DIAGNOSTIC
In the event of a fault the
PLUS300 EXPERT U THR
controller warns the operator by
displaying an alarm code and emitting a warning sound via the buzzer inside the control
console.
If alarm conditions arise, the display will show one of the following messages:
ALLARM
CODE
POSSIBLE CAUSE
OPERATION TO BE PERFORMED
E0
Temperature sensor fault
Check the room temperature
sensor.
If the problem persists replace the
sensor.
E1
Humidity sensor fault
Check the humidity sensor.
If the problem persists replace the
sensor.
E2
Defrost sensor fault
(In this case eventual defrosts will last as d5)
Check the defrost sensor.
If the problem persists replace the
sensor.
E3
Eeprom alarm
An error in the EEPROM memory has been
detected.
(all output deactivated except the alarm ones)
Switch system off and back on
again.
E4
Software compatibility error
Check for proper match between
MASTER board and console
board.
E6
Flat battery alarm
Replace lithium battery (CR2032
type) of the Console.
Ec
General alarm
(e.g. overheat or max pressure
switch)
(All outputs, except alarm, if present, are
deactivated)
Check compressor absorption.
If the problem persists, to contact
the technical assistance service.
En
No connection between the Console and the
MASTER
board.
Check the connection between
the two units.
If the problem persists, to contact
the technical assistance service.
Eu
Minimum or maximum humidity alarm.
A humidity higher or lower to that set for minimum or
maximum humidity alarm has been reached in the
ambient (
See variables AU1 and AU2, user
programming level
)
Check humidity management.
The probe does not correctly
detect the humidity.
Et
+
Temperature
on display is
flashing
Minimum or maximum temperature alarm.
A temperature higher or lower to that set for
minimum or maximum temperature alarm has been
reached in the ambient (
See variables At1 and At2,
user programming level
)
Check the compressor status.
The probe incorrectly detects the
temperature or the stop/start
control of the compressor does
not work.
Ed
Limit Timeout for dehumidification
Check humidity management.
The probe does not correctly
detect the humidity.
CHAPTER 8: DIAGNOSTIC