A421 Series Standard Electronic Temperature Controls Installation Instructions

7

Setup and Adjustments

Front Panel

The front panel of the A421 Series Electronic 
Temperature Control has a simple LCD and a 
three-button user interface (Figure 5). 

Liquid Crystal Display

The A421 Series Control has a backlit LCD screen 
(Figure 5). The LCD brightness is adjustable. During 
normal operation, the LCD

 

displays the Main screen, 

which provides following information: 

the temperature sensed at the A99 sensor

the selected temperature units (°F or °C)

the mode of operation (Flame = Heating mode, 
Snowflake = Cooling mode)

Binary Input status (BIN) when a (user-supplied) 
binary input (switch) is connected and closed to 
enable the temperature setback feature.

During setup and adjustment, the LCD displays the 
parameter code screens and the parameter value 
screens. See th

A421 Control Parameter Setup 

Menus

 on page 9 for more information.

Three-Button Touchpad

The touchpad has three buttons for setup and 
adjustment of the A421 control (Figure 5). Se

Menu 

Navigation Guidelines

 on page 9 for more information 

on using the three-button touchpad.

Relay Status LED

The green LED on the front panel illuminates when the 
SPDT output relay is energized and the

 LC

 and

 LNO

 

contacts are closed. See Figure 5.

Parameter Codes and Modes of Operation

Relay Off Temperature 

(

OFF

)

:

 Select the temperature 

at which the output relay de-energizes, the LC to LNO 
relay contacts open (cutout), and the green LED goes 
off. The range of usable temperature values is 
-40 to 212 °F (-40 to 100 °C) in 1° increments.

Relay On Temperature 

(

On

)

:

 Select the temperature 

at which the output relay energizes, the

 

LC to LNO 

relay contacts close (cut in), and the green LED lights. 
The range of usable temperature values is 
-40 to 212 °F (-40 to 100 °C) in 1° increments.

Heating or Cooling Mode of Operation: 

When you 

select your desired 

On

 and 

OFF

 values, the control 

automatically determines the mode of operation and 
displays the proper mode icon on the Main screen. 

Note:

The A421 Series controls do 

not 

have jumpers 

for setting up the heating or cooling mode.

The heating or cooling mode is determined by the 

On

 

and 

OFF

 value relationship as follows: 

OFF > On

 = Heating mode = Flame icon

OFF < On

 = Cooling mode = Snowflake icon

Anti-Short Cycle Delay

 

(ASd):

 Select the minimum 

time that the output relay remains off (de-energized) 
before the next on-cycle can start. The ASd interval 
overrides any load demand (On) and does not allow 
the output relay to go on until the selected ASd interval 
has elapsed. See Figure 6

Figure 5: A421 Control Front Panel with LCD

and Three-Button User Interface

IMPORTANT:

 During normal operation, just the 

On

 value or just the 

OFF

 value on the A421 control 

changes the differential between 

On

 and 

OFF

, and 

can potentially change the mode of operation from 
heating to cooling or cooling to heating. To maintain 
a constant differential between 

On

 and 

OFF

, you 

must adjust both the 

On

 value and 

OFF

 value by an 

equal number of degrees; or set up the control in the 
Restricted Adjustment Mode. See 

Restricting User 

Adjustment

Figure 6: Anti-Short Cycle Delay

Summary of Contents for A421ABC-02C

Page 1: ...A421 control could lead to personal injury or property damage to the controlled equipment or other property additional precautions must be designed into the control system Incorporate and maintain ot...

Page 2: ...is connected to a standard A421 control the range of usable values is restricted by the control to 40 to 212 F 40 to 100 C See Wiring Technical Specifications and refer to the A99B Series Temperature...

Page 3: ...rness between the enclosure base and cover more than 180 Wiring WARNING Risk of Electric Shock Disconnect or isolate all power supplies before making electrical connections More than one disconnection...

Page 4: ...l does not provide any internal power to the TB2 terminals or relay contacts The A421 control simply energizes and de energizes the relay to open and close the contacts based on the On OFF temperature...

Page 5: ...d Wire Sizes TB1 24 VAC Models LN Low Voltage 24 VAC Control Power Common Connect the 24 VAC supply power to operate the control 28 AWG to 12 AWG 0 08 mm2 to 4 0 mm2 24V Low Voltage 24 VAC Control Pow...

Page 6: ...12 AWG 0 08 mm2 to 4 0 mm2 LNO Line Voltage SPDT Relay Normally Open Contact Connects controlled equipment to the Line Voltage Normally Open LNO contact on the SPDT relay When LC is closed to LNO the...

Page 7: ...and the green LED goes off The range of usable temperature values is 40 to 212 F 40 to 100 C in 1 increments Relay On Temperature On Select the temperature at which the output relay energizes the LC t...

Page 8: ...ode the effective On and OFF setback values On tBs and OFF tBs can be greater than the selected HtS value or less than the selected LtS value Temperature Setback tSb Select a temperature value for set...

Page 9: ...gh all of the available parameter values for the associated parameter code With the preferred parameter value displayed press MENU to save the value and go to the next parameter code screen Note If yo...

Page 10: ...Modes of Operation and Table 4 for more information regarding parameter codes usable parameter values and default values 1 With the Main screen displayed press MENU The LCD displays OFF which is the f...

Page 11: ...On value automatically shifts equal to the OFF value adjustment The OFF value can only be adjusted to values that maintain the entire control band within the restricted temperature adjustment range de...

Page 12: ...OFF value and return to the OFF code screen 5 Press and simultaneously to return to the Main screen Troubleshooting Fault Codes A421 Series controls display fault codes on the LCD as described in Tabl...

Page 13: ...ad from the output relay terminals b Ensure that the Parameter Adjustments jumper is installed so that access to adjust parameters is unrestricted c Reconnect the sensor leads and supply power to the...

Page 14: ...l Type 4X NEMA IP66 watertight enclosure for surface mount applications Rated for 120 240 VAC Includes an A99BB 200C temperature sensor with 6 6 ft 2 0 m cable A421GBF 02C Low Voltage Type 1 Electroni...

Page 15: ...erating temperature range 40 to 248 F 40 to 120 C A99CB 200C PTC Temperature Sensor Extended probe 6 in 15 2 cm with 6 6 ft 2 0 m PVC cable Ambient operating temperature range 40 to 212 F 40 to 100 C...

Page 16: ...lass B limits Europe CE Mark Johnson Controls Inc declares that this product is in compliance with the essential requirements and other relevant provisions of the EMC Directive Low Voltage Directive A...

Page 17: ...rd A421 control model the range of displayed temperature values is 40 to 212 F or 40 to 100 C The performance specifications are nominal and conform to acceptable industry standards For application at...

Reviews: