PB_P216_11 2016
5
Normal operation example using a 230 V supply
Output voltage vs input pressure
16 Bar
220 V
46 V
1
2
3
4
ON
20%
100%
-
+
0 V
20 Bar
Figure 2
0 – 10 Vdc slave operation example using 230 V supply
Output vs input voltage
6,0 Vdc
220 V
230 V*0,2 = 46 V
1
2
3
4
ON
20%
100%
-
+
0 V
10,0 Vdc
+
-
V P1 C
Figure 3
Note
Set switches 1–3 as shown to select a
14-24 Bar setpoint range with a 4 Bar
proportional band.
Adjust the setpoint potentiometer to
20 Bar (which is 60% rotation from
the "-" or CCW end of the setpoint
potentiometer).
Adjust the minimum speed potentiometer
completely CCW (to set the minimum
speed to 20% of 230 V or 46 V).
Setting switch 4 to ON causes the
motor to always run at minimum speed
or greater.
Note 1
If min speed is set to 40%, then output
turns off at 230 V*0,4 = 92 VAC when
input voltage drops to 6,0 V* 0,4 = 2,4 Vdc
DIP switch block
Min speed 20%
Setpoint 60% from “-”
Output to motor
(VAC)
Min. speed
Input (Pressure - Bar)
Setpoint
Proportional
band
DIP switch block
Min speed
20%
Setpoint
at midscale
Proportional band
Setpoint
Output to motor
(VAC)
6,0 V*0,2 = 1,2 Vdc
20% min speed
Switch 4 = OFF
Input (Voltage)
See "Note 1"
DC voltage
connection
0 - 10 Vdc
Control signal