5 SAFETY RULES:
Before starting to work:
• Disconnect
• Secure against restarting
• Check that no voltage is present
• Ground and short-circuit
• Cover or short-circuit
surrounding parts that are under
voltage or fence off
6.4 Conditions for the electrical
connection
Specifications for the sub-distribution:
k
Each charging point must have its own supply line
with appropriate fuse protection.
k
The wallbox needs a suitable line circuit breaker
and residual current circuit breaker.
k
Since the wallbox already has a DC fault detection
>6mA, you do not need a RCD type B.
k
If possible, use overvoltage protection in the sub-
distribution.
k
Observe the labeling of the connection terminals
(L3, L2, L1, N, PE).
k
Use the cable cross-sections specified in the table.
NOTE
The charging station does not have its own
mains switch. The circuit breaker of the supply
line serves as the mains disconnection device.
Clampable conductors (rated connection)
Conductor cross-section AWG
min. AWG 12 / max. AWG 28
Conductor cross-section, solid
min. 0,5mm² / max. 2,5 mm²
Conductor cross-section, flexible with end sleeves
with plastic collar DIN 46228/4
min. 0,5mm² / max. 2,5 mm²
Material
Wemid
Color
dark beige
Flammability class according to UL94
V-0
Continuous service temperature
min. -60°C / max. 130°C
Terminals used:
Manufacturer:
Weidmüller Interface GmbH & Co KG
Make:
Klippon®Connect
Product Family:
A-Series
Type:
A4C 2.5
Rated data
Rated cross section:
2,5 mm²
Rated voltage:
800 V
Rated impulse withstand voltage:
8 kV
Rated current:
24 A
Power dissipation:
0,77 W
Standards:
IEC 60947-7-1
Current at max. conductor:
24 A