PLUS
300 EXPERT
U THR
Pag. 21
USE AND MAINTENANCE MANUAL
Rev. 01-18
VARIABLES
MEANING
VALUES
DEFAULT
CIC
CIC = 0 at the end of the last program
phase (phase 5) it moves to manual.
CIC = 1 at the end of the last timed phase
(phase 5) it returns to initial phase (phase
0). An infinite loop of the phases is therefore
created.
CIC = 2 at the end of the last program
phase (phase 5) it moves on to the
subsequent program.
0 = it ends the program and
moves on to manual.
1 = loop phases
2 = calls subsequent program
0
Sgt
Phase 0 or dripping phase temperature
setpoint
-45 ÷ +45°C
0
SgU
Phase 0 or dripping phase humidity setpoint
0...99 rH%
0= disabled
60%
Sg
Dripping enabling
0 = normal functioning
1 = hot only enabled
2 = hot, cold only enabled
0
Sgr
Refreshment
0= NO
1= YES
0
vSg
Dripping phase evaporator fans speed.
Amends the value of 2nd level variable (F8)
0 = High speed
1 = Low speed
(only if rin=1)
0
tSg
Dripping phase duration
0:00...99:30
(30 min steps)
0:00
St1
Phase 1 temperature setpoint
-45 ÷ +45°C
0
SU1
Phase 1 humidity setpoint
0...99 rH%
0 = Disabled
60
rn1
Phase 1 refreshment
0 = NO
1 = YES
0
v1
Phase 1 evaporator fans speed. Amends
the value of 2nd level variable (F8)
0 = High speed
1 = Low speed
(only if rin=1)
0
t1
Phase 1 duration
0:00...99:30
(30 min steps)
0:00
St2
Phase 2 temperature setpoint
-45 ÷ +45°C
0
SU2
Phase 2 humidity setpoint
0...99 rH%
0 = Disabled
60%
rn2
Phase 2 refreshment
0 = NO
1 = YES
0
v2
Phase 2 evaporator fans speed. Amends
the value of 2nd level variable (F8)
0 = High speed
1 = Low speed
(only if rin=1)
0
t2
Phase 2 duration
0:00...99:30
(at 30 min steps)
0:00
St3
Phase 3 temperature setpoint
-45 ÷ +45°C
0
SU3
Phase 3 humidity setpoint
0...99 rH%
0 = Disabled
60%