Expert nano LINE

 

200NANO4CK1*   

Termoregolatore elettronico / Electronic thermostat 

Manuale d’uso e manutenzione / Use and maintenance manual 

PEGO S.r.l. 

Via Piacentina, 6/b - 45030 -  ROVIGO 

Tel : +39(0)425 762906 - Fax: +39(0)425 762905 

www.pego.it   -  e-mail: [email protected] 

 

200NANO4CK1#_02-13_ITA_ENG  #  Rev.02-13  #  29/04/2013

 

 

 

TECHNICAL DATA

 

GENERAL INFORMATION 

PEGO  S.r.l.  does  not  accept  responsibility  for  any  loss  of  data  or 
information,  costs  of  goods  or  substitute  services,  damages  to 
objects,  persons  or  animals,  lost  sales  or  profits,  interruption  of 
activities, any direct, indirect, accidental, property, insured, punitive, 
special or consequential damage caused in any way, be it contractual, 
extra-contractual  or  due  to  negligence  or  other  responsibility 
resulting from the use of the product or its installation. The guarantee 
automatically becomes invalid in the case of poor functioning due to 
tampering,  impact  or  inadequate  installation.  It  is  mandatory  to 
observe all instructions in this manual and the operating conditions of 
the  device.  PEGO  S.r.l.  does  not  accept  responsibility  for  any 
inaccuracies which may be present in this manual in the case that 
these are due to printing or transcription errors and reserves the right  
to make modifications to its products which it deems necessary or 
appropriate, 

without 

prejudicing 

the 

products 

essential 

characteristics. 
 

ELECTRICAL PRESCRIPTIONS 

Avoid using multipolar cables with conductors connected to inductive  
and  power  loads  and  signal conductors such  as  probes and  digital 
inputs. Avoid installing in the same channels power cables and signal 
cables  (probes,  digital  inputs  or  RS485  connections).  Reduce  to  a 
minimum  the  length  of  the  connecting  cables,  avoiding  that  the 
cabling takes on a spiral form which may have inductive effects on 
the  electronic  system.  All  conductors  used  in  the  cabling  must  be 
appropriately  sized  in  order  to  support  the  load  which  they  must 
provide. If it is necessary to extend the probes, use conductors with 
appropriate cross-sections and not less than 1 mm². The extension or 
reduction  of  the  probes  may  alter  the  calibration  which  was 
performed in the factory.  Therefore, verify and calibrate by means of 
an external thermometer. 
 
 

HACCP ALARM MANAGEMENT 

 
With ambient probe temperature ≤ A1 , after the Ald time, the EL 
low temperature alarm is activated.  
 
With ambient probe temperature ≥ A2 , after the Ald time, the EH 
high temperature alarm is activated.  
 
During a high or low temperature alarm, the display alternates the 
visualisation  of  the  temperature  with  the  EH  or  EL  headings;  the 
alarm  relay  is  activated  (if  set),  the  Buzzer  (silenceable)  and  the 
alarm bell icon (flashing).  
 
When  the  set  alarm  conditions  are  turned  off,  alarm  signals 
automatically  undo  (the  alarm  relay  is  deactivated,  the  buzzer  is 
silenced and the normal visualisation is reactivated). 
 
The alarm bell icon remains on (fix) to indicate that EH or EL alarm 
was triggered and the memorisation of the event (see HACCP menu 
for displaying the latest temperature alarm activated). 
 
To get the alarm, push the arrow button up when the fix bell light is 
on.

 

 
Besides, the starting date of the latest EH or EL event is registred, 
together  with  its  duration and its  maximum  or  minimum reached 
temperature. 
 
A counter of the nr of occurred alarms from the latest alarm reset 
(max 99 alarms can be counted) is also present.

 

 

To display data related to the latest temperature alarm, enter in the 
HACCP menu (push the arrow button up + stand-by for 3 seconds). 
 
Inside the menu, all the data can be scrolled with the up and down 
arrows or they can be reset, by pressing the SET  arrow up 
button for 5 seconds.

 

 
Once the reset occurred, a BIP with the buzzer is provided to 
confirm the occurred cancelation. 
 
To exit the menu, wait 10 seconds without pressing anything or 
press simultaneously the up and down arrows. 
 
HACCP variables are available in read-only mode and are the 
following: 
 

DIAGNOSTICS 

In  the  case  of  faults,  the  “Expert  nano”  control  unit  informs  the 
operator  by  means  of  alarm  codes  shown  on  the  display  and  an 
acoustic  signal  emitted  by  the  buzzer  (if  present).  The  acoustic 
alarm  can  be  stopped  by  pressing  the  UP  key  (the  error  code 
remains)  and  can  be  reactivated  by  pressing  the  SET  key.  In  the 
event of an alarm, one of the following messages is displayed: 

 

ALARM CODE TABLE 

Var 

MEANING 

E0

 

Functional fault of ambient probe. 

E1 

Functional fault of defrosting probe (in this case, any defrosting 
processes will have a duration equal to time d3). 

E2 

EEPROM memory error.  All outputs are deactivated except for 
alarm outputs if present. 

E8 

Man-in-room alarm. 

Ec 

Compressor protection alarm (e.g. thermal protection or max. 
pressure  switch).  All  outputs  are  deactivated  except  for  the 
alarm output if present. 

Ed 

Door open  alarm.  When  the  door  switch  opens  and  the  tdo 
time  has  elapsed,  normal  function  of  the  control  is  reset, 
triggering the door open alarm (Ed). 

EL 

Minimum  temperature  alarm.  The  letters  EL  flash  alternating 
with the temperature (see parameter A1). 

EH 

Maximum temperature alarm. The letters EH flash alternating 
with the temperature (see parameter A2). 

E9 

Room  light  alarm.  The  letters  E9  flash  alternating  with  the 
temperature (see parameter  dO2 and Tdo). 

 

VARIABLE LIST HACCP LEVEL  
(Values in read-only)

 

E## 

Indicates the latest 
activated 
temperature alarm. 
 

EH = high temperature 
alarm  
EL = low temperature 
alarm 
-- = no alarms have been 
activated from the latest 
reset 

### 

Temperature 

peak 

value  reached  during 
the  latest  EH  or  EL 
alarm 

-45…+45°C 
--- = no alarms have been 
activated from the latest 
reset 

y## 

Year  of  the  start  of 
the 

lastest 

temperature alarm 

y 00 – y99 
y -- = no alarms have been 
activated from the latest 
reset 

M## 

Month of the start of 
the lastest 
temperature alarm  

M 01 – M12 
M -- = no alarms have been 
activated from the latest 
reset 

d## 

Day of the start of the 
lastest temperature 
alarm 

d 01 – d31 
d -- = nessun allarme 
intervenuto dall’ultimo 
reset 

h## 

Hour of the start of 
the lastest 
temperature alarm 

h 00 – h24 
h -- = no alarms have been 
activated from the latest 
reset 

m## 

Minutes of the start 
of the lastest 
temperature alarm  

m 00 – m59 
m -- = no alarms have been 
activated from the latest 
reset 

t## 

Duration (hours) of 
the latest 
temperature alarm 

t 00 – t99 
t -- = no alarms have been 
activated from the latest 
reset 

C## 

Contactor of the nr of 
temperature alarm events 
occurred (being 
memorised data of the 
latest  temperature alarm 
event, the contactor is 
boosted to know if 
previously other alarms 
occurred) 
. This contactor resets with 
the memorised alarm reset 
(silenced  SET for 5 
sec.) It is implemented at 
every new temperature 
alarm.) 

C 00 – C99 
C -- = no alarms have been 
activated from the latest reset 

 
 

E   N   G   L   I   S   H

 

Power Supply 

Power voltage 

12V

~

 +10/-15%  50/60Hz  / 12Vdc +10/-15%  class 2 

Absorbed power  

3 VA  Max 

Environment conditions 

Operating temperature 

-5T55°C  - humidity < 90% Rel. Hum. Not condensing 

Storage temperature 

-20T70°C - humidity < 90% Rel. Hum.  Not condensing 

Unsuitable operating 
environments 

Environments with strong vibrations or impacts; aggressive, polluted or corrosive 

atmospheres, exposure to direct solar radiation, explosive atmospheres or flammable gas. 

General characteristics 
Display 

3-Digit with sign, decimal point and 9 LED status indicators 

Resolution 

0.1 °C 

Probe precision (electronic) 

± 0.5 °C 

Reading range 

-45T99 °C 

200NANO4CK12 

Connector for temperature repeater ECHO 

Clamps 

 

Power clamps: extractable, screw for cables with c/section 0.2 to  2.5mm

2

 

Signal clamps: extractable, screw for cables with c/section  0.2 to  1.5mm

2

 

Software class: A  /  Parameters saved on non-volatile memory (EEPROM) 
Input characteristics 
Analogue inputs 

2 Inputs for NTC probes (10K Ώ 1%  at 25°C)   

Digital inputs 

1 Input (clean contact) 

Output characteristics 
Compressor relay (DO1) 

N.O.  16(6)A  / 250V

~

 

Fan relay  (DO2) 

N.O.  8(3)A    /  250V

~

 

Heating elements relay (DO3) 

N.O.  8(3)A   /  250V

~

 

Relay (DO4) 

N.O.  8(3)A   /  250V

~

 

Buzzer 

Present 

Dimensional, insulation and mechanical characteristics 

Dimensions 

93x37x65mm  Depth 59mm  
(Depth 69mm with removable clamps) 

Drill hole template 

71x29mm (+0.2/-0.1mm) 

Front protection rating 

IP65 with front board installation 

Installation 

In front of board by means of rear fastening clips or or two front screws 

Casing 

Plastic PC+ABS UL94 V-0 body, PC transparent front, Key panel PC or PC+ABS 

Insulation type 

Class II 

Conformity with EEC low voltage directives, electromagnetic compatibility and EC mark 
Conforms to following EEC Directives : Directives 2004/108/EEC , 2006/95/EEC, 93/68 EEC 
Conforms to following harmonised standards:  EN60730-1, EN60730-2-9, EN61000-6-1,  EN61000-6-3 

 

Reviews: