1
1
2
2
3
3
4
4
A
A
B
B
CODE
IDENT. NO.
52681
DWG. NO.
SCALE:
SHEET
DRAWN
CHECKED
ENGINEER
TITLE
UNLESS OTHERWISE SPECIFIED
DIMENSIONS ARE IN INCHES
DECIMALS X
.05
XX
.01
XXX
.005
ANGLES ± 2 DEGREES
FILLETS AND RADII .003 - .005
HEX DIMENSIONS ARE:
≤
.5 + .000 / - .003
> .5 + .000 / - .005
REMOVE ALL BURRS
SHARP = R.000 - R.003
INTERNAL THREAD DEPTH MIN.
3425 WALDEN AVE. DEPEW, NY 14043
(716) 684-0002 E-MAIL: [email protected]
61680
CSA APPROVAL
615A42
INTERCONNECTIONS
1 OF 1
NONE
XXXX
.0005
BB
10/19/15
ECB
10/19/15
PML
10/19/15
b
b
e
h
rin
g
e
r
0
8:
17
10
/1
9/
20
15
NON-HAZARDOUS / SAFE AREA
HAZARDOUS AREA
-
+
SENSOR
=
<
VIN 30V
AMPLIFIER
SHIELD
BARRIER
CABLE
TRANSDUCER
61
68
0
PCB Piezotronics Inc. claims proprietary rights in
the information disclosed hereon. Neither it nor any
reproduction thereof will be disclosed to others
without the written consent of PCB Piezotronics Inc.
REVISIONS
REV
DESCRIPTION
DIN
NR
RELEASED TO DRAFTING
43970
SCHEDULE DRAWING
NO MODIFICATIONS PERMITTED
WITHOUT REFERENCE TO THE
NOTIFIED BODY
Ci AND Li BASED ON CABLE WITH 30 pF/ft AND .33
µ
H/ft WITH A MAXIMUM CABLE LENGTH OF 100ft.
Ci AND Li WILL BE DECREASED WITH SHORTER CABLE LENGTHS.
SHIELDS TO BE EARTHED AT BARRIER END.
THE INSTALLER SHALL INSURE THAT THE TRANSDUCER MOUNTING
STRUCTURE IS AT THE SAME GROUNDING POTENTIAL AS THE BARRIER
GROUND. TOTAL EARTH LOOP IMPEDANCE SHALL BE LESS THAN
ONE OHM.
BARRIER WILL BE MOUNTED IN AN ENCLOSURE THE SUITABILITY
OF WHICH WILL BE DETERMINED BY LOCAL AUTHORITIES.
ENTITY APPLICATION:
Barrier I.S. Apparatus
Voc/Uo < V /Ui
Isc/Io < I /Ii
Ca/Co < Ci + C
La/Lo < Li + L)
BARRIERS WITHIN THE SPECIFIED LIMITATIONS ARE PERMITTED.
ENTITY PARAMETERS:
Ui <= 30 V
Ii <= 100 mA
Pi <= 0.7 W
Ci <= 15 nF
Li <= 30
µ
H
CERTIFIED BY THE APPROPRIATE APPROVAL AUTHORITY FOR CONNECTION
TO THE FOLLOWING AREAS:
CLASS 1 DIVISION 2
5
4
3
2
1
5
5
CAUTION
ELECTROSTATIC
DISCHARGE SENSITIVE
2
4
1
3
T-CODE
AMBIENT
T2
-55°C TO 260°C
T3
-55°C TO 195°C
T4
-55°C TO 130°C
T5
-55°C TO 95°C
T6
-55°C TO 80°C