background image

9                                                                                                                                          10 

 

that subdivision of large installations might be necessary 
because  of  the  large  number  of  parallel  insulation 
resistance. In such a case, an installation may be divided 
into sections, each being separately tested. Each section 
must  have  not  less  than  fifty  outlets,  an  outlet  being  a 
switch,  socket,  lighting  point  etc.  A  switched  socket 
counts as one outlet. The minimum acceptable insulation   
resistance  is  1M

.  For  a  large  installation,  the 

capacitance of the insulation will be high, and it will take 
longer  for  it  to  become  charged  by  the  direct  testing 
voltage.  Care  must  be  taken  not  to  take  a  reading  until 
there  is  a  steady  reading,  indicating  that  the  charging 
process is complete. 

Note: 

The charge stored in the insulation will be discharged 
automatically  when  the  test  button  is  released.  Be 
careful not to turn the range switch knob whilst the test 
button is pressed, or the instrument will be damaged. 

 

b). Measurements at 2000M

/1000V 

Some specifications require testing at 1000V. This voltage 
must  also  be  selected  where  the  supply  voltage  of  the 
installation  is  between  500V  and  1000V.  First,  set  the 
range switch to 1000V and then proceed as indicated in a 
above  for  500V  testing.  The  above  note  also  applies  to 
testing at 1000V. In addition the following applies. 

Note:

  Make  sure  that  the  circuit  under  does  not  include 

components  Which  will  be  damaged  by  the  1000V 
applied.  Many  normal  components  of  an  installation  are 

likely  to  be  damaged  if  tested  at  1000V.  Examples  are 
power  factor  correction  capacitors,  low  voltage  mineral 
insulated  cables,  electronic  light  dimmers,  electronic 
ballasts and starters for fluorescent lamps etc… 

 

c). Lock power on Feature   

For  hands  free  operation  a  lock  power  on  feature  is 
incorporated on the press to test button. Set LOCK button 
to lock test voltage, Pressing it again will tester off. 

 

5.  LOW RESISTANCE (CONTINUITY) 

MEASUREMENTS 

a). Set the range switch to 200

 

·

))) Position 

b). Connect the red test lead to the V 

 terminal and black to 

the COM terminal. 

c).  Connect  the  tips  of  the  test  leads  to  both  ends  of  the 

circuit under test. read resistance in 

 on the LCD. 

d). When the impedance on circuit is below approximately 

40

.It will indicate by a continuous beeper. 

 

6.  AC/DC VOLTAGE MEASUREMENTS 

a). Set the range switch to ACV or DCV position 
b). Connect red test lead to “V 

” terminal and black test lead 

to terminal “COM”. 

c).  Connect  test  prods  of  test  leads  IN  PARALLEL  to  the 

circuit being measured. 

d). Read the voltage value on LCD. 

Summary of Contents for PCE-IT55

Page 1: ...se extreme caution when working around bare conductors or bus bars Accidental contact with the conductor could result in electric shock Use the meter only as specified in this manual otherwise the pro...

Page 2: ...Periodically wipe the case with a dry cloth Do not use abrasives or solvents on this instruments Display Large LCD with dual display Measurement Range 200 200k 200M 250V 200M 500V 2000M 1000V 750V ACV...

Page 3: ...ance 40 4 5V 250Vrms Short circuit current 200mA DC Voltage Range Resolution Accuracy Input Impedance Overload Protection 1000V 1V 0 8 3 10M 1000Vrms AC Voltage 40Hz 400Hz Range Resolution Accuracy In...

Page 4: ...f 6 pcs new batteries type 1 5V size AA is Required b Place back the battery cover and four the screws 3 3 Test leads check Set the range select switch to the 200 range With the tip and alligator clip...

Page 5: ...00V and then proceed as indicated in a above for 500V testing The above note also applies to testing at 1000V In addition the following applies Note Make sure that the circuit under does not include c...

Page 6: ...include the resistance of the motor wire and all other components between the motor and the main switch If a weakness is in dicated the motor and other components should be checked individually If th...

Page 7: ...from other equipment Check each conductor to ground and or lead sheath by connecting one megohmmeter lead to a ground and or lead sheather and the other megohmmeter lead to each of the conductors in...

Reviews: