PB_P216_11 2016

5

Normal operation example using a 230 V supply 

Output voltage vs input pressure

16 Bar

220 V

46 V

1

2

3

4

ON

20%

100%

-

+

0 V

20 Bar

                                                              Figure 2

0 – 10 Vdc slave operation example using 230 V supply 

Output vs input voltage

6,0 Vdc

220 V

230 V*0,2 = 46 V

1

2

3

4

ON

20%

100%

-

+

0 V

10,0 Vdc

+

-

V P1 C

                                                              Figure 3

Note

Set switches 1–3 as shown to select a 

14-24 Bar setpoint range with a 4 Bar 

proportional band.  

Adjust the setpoint potentiometer to 

20 Bar (which is 60% rotation from 

the "-" or CCW end of the setpoint 

potentiometer).  

Adjust the minimum speed potentiometer 

completely CCW (to set the minimum 

speed to 20% of 230 V or 46 V).  

Setting switch 4 to ON causes the 

motor to always run at minimum speed 

or greater.

Note 1

If min speed is set to 40%, then output 

turns off at 230 V*0,4 = 92 VAC when 

input voltage drops to 6,0 V* 0,4 = 2,4 Vdc

DIP switch block

Min speed 20%

Setpoint 60% from “-”

Output to motor 

(VAC)

Min. speed

Input (Pressure - Bar)

Setpoint

Proportional  

band

DIP switch block

Min speed 

20%

Setpoint  

at midscale

Proportional band

Setpoint

Output to motor 

(VAC)

6,0 V*0,2 = 1,2 Vdc

20% min speed

Switch 4 = OFF

Input (Voltage)

See "Note 1"

DC voltage 

connection

0 - 10 Vdc

Control signal

Summary of Contents for P216

Page 1: ...for dual pressure input varies the fan speed by directly sensing the pressure changes of two separate refrigerant circuits The setpoint of each pressure transducer can be separately adjusted The cont...

Page 2: ...ion The P216 can be used for single or dual pressure input In the case of dual input the controller selects the input with the greater cooling demand to control the fan speed There are four pressure r...

Page 3: ...indicate that power is applied Two 3 position screw terminal blocks will be used to connect the 50 bar transducers A 3 position screw terminal block will be used to select HP or reverse modes Contact...

Page 4: ...e CCW CW Vdc Proportional band BAR OFF OFF ON Slave 2 10 Vdc See Note 1 OFF ON ON Slave 1 5 Vdc Note 1 The proportional band in slave mode extends from 0 Vdc to the setpoint voltage TB1 M1 L1 L2 N L2...

Page 5: ...CCW end of the setpoint potentiometer Adjust the minimum speed potentiometer completely CCW to set the minimum speed to 20 of 230 V or 46 V Setting switch 4 to ON causes the motor to always run at mi...

Page 6: ...nection Terminal Red V Black C White P P499 electronic pressure transducers P216 performance using high efficiency motors Current rating based on DI percent Maximum Amps DI 12 00 0 11 43 5 10 91 10 10...

Page 7: ...n Controls International plc declares that these products are in compliance with the essential requirements and other relevant provisions of the EMC Directive and Low Voltage Directive The performance...

Reviews: