPORTANT To decrease the pressure in the sensing element on the V47 valve cool the bulb by submerging it in ice water Do not remove the bulb from the ice ...

Page 7: ...ssemble the new valve stem disc disc cup and disc stud and place into the valve body Figure 5 10 On 1 in and larger pressure valves and all temperature valves replace the guide plate gasket and bellows sealing ring Figure 8 11 If servicing a V47 or V46 valve other than low flow place new diaphragms on the sensing element end of the valve stem assembly Use two diaphragms on 3 8 in 1 2 in and 3 4 in...

Page 8: ... bellows push rod Attach the sensing element to the valve body See Figure 7 13 Place two new diaphragms on the spring housing side of the valve body Screw into place with the seat guide post Figure 7 14 Place the spring housing assembly over the seat guide post and secure in place with the four housing screws 15 Adjust the valve to desired opening point Then manually flush the valve See the Manual...

Page 9: ... All Types Seat Guide Post 1 1 1 1 1 1 1 1 1 1 1 Disc Stud 1 1 1 1 1 1 1 1 1 1 1 Disc Cup Retainer 1 1 1 1 1 1 1 1 1 1 1 Valve Disc 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Valve Seat 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Valve Stem 1 1 1 1 1 1 1 1 1 1 1 Rubber Diaphragm1 4 4 4 4 5 5 5 5 4 4 4 5 5 5 5 5 Guide Plate Gasket 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Bellows Sealing Ring 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Valve Assembly...

Page 10: ...JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 53202 USA JOHNSON CONTROLS C O CONTROLS PRODUCT MANAGEMENT NO 22 BLOCK D NEW DISTRICT WUXI JIANGSU PROVINCE 214142 CHINA 10 Extension Sleeve 1 1 1 Seat Wrench 1 1 1 1 1 1 1 1 1 1 1 Sensing Element Contact Application Engineering at 414 524 5535 Stem Washer 1 ISO loss Washer2 1 1 1 O ring Seals 2 2 1 3 8 1 2 and 3 4 in valves require two diaphragms on...

Reviews: