Pego Expert nano 200NANO1LT Series Quick Start Manual Download Page 4

 

 

Expert 

nano LINE

 

200NANO1LT**

   

Thermorégulateur électronique / Electronic thermostat 

Manuel d’utilisation et d’entretien / Use and maintenance 
manual 

 

Manuale d’uso e manutenzione / Use and maintenance manual

 

PEGO S.r.l. 

Via Piacentina, 6/b - 45030 -  ROVIGO 

Tel : 0425 762906 - Fax: 0425 762905 

www.pego.it   -  e-mail: [email protected] 

 

200NAN1LT_01-18_FRA  #  Rev.01-18  #  22/02/2018

 

 

Manuale d’uso e manutenzione / Use and maintenance manual

 

 

 

 

 

 

 

 

 

 

LIST OF FIRST LEVEL VARIABLES 

(User level) 

Var 

MEANING 

DEF. 

r0

 

Temperature  differential  in  relation  to  principal 

SET-POINT 

< Range: 0.2 ÷ 10,0°C > 

Expressed in absolute  values and  defines  hysteresis 

(positive if mOd = 0 or 2 or negative if mOd = 1 or 3) 

of temperature in relation to SET POINT. 

2,0 

d0 

Defrosting interval 

< Range: 0 ÷ 24 hours > 

If d0=0 defrosting is excluded. 

d3 

Massima durata sbrinamento. 

< Range: 1 ÷ 240 min >

 

25 

A1 

Minimum temperature alarm

 

< Range: - 45 ÷ (A2-1)°C >

 

Absolute  temperature  referred  to  by  the  ambient 

probe  below  which,  following  the  ALD  delay,  the 

LOW  temperature  alarm  is  triggered,  showing  the 

letters  EL  alternating  with  the  temperature  on  the 

display, as well as the flashing alarm icon. 

-45 

A2 

Maximum temperature alarm 

< Range: (A1+1) ÷ 99°C  >

 

Absolute  temperature  referred  to  by  the  ambient 

probe  above  which,  following  the  ALD  delay,  the 

HIGH  temperature  alarm  is  triggered,  showing  the 

letters  EH  alternating  with  the  temperature  on  the 

display, as well as the flashing alarm icon. When the 

alarm  is  reset  the  alarm  icon  remains  on  without 

flashing to indicate that the event occurred, until the 

UP key is pressed. 

99 

 

 

 

LIST OF SECOND LEVEL VARIABLES 

(Installer level) 

Var 

MEANING 

DEF. 

C1 

Minimum time between each turning off and on of 

the compressor

 

< Range: 0 ÷ 15 min >

 

CE1 

Duration of compressor ON time in the case of faulty 

ambient probe

 (emergency mode).  

< Range: 0 ÷ 240 min / 0=Disabled > 

If CE1=0 the emergency mode in the presence of error 

EO remains disabled, the compressor remains off and 

defrosting  is  prevented  in  order  to  conserve  the 

remaining cold. 

CE2 

Duration of compressor OFF time in the case of faulty 

ambient probe

 (emergency mode).  

< Range: 5 ÷ 240 >

 

mOd 

Thermostat functioning mode 

< Range: 0 ÷ 3 >

 

0 =   NTC - Cold function 

1 =   NTC - Hot function (in this mode, defrosting is 

excluded) 

2 =   PTC - Cold function 

3 =   PTC - Hot function (in this mode, defrosting is 

excluded) 

4 =    NTC - alarm N.O. 

5 =    NTC - alarm N.C. 

6 =    PTC - alarm N.O. 

7 =    PTC - alarm N.C. 

LSE 

Minimum value attributable to set point 

< Range:

 -45 ÷ (HSE-1) °C

 >

 

-45 

HSE 

Maximum value attributable to set point 

< Range:

 +99 ÷ (LSE+1) °C

 >

 

99 

CAL 

Ambient probe value correction 

< Range:

 -10,0 ÷ 10,0 °C

 >

 

0,0 

Ald 

Delay time for signalling and display of minimum 

and maximum temperature alarm 

< Range: 0 ÷ 240 >

 

120 

P1 

Password: protection type 

( active when PA is different from 0) 

< Range: 0 ÷ 3 >

 

0 = Displays only the set point and allows alarm 

stop 

1 = Displays the set point, allows alarm stop, + 

defrost 

2 = Blocks access to levels 1 and 2 during 

programming (all other functions permitted) 

3 = Blocks access to level 2 during programming 

(all other functions permitted) 

PA 

Password 

(see P1 for protection type) 

< Range: 0 ÷ 999 / 0=Disabled >

 

reL  Software release

 

reading 

only

 

 

THERMOSTAT FUNCTION MODES (mOd) 

The variable mOd allows the selection of function mode of the 

thermostat, in particular: 

COLD MODE (mOd=0 or 2) 

The  DO1 output  is  activated  when  the  temperature  measured 

by  the  ambient  probe  reaches  or  exceeds  the  SET  POINT+r0 

value and remains active until the temperature drops below the 

SET  POINT. In  this  mode,  the DO1 output  is  linked  to the cold 

function icon. 

HOT MODE (mOd=1 or 3) 

The  DO1 output  is  activated  when  the  temperature  measured 

by  the  ambient  probe  reaches  or  exceeds  the  SET  POINT-r0 

value  and  remains  active  until  the  temperature  increases  and 

exceeds the SET POINT. In this mode the DO1 output is linked to 

the heat icon and defrosting is DISABLED.

 

ALARM MODE (mOd = 4, 5, 6 or 7) 

The DO1 output is activated when the temperature measured 

by the ambient probe exceeds A2 or drops below A1 for longer 

than  Ald  and  remains  active  until  the  temperature  returns 

within the limits. In this mode the DO1 output is linked to the 

alarm icon. 

 

PASSWORD FUNCTION

 

The  password  function  is  activated  by  entering  a  value  other 

than  0  for  the  PA  parameter.  See  parameter  P1  for  various 

protection  levels.  The  protection  is  activated  automatically  if 

the keyboard remains inactive for about 30 seconds. The figure 

000  appears  on  the  display.  Use  the  up/down  keys  to  change 

the  number  and  the  SET  key  to  confirm.  The  password  entry 

template 000 disappears if the keyboard is not activated within 

30 seconds. 

If you forget the password, use the universal number 100. 

 

EMERGENCY MODE IN THE CASE OF ERROR EO

 

This safety mode guarantees the functioning of the compressor 

even in the case of a faulty ambient probe (error EO). If probe 

errors E0 and CE1 are different to 0, the compressor functions 

in operation pause mode, with compressor ON for the time CE1 

and  OFF  for  the  time  CE2.  If  CE1>0  in  the  case  of  error  E0, 

defrosting  is  performed  in  normal  functioning  mode.  If  CE1=0 

the  emergency  mode  in  the  presence  of  error  E0  remains 

disabled.  The  compressor  remains  off  and  defrosting  is 

prevented to conserve the remaining cold. Eliminate as soon as 

possible  the  cause  of  error  E0  and  reactivate  the  control’s 

normal function for a correct temperature adjustment. 

 

MANUAL DEFROSTING ACTIVATION

 

To  activate  defrosting  simply  press  the  DOWN  key  for  more 

than  3  seconds;  this  activates  off-cycle  defrosting.  End  of 

defrosting is based on the maximum defrosting duration (d3) or 

occurs by forced manual termination (end-of-defrosting key). 

 

MANUALLY FORCED END OF CURRENT DEFROSTING

 

Pressing the DOWN key for 3 seconds during defrosting forces 

the end of the current defrosting. In the case of manual end-of-

defrosting, dripping is also excluded. 

 

AMBIENT  TEMPERATURE  DISPLAY  DURING  AND  AFTER 

DEFROSTING

 

During  defrosting  and  for  a  minute  following  the  end  of 

defrosting,  the  display  continues  to  display  the  last  ambient 

temperature value read before start of defrosting.

   

 

DIAGNOSTICS 

The  display  shows  ‘orH’  for  temperature  out  of  range  greater 

than  +99.9°C,  or  ‘orL’  for  temperature  out  of  range  less  than        

-45.0°C. 

In the case of faults, the “Expert nano” control unit informs the 

operator by means of alarm codes shown on the display. In the 

event of an alarm, one of the following messages is displayed: 

 

ALARM CODE TABLE 

Var 

MEANING 

E0

 

Functional fault of ambient probe. 

E2 

EEPROM memory error.  All outputs are deactivated except for 

alarm outputs if present. 

EL 

Minimum  temperature  alarm.  The  letters  EL  flash  alternating 

with the temperature (see parameter A1). 

EH 

Maximum temperature alarm. The letters EH flash alternating 

with the temperature (see parameter A2). 

 
 

GENERAL INFORMATION 

PEGO  S.r.l.  does  not  accept  responsibility  for  any  loss  of  data  or 

information,  costs  of  goods  or  substitute  services,  damages  to 

objects,  persons  or  animals,  lost  sales  or  profits,  interruption  of 

activities, any direct, indirect, accidental, property, insured, punitive, 

special  or  consequential  damage  caused  in  any  way,  be  it 

contractual,  extra-contractual  or  due  to  negligence  or  other 

responsibility resulting from the use of the product or its installation. 

The  guarantee  automatically  becomes  invalid  in  the  case  of  poor 

functioning due to tampering, impact or inadequate installation. It is 

mandatory  to  observe  all  instructions  in  this  manual  and  the 

operating  conditions  of  the  device.  PEGO  S.r.l.  does  not  accept 

responsibility  for  any  inaccuracies  which  may  be  present  in  this 

manual  in  the  case  that  these  are  due  to  printing  or  transcription 

errors and reserves the right  to make modifications to its products 

which  it  deems  necessary  or  appropriate,  without  prejudicing  the 

products essential characteristics. 

 

ELECTRICAL PRESCRIPTIONS 

Avoid  using  multipolar  cables  with  conductors  connected  to 

inductive  and power loads and signal conductors such as probes and 

digital inputs. Avoid installing in the same channels power cables and 

signal cables (probes, digital inputs or RS485 connections). Reduce to 

a minimum  the length of the connecting cables, avoiding that the 

cabling takes on a spiral form which may have inductive effects on 

the  electronic  system. All  conductors  used  in  the  cabling  must  be 

appropriately  sized  in  order  to  support  the  load  which  they  must 

provide. If it is necessary to extend the probes, use conductors with 

appropriate cross-sections and not less than 1 mm². The extension or 

reduction  of  the  probes  may  alter  the  calibration  which  was 

performed in the factory.  Therefore, verify and calibrate by means of 

an external thermometer. 

 

 

 

 

 

 

 

 

NANO1LT SERIES MODELS 

PEGO CODE 

EXPERT NANO DESCRIPTION 

200NANO1LT01 

Power 230Vac. 

Relay (16A), select hot or cold function. 

Fixed clamps. 

200NANO1LT11 

Power 12Vac. 

Relay (16A), select hot or cold function. 

Fixed clamps. 

200NANO1LT02 

Power 230Vac. 

Relay (16A), select hot or cold function. 

Removable clamps. 

 

 

ELECTRICAL CONNECTIONS MODEL 
 

200NANO1LT01 / 200NANO1LT02 

 

 

 

ELECTRICAL CONNECTIONS MODEL 
 

200NANO1LT11 

 

 

 
 
 

E N G L I S H

 

 