MODBUS Register List
Each sensor has 4 MODBUS register block. Register for the sensor are sequential. First
register is for current gas reading, second register has sensor status and diagnostics bit
map, third is register holding data for the battery voltage. Fourth register is used
internally and should not be read by the user’s PLC . However, when read may give a
non-zero value.
Table below lists the MODBUS register number for each sensor data value.
Table I. Sensor MODBUS Register Map
Sensor Number or
Address
MODBUS Registers for
Gas Reading Status Battery Voltage
1
400031
400032
400033
2
400035
400036
400037
3
400039
400040
400041
4
400043
400044
400045
5
400047
400048
400049
6
400051
400052
400053
7
400055
400056
400057
8
400059
400060
400061
9
400063
400064
400065
10
400067
400068
400069
11
400071
400072
400073
12
400075
400076
400077
…….
……..
n
(n * 4) + 400027
(n * 4) + 400028
(n * 4) + 400029