P47 Installation Instructions 

Note:

 If the boiler manufacturer 

recommends a specific mounting 
location for the pressure control, 
follow the manufacturer’s 
mounting recommendations. 

Wiring 

!

 WARNING: 

Risk of 

electrical shock. 

Disconnect the power 
supply before mounting and 
wiring to prevent possible 
electrical shock. On multiple 
circuit units, more than one 
circuit may have to be 
disconnected. 

 

!

 CAUTION: 

Risk of 

equipment damage. 

Disconnect the power 
supply before mounting and 
wiring to prevent possible 
equipment damage. On 
multiple circuit units, more 
than one circuit may have to 
be disconnected. 

All wiring must conform to the 
local, national, and regional 
regulations. Do not install the 
control on electrical loads in 
excess of the rating that is listed 
on the inside of the control 
cover. Use copper conductors 
only. 

IMPORTANT: Use the terminal 

screws furnished in the 
switch (8-32 x  
1/4 in.). Longer terminal 
screws can interfere with 
the switch mechanism and 
damage the switch. 

Refer to Figures 8 and 9 for the 
SPDT wiring hookups on EA and 
FA types. The red terminal is 
common, the red to yellow circuit 
closes on pressure increase, and 
the red to blue circuit opens on 
pressure increase. 

See Figures 4-7 for wiring 
hookups on other P47 models. 

Adjustment 

Figure 3 illustrates open-high 
models. On open low models, 
adjusting screw “A” raises or 
lowers the cut-in point (this also 
raises or lowers the cutout point 
by a like amount). Set the cut-in 
point first using adjusting screw 
“A.” Cutout adjusting screw 
“B”changes the cutout point only. 

Checkout Procedure 

Before leaving the installation, 
observe at least three complete 
operating cycles to be sure that 
all components are functioning 
correctly.  

Test the limit switch function to 
be sure the system shuts down 
when the limit contacts open. 

Repairs and Replacement 

Field repairs must not be made 
except for replacement of the 
knob and cover. For a 
replacement knob or cover, 
contact the nearest Johnson 
Controls distributor. 

 