Guidelines

 

 

The PDI-772HE-IND is a specialized power supply designed to power low-voltage AC small screen televisions and 
is intended for use in a hospital, a nursing home, a medical-care center, or a similar healthcare facility in which 
installation is limited to a non-hazardous  area in accordance with the National Electrical Code ANSI/ NFPA70. 

 
This installation should be made by a qualified service person and should conform to all local codes.  
Do not attempt this installation without an assistant. 
 

 

Location 

The supply is mounted in a utility or electrical closet near an AC wall outlet.  Due to coaxial cable length 
restrictions, select a location that limits the longest coaxial cable run, that is the distance between the supply and 
furthest room, to a maximum of 150 feet. Refer to the section titled 

CATV Wiring 

for coax cable 

recommendations. 
 

Cooling 

This power supply is engineered for high efficiency. Please observe these guidelines. 

1.

 

Select a location with a maximum ambient room temperature of less than 100°F. 

2.

 

Allow a minimum  clearance distance of 8 inches on top, bottom, and both sides of the power supply cabinet. 
This clearance is required for cooling.  Do not cover or obstruct ventilation grills on the cabinet as this 

supply utilizes convection cooling.  For example, the supply should NOT be mounted  in a drop ceiling due to 
the restricted airflow that occurs in such a tight air space. 

3.   Do not route cables between the wall and back of the power supply.  The back of the supply must be kept 

clear to allow for convection air cooling. 

4.   The supply when under full load will generate approximately 110 watts of waste heat.  Please consider the 

installed location

s additional temperature rise caused by operation of this supply. 

 

Electrical 

This power supply requires a 120 VAC circuit capable of supplying 10 amperes of current.  Do NOT use an 
extension cord with this power supply. 

 

 
 

 

 

Summary of Contents for PDI-772HE-IND

Page 1: ...in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment...

Page 2: ...t exhibits a distinct change n performance which indicated a need for service Replacement Parts When replacement parts are required be sure the service technician has used replacement parts specified...

Page 3: ...It is not intended for mobile operation Do not use this product with a cart 13 Unplug this apparatus during lightning storms or when unused for long periods of time 14 Refer allservicing to qualified...

Page 4: ...set top satellite box a cable box or other similar RF device to be directed to one specific television Please refer to the schematic ACline voltage is stepped down using an isolation transformer inco...

Page 5: ...ance betweenthe supply and furthest room to a maximum of 150feet Refer to the section titled CATV Wiring for coaxcable recommendations Cooling This power supply is engineered for high efficiency Pleas...

Page 6: ...nt on a wall in an upright position with the power cord pointing down The supplyshould be positioned near an ACwall outlet This unit is convection cooled and requires clearance at the top bottom and s...

Page 7: ...style coaxcable This style of coaxcan be easily confused with a pure copper coaxas the steelcenter conductor is platted with a copper cladding it looks likecopper Asa test touch a magnet to the cente...

Page 8: ...binet and detach the ventilation cover exposing the RF F connector rows 3 Connect the RF signal cable from the satellite or set top box to the RF IN F connector Top Row Note Be sure the center conduct...

Page 9: ...eeper and insert the IEC power cord plug into the ACjacklocated on the bottom of the power supply Press and seat the plug keeper onto the body of the plug 2 Now insert the ACpower cord plug into a pow...

Page 10: ...s connected to the RFOUT F connector on the bottom row of the central power supply Wrong coaxcable used see CATV Wiring Poor reception or No Picture Station or CableCompany experiencing problems tune...

Page 11: ...ifaffixed to any attachment not specified for the product 2 Product that has either the model number or serialnumber altered tampered with defacedor removed 3 Initial installation and removal for rep...

Page 12: ...Reach MODEL NUMBER PDI 772HE IND Document Number PD196 181R3 Individual Input Port Central Power Supply Page 12 of 12 PDi Communication Systems Inc 40 Greenwood Lane Springboro Ohio 45066 USA PH 1 80...

Reviews: