Pego 202BASE Manual Download Page 4

   

Pag.  4 

ECP202 BASE 

– Parameters Abstract 

Rev. 01-21 

d1  

Defrost  type

,  cycle  inversion  (hot  gas)  or 

with heater elements 

0 = heating element 
1 = hot gas 
2 = heater with temperature control 

dPo 

Defrost at Power On 

0 = disabled 
1 = defrost at power-on (if possible) 

dSE 

Smart defrost 

0 = disabled 
1 = enabled 

dSt 

Smart defrost Setpoint (if dSE=1) 

The  counting  of  the  time  between  the  defrost  is 
incremented  only  if  the  compressor  is  ON  and  the 
evaporator temperature is less than dSt.

 

-30 ÷ 30 °C 

1 °C 

dFd 

Display viewing during Defrost 

0 = current temperature 
1 = temperature at the start of the defrost 

2 = “DEF” 

Ad 

Net  address

  for  connection  to  TeleNET 

supervision system or Modbus 

0 ÷ 31 (with SEr=0) 

1 ÷ 247 (with SEr=1) 

SEr 

RS-485 communication protocol  

0 = TeleNET protocol  
1 = Modbus-RTU protocol 

Bdr 

Modbus baudrate 

0 = 300 baud          
1 = 600 baud  
2 = 1200 baud 

3 = 2400 baud 
4 = 4800 baud  
5 = 9600 baud 

6 = 14400 baud 
7 = 19200 baud  
8 = 38400 baud 

Prt 

Modbus parity check 

0 = none    |    1 = even    |    2 = odd 

Ald 

Minimum  and  maximum  temperature 

signalling and alarm display delay 

0 ÷ 240 min 

120 min 

C1 

Minimum  time  between  shutdown  and

 

subsequent 

switching 

on 

of 

the 

compressor

0 ÷ 15 min 

0 min 

CAL 

Cold room sensor value correction 

-10,0 ÷ +10,0 °C 

0,0 °C 

CE1 

Duration  of  compressor  ON  time  in  the 
case  of  faulty  ambient  probe 

(emergency 

mode). If CE1=0 the emergency mode in the 
presence  of  error  E0  remains  disabled,  the 
compressor  remains  off  and  defrosting  is 
prevented in order to conserve the remaining 
cold.

 

0 ÷ 240 min 

 

0 = disabled 

0 min 

CE2 

Duration  of  compressor  OFF  time  in  the 
case  of  faulty  ambient  probe 

(emergency 

mode). 

5 ÷ 240 min 

5 min 

doC 

Compressor safety time for door switch:

 

when the door is opened the evaporator fans 
shut down and the compressor will continue 
working for time 

doC

, after which it will shut 

down.

 

0 ÷ 5 min 

0 min 

tdo 

Compressor  restart  time  after  door 
opening: 

when the door is opened and after 

tdo 

time,  it’s  setted  back  the  normal 

functioning giving door open alarm (Ed) 
If  the  door  switch  is  closed  and  the  light 
stays  on  for  a  longer  time  than  tdo  light  cell 
alarm is signaled (E9). 
With tdo=0 the parameter is disabled. 

0 ÷ 240 min 

 

0 = disabled 

0 min 

Fst 

FAN shutdown TEMPERATURE 

The  fans  will  stop  if  the  temperature  value 
read  by  the 

evaporator 

sensor  is  higher 

than this value. 

-45 ÷ +99 °C 

+99 °C 

Fd 

Fst differential 

1 ÷ +10 °C 

2 °C 

LSE 

Minimum value attributable to setpoint. 

-45 ÷ (HSE-1) °C 

-45 °C 

HSE 

Maximum value attributable to setpoint. 

(LSE+1) ÷ +99°C 

+99 °C 

Summary of Contents for 202BASE

Page 1: ...t In this case we advise you to apply inside the panel the label present in the packaging to have the correct wiring diagram Below is the quick guide to the programming parameters The complete manual...

Page 2: ...Pag 2 ECP202 BASE Parameters Abstract Rev 01 21...

Page 3: ...rm LED flashes displayed temperature flashes and the buzzer sounds to indicate the problem 45 A2 1 C 45 C A2 Maximum temperature alarm It allows user to define a maximum temperature for the room being...

Page 4: ...the compressor 0 15 min 0 min CAL Cold room sensor value correction 10 0 10 0 C 0 0 C CE1 Duration of compressor ON time in the case of faulty ambient probe emergency mode If CE1 0 the emergency mode...

Page 5: ...int flashes 20 0 20 0 C 0 0 C In1 INP 1 input setting 8 Night mode digital input energy saving N O 7 Stop defrosting remotely N O reads rising edge of impulse 6 Start defrosting remotely N O reads ris...

Page 6: ...are deactivated Check that compressor is working properly Check compressor absorption If the problem persists contact the technical assistance service Ed Open door Alarm When the door is opened and af...

Page 7: ...Deze tijd begint na het einde van de druptijd Als er geen druptijd is ingesteld start de ventilatorpauze direct na het einde van de ontdooiing 0 10 min 0 min A1 Minimum temperatuuralarm Maakt het moge...

Page 8: ...met SEr 0 1 247 met SEr 1 0 SEr RS 485 communicatieprotocol 0 TeleNET protocol 1 Modbus RTU protocol 0 Bdr Modbus baudrate 0 300 baud 1 600 baud 2 1200 baud 3 2400 baud 4 4800 baud 5 9600 baud 6 14400...

Page 9: ...ux relais 45 99 C 0 C nSC Correctiefactor voor de SET knop tijdens nachtbedrijf energiebesparend met In1 of In2 8 of 8 Tijdens nachtbedrijf is de controleset Set Control Set nSC In de nachtmodus knipp...

Page 10: ...uit en opnieuw aan E8 Man in koelcel alarm Reset het alarm binnen in de koelcel Ec Compressor beveiliging aangesproken thermische beveiliging of max druk pressostaat alle uitgangen muv het alarm word...

Page 11: ...en Diese Zeit beginnt am Ende des Abtropfens Wenn kein Abtropfen eingestellt ist beginnt die L fterpause direkt nach dem Abtauen 0 10 min 0 min A1 Mindesttemperaturalarm Erm glicht dem Benutzer die Fe...

Page 12: ...TeleNET Protokoll 1 Modbus RTU Protokoll 0 Bdr Modbus Baudrate 0 300 baud 1 600 baud 2 1200 baud 3 2400 baud 4 4800 baud 5 9600 baud 6 14400 baud 7 19200 baud 8 38400 baud 5 Prt Modbus Parit tspr fun...

Page 13: ...tellung f r Hilfsrelais 45 99 C 0 C nSC Korrekturfaktor f r die SET Taste im Nachtbetrieb Energieeinsparung mit In1 oder In2 8 oder 8 W hrend des Nachtbetriebs ist der Steuerungssatz Set Control Set n...

Page 14: ...m in der Zelle Setzen Sie den Alarmeingang im K hlraum zur ck Ec Kompressorschutz ausgel st z B W rmeschutz oder maximaler Druckschalter Alle Ausg nge sind au er f r den Alarm sofern vorhanden deaktiv...

Page 15: ...rme temp rature minimale Permet d tablir une valeur de temp rature minimale pour l espace r frig rer L tat d alarme se d clenche au dessous de la valeur A1 une LED d alarme clignote la temp rature aff...

Page 16: ...1 pair 2 impair 0 Ald Temporisation signalisation et affichage alarme de temp rature minimale ou maximale 0 240 min 120 min C1 Temps minimum entre la coupure et le rallumage du compresseur 0 15 min 0...

Page 17: ...t de consigne compresseurs on consid re Set contr leur Set nSC En mode nuit Point d cimal clignot 20 0 20 0 C 0 0 C In1 R glage d entr e INP 1 8 Entr e num rique du mode Nuit conomie d nergie N O 7 Ar...

Page 18: ...mique ou interrupteur de pression max Toutes les sorties l exception de l alarme sont d sactiv s Contr lez l tat du compresseur Contr lez l absorption du compresseur Si le probl me persiste contactez...

Page 19: ...adores 0 10 min 0 min A1 Alarma de m nima temperatura Permite definir un valor de temperatura m nima para el ambiente a refrigerar Por debajo del valor A1 se se alar el estado de alarma con el led de...

Page 20: ...400 baud 4 4800 baud 5 9600 baud 6 14400 baud 7 19200 baud 8 38400 baud 5 Prt Bit de paridad Modbus 0 sin paridad 1 paridad par even 2 paridad impar odd 0 Ald Tiempo de retraso se alizaci n y visualiz...

Page 21: ...Ajuste de entrada INP 1 8 Entrada nocturna ahorro de energ a N O 7 Detener la descongelaci n desde el control remoto N O se toma el flanco ascendente del pulso 6 Inicio de descongelamiento remoto N O...

Page 22: ...Compruebe la absorci n del compresor Si el problema persiste contacte con el servicio de asistencia t cnica Ed Alarma de puerta abierta A la abertura del microporta y a pasado el tiempo tdo es restab...

Page 23: ...i definire un valore di temperatura minima all ambiente da refrigerare Al di sotto del valore A1 sar segnalato lo stato di allarme con il led di allarme lampeggiante la temperatura visualizzata lampeg...

Page 24: ...bus bit di parit 0 nessuna parit 1 parit pari even 2 parit dispari odd 0 Ald Tempo di ritardo segnalazione e visualizzazione allarme di minima o massima temperatura 0 240 min 120 min C1 Tempo minimo t...

Page 25: ...sparmio energetico con In1 o In2 8 o 8 Durante il funzionamento notturno il Set di regolazione Set regolazione Set nSc In mod notte il punto decimale lampeggia 20 0 20 0 C 0 0 C In1 Impostazione ingre...

Page 26: ...Le uscite sono tutte disattivate tranne quella di allarme Verificare lo stato del compressore Verificare l assorbimento del compressore Se il problema persiste contattare il servizio d assistenza tec...

Page 27: ...Pag 27 ECP202 BASE Parameters Abstract Rev 01 21...

Page 28: ...Via Piacentina 6 b 45030 Occhiobello ROVIGO ITALY Tel 39 0425 762906 e mail info pego it www pego it AFTER SALES ASSISTANCE Tel 39 0425 762906 e mail tecnico pego it Distributor PEGO s r l reserves th...

Reviews: