Penn A421 Series Installation Manual Download Page 10

Control adjustment is now restricted to changing only

the OFF value, which shifts the On and OFF control band

within the restricted adjustment range defined by HtS and

LtS (Figure 9).

Note: 

To completely restrict and lockout all user

adjustment on the control, set the HtS value equal to

the On or OFF value and the LtS value equal to OFF or

On value. Then the (On to OFF) control band is equal

to the restricted adjustment range (LtS to HtS) and

the OFF value cannot be adjusted in the restricted

mode.

Adjusting the control in Restricted mode

In this task you adjust the OFF value and shift the On and

OFF control band within the restricted adjustment range,

when the control is in the restricted adjustment mode.

1.

In the Main screen, press 

MENU

 to go to the

restricted adjustment mode menu and display the

OFF parameter code screen (Figure 11).

2.

To go to the OFF value screen, press 

MENU

.

3.

In the OFF value screen, press 

Down

 or 

Up

 to change

the OFF value within the restricted adjustment range.

4.

To save the selected OFF value and return to the OFF

code screen, press 

MENU

.

5.

To return to the Main screen, press 

Down

 and 

Up

simultaneously.

Figure 11: Adjusting temperature in the Restricted menu

Troubleshooting

A421 Series Controls display fault codes on the LCD as

described in Table 4.

Table 4: Fault Codes Defined

Fault code Definition

System status Solution

SF

 flashing

alternately

with 

OP

Open

temperature

sensor or

sensor wiring

Output

functions

according to

the selected SF

mode

See 

Troubleshooting

procedure

. Cycle

power to reset the

control.

SF

 flashing

alternately

with 

SH

Shorted

temperature

sensor or

sensor wiring

Output

functions

according to

the selected SF

mode

See 

Troubleshooting

procedure

. Cycle

power to reset the

control.

EE

Program

failure

Output is off

To reset the control,

press 

MENU

. If

problems persist,

replace the control.

Troubleshooting procedure

1.

Check for proper voltage to the A421 Control.

a. To remove the cover, loosen the two captive cover

screws.

b. Use an AC voltmeter to check the voltage between

the COM and 120V or 240V terminals on line-

voltage models. See Figure 4.

Note: 

The voltage must be between:

- 102 VAC and 132 VAC for 120 VAC

applications

- 177 VAC and 264 VAC for 208/240 VAC

applications

c. If the voltage reading is not within the required

range, check the power source and input power

wires for problems.

2.

Check for proper sensor operation.

a. Disconnect all power sources to control.

b. Using an accurate thermometer, take a

temperature reading at the sensor location.

c. Disconnect the sensor from the control.

d. Using an ohmmeter, measure the resistance

across the two sensor leads while the sensor is at

the temperature taken in Step 2b.

e. Consult Figure 12 to verify that the measured

temperature and resistance conform to

established temperature and resistance values.

f. If the measured values conform to the values in

Figure 12, proceed to Step 3.

g. If the sensor’s measured resistance value is

substantially different from the expected value

for that temperature, check the sensor wiring. If

sensor wiring is correct, replace the sensor.

A421 Series Electronic Temperature Controls with Cycle Timer Installation Guide

10

Summary of Contents for A421 Series

Page 1: ...ou de protection en cas de d faillance ou de dysfonctionnement du A421 Control The A421 Series Electronic Temperature Controls are single stage electronic temperature controls with a single pole doubl...

Page 2: ...range of usable values from 40 F to 212 F or 40 C to 100 C See Wiring Technical specifications and refer to the A99B Series Temperature Sensors Product Technical Bulletin LIT 125186 for more informat...

Page 3: ...l ratings Exceeding the electrical ratings can result in permanent damage to the control and void any warranty Important Run all low voltage wiring and cables separate from all high voltage wiring It...

Page 4: ...re for 120 VAC supply power applications Connect the L1 supply power lead for all 208 240 VAC supply power applications 120V Line voltage 120 VAC control power hot Connect the 120 VAC supply power hot...

Page 5: ...On temperature On Select the temperature at which the output relay energizes the LC to LNO relay contacts close cut in and the green LED lights The range of usable temperature values is 40 F to 212 F...

Page 6: ...brightest backlight setting and the system default The selected backlight brightness level is applied to the LCD during normal operation When you enter the programming menus to set up the control or p...

Page 7: ...ave a new value the control reverts to the last saved value After 30 seconds of inactivity while in any screen the control reverts to the Main screen Basic menu Use the Basic menu to quickly edit the...

Page 8: ...tween the On and OFF values the following behavior is enforced The fan relay is On for at least the Minimum Relay On Time Ont during a Cycle Period cP See Figure 8 The fan relay goes Off when the sens...

Page 9: ...Restricted mode prevents casual users from over adjusting the control in your application or from inadvertently changing the mode of operation from cooling to heating or heating to cooling by over adj...

Page 10: ...e See Troubleshooting procedure Cycle power to reset the control SF flashing alternately with SH Shorted temperature sensor or sensor wiring Output functions according to the selected SF mode See Trou...

Page 11: ...with Cycle Timer Type 1 NEMA IP20 standard enclosure for DIN rail and surface mount applications Rated for 120 240 VAC Includes timer for On Off duty cycle control Includes an A99BB 200C temperature s...

Page 12: ...Specification Description Power consumption 1 8 VA maximum Supply power 110 120 or 208 230 240 VAC 50 60 Hz Table 8 A421 Series Electronic Temperature Controls Technical Specifications Specification...

Page 13: ...00 RH condensing Shipping weight 1 4 oz 41 g for 6 1 2 ft 2 m sensor Accessories See Table 7 1 When any A99 Series Temperature Sensor is connected to a standard A421 Control model the range of display...

Page 14: ...SON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 53202 USA For more contact information refer to www johnsoncontrols com locations 2019 Johnson Controls Al...

Reviews: